NAVY MIL-W-19150 B-1977 WIRE INSULATED HARD DRAWN COPPER《冷拔出加工铜绝缘线》.pdf
《NAVY MIL-W-19150 B-1977 WIRE INSULATED HARD DRAWN COPPER《冷拔出加工铜绝缘线》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-W-19150 B-1977 WIRE INSULATED HARD DRAWN COPPER《冷拔出加工铜绝缘线》.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、P! I L-W- I 9 I 506 ( OS 1 I I February 1977 5upersedinq MILITARY SPECIFICATION M I L -W - I 9 i 5A Piep 1 30 January 1962 W I RE, I NSULATED, HARD DRAWN COPPER This specification is approved for use by the Naval Sea Systems Command, Department of the Navy, and is available for use by all Department
2、s and Agencies of the Department of Defense. /- I. SCOPE 1.1 Scope. This specification covers procurement of a special purpose, hard drawn copper conductor, polyethylene-insulated, nylon- jacketed wire. 2. APPLICABLE DOCUMEiJTS * 2.1 Issues of documents. The following documents of the issue in effec
3、t on date of invitation for bids or request for proposal form a Dart of this specification to the extent specified herein. SPECIFICATIONS Federa I * L-P-390 QQ-W - 343 Mi I itary MI L-R-324 I STANDARDS Mi I i taiy MI L-STD- I05 Plastic, Molding and Extrusion Material, Polyethylene and Copolymers (Lo
4、w, Medium and High Density) Wi re, E lectr ica I and FJoneI ectr ica I Copper ( Un i nsu I ated 1 Reels, Cable (Reels DR-5, DR-7, DR-15-B, RL-I59/U) Sampling Procedures and Tables fcir Inspection by Attributes Goneficial comments (recommendations, additions, deletions) and dny pertinent data which m
5、ay be of use in improving this document should be addressed to: Commanding Officer, Naval Ordnance Station, Standardization Division (611), Indian Head, Marytand 20640 by using the self-addressed Ctandardiza- tion Document Improvqmerit Proposal (DD Form 14?6) appearinq . at the end of this document
6、or by letter., Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-W-LSLSOB bL W 7797706 0087508 3 W - Conduc- tor size M I L-W-I 9 I 5OB(OS 1 Diameter of Po I yethy Iene Na I I Diameter of Insulated Rare Conductor Th i cknecs Conductor -1 I I I I I
7、MIL-STD-129 Marking for ShiDment and Storage #I9 #24 (Copies of specifications, standards, drawings and publications required by contractors in connection with specific procurement functions should be obtained from the procuring activity or as directed by the contracting officer.) 0.0355 0.3359 0.03
8、63 0.009 0.011 0.013 0.0535 0.0579 0.062 0.0199 0.0201 0.0203 0.008 0.011 0,016 0.040 0.0421 0.044 3. REOUIREMENTS 3. I Description. The wire described by this specif ication consists of a solid hard drawn copper conductor insulated with polyethylene and jacketed with nylon. 3.2 General requirements
9、. 3.2.1 Materials. Unless otherwise specified in the contract, requi- sition, or order, all materials shall conform to the requirements listed below. 3.2. I. I Conductor. The conductor shal I be hard-drawn copper in accordance with 00-W-343. The conductor shall be continuous and free from splices. 3
10、.2.1.2 Insulation. The insulation shall consist of extruded, * heat stabilized, non-oxidizing polyethylene compound in accordance with L-P-390, Type II, Grade 7. There shall be no repairs or patches in the insulation. 3.2.1.3 Jacket. The jacket shall consist of a transparent, heat stabilized, non-ox
11、idizing polyamide (nylon), applied over the polyethy- !ene-insulated conductor by a continuous extrusion process to insure a smooth, tight-fitting, flexible and abrasion resistant covering. There shall be no repairs to or patches in the jacket. 3.2.2 Dimensions. Wire lengths will be specified in the
12、 contract, recuisition, or order. Other dimensions shall conform to TABLE I and wi II be specif-iec! in the contract, requisition, or prder. TABLE I. Homi na II il II 1. 2 o Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-W-LS15OB 61 111 7777906
13、0087509 5 = DC Resistance OHMS/M Ft Max at or cor- rected to 2OoC (68OF) 8.5 , TABLE I (CONTINUED) c. Tensile Strength Lbs.,Min. 32 Nom i na Cond uc. tor Size (AWG) Min. 0.004 #I9 #24 Nom. Max. Min. Nom. Max. 0.0055 0.0065 0.066 0,0689 0.072 . Nylon Wall Thickness Diameter of Finished I Wire 0.003 I
14、 0.0055l 0.009 I 0.050) 0,0531 10.056 I I 1 27.0 I 20 I 3.2.3 Gages. The contractor shall provide himself with whatever gages are necessary and adequate for manufacture use to insure that the wire will meet the dimensional requirements of Table I, 3.2.4 Marking. Each length of wire shall be assigned
15、 a designating - serial number polyethylene insulation. This number shal I identify the length of wire throughout the jacketing process, testing and shipping. a tag containing the following information will be secured to the wire: (I), the AWG size; (21, the serial number; (31, the total footage; (4
16、1, the conductor resistance per thousand feet; and (51, the insulation resistance per thousand feet of wire. by the contractor immediately after the application of the Prior to packaging, 3.2.5 Conflicting requirements. Conflicting requirements arising between this sDecification and any specificatio
17、ns, publications, or drawings 1 isted herein shal I be referred in writing to the procuring agency or appointed agent for interpretation and clarification. 3.3 Performance. The fol lowing performance rebuirements shal I aDply to the insulated and jacketed wire. 3.3.1 Direct-Current Resistance. The.w
18、ire shall meet the D.C. resistance requirements of TABLE I. 3.3.2 Insulation and Jacket. The insulation and jacket shall be applied in such a manner that they are concentric with the conductor (see TABLE I). The insulation and jacket shall be free from splinters, blisters, and other non-homogeneitie
19、s visible to the normal eye. 3.3.2.1 Spark. The insulated wire shall withstand without breakdown, both before and after jacketing, the dry spark-test voltage specified in 4.3.2. I. 3.3.2.2 Dielectric Strength. The completed wire shall withstand without breakdown the dielectric strength test specifie
20、d in 4.3.2.3. 3.3.2.3 Insulation Resistance. The completed wire shall exhibit an insulation resistance of no less than 20,000 megohms per thousand feet of wire. o _. 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-M I L-We.19 I 50B(OS 1 3.3.3 Tensi
21、le Strength. The insulated and jacketed wire shall meet the minimum tensile strength requirements of TABLE 1. 4. QUALITY ASSURANCE PROVISIONS 4.1 Responsibility for inspection. Unless otherwise specified in the contract or purchase order, the supplier is responsible for the performance of all inspec
22、tion requirements as specified herein. Except as otherwise specified in the contract or order, the supplier may use his own or any other facilities suitable for the performance of the inspection requirements specified herein, unless disapproved by the Government. inspections set forth in the specifi
23、cation where such inspections are deemed necessary to assure supplies and services conform to prescribed requirements. of product, the term llotl shal I mean “inspection lot“, i .e., a col lection of units cf product submitted by a supplier for government inspection. Unless oi-herwise specified, the
24、 number of units of product in “inspection lots“ shall be as determined by the government inspector and may differ from the quantity designated in the contract or order as a lot for production, shipment, or other purpose. * The Government reserves the right to perform any of the 4.1.1 Lot Size. As a
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILW19150B1977WIREINSULATEDHARDDRAWNCOPPER 拔出 加工 绝缘线 PDF

链接地址:http://www.mydoc123.com/p-983199.html