1、This amendmen .MILITARY SPECIFICATION REGULATORS, LINE VOLTAGE, SINGLE PHASE, -400 HERTZ A.C. NAVAL SHIPBOARD fi- +8, line 3: Delete “3.3.8.2 and substitute “3.3.8.3“. 3.3.8.1, items (a) and (b): Delete and substitute: “(a) Single-phase or three-phase wye (4Lwire); 3.5 percent for 150 ampere and 225
2、 ampere regulators; 6 percent for 75 ampere regulators: 6 percent for 20 “(b) Three-phase delta: 6 percent for 150 ampere and 225 ampere regulators: 10 percent for 75 ampere regulators; 10.5 percent for 20 ampere and 40 ampere regulators.“ - ampere and 90 ampere regulators. 3.3.8.2: Delete. 3.3.8.3,
3、 make the following changes: (a) Line 1, heading, after “slope“, add: “(steady-state).“ (b) Line 6, delete8 “both“; delete “and dynamic“. .- (c) Line.7, delete: “and 3.3.8.2“. Page 8 3.3.9, lines 2 and 8: 3.3.11.1, delete and substitute: Delete “35 milliseconds“ and substitute “100 milliseconds“. .“
4、3.3.11.1 KvA efficiency. “3.3.11.1.1 KVA efficiency of each equipment connected in a three-phase four-wire wye system shall be at least 70 percent at any load between 60 percent load and rated full load, at 0.75 lagging and unity power factor. “3.3.11.1.2 KVA efficiency of each equipment connected i
5、n a three-phase delta system shall be at least 60 percent at any load between 60 percent load and rated full load, at 0.75 lagging and unity power factor.“ Page 9 3i5.3, line 1: Delete “A“ and substitute “P. Page 2 of 6 I Provided by IHSNot for ResaleNo reproduction or networking permitted without l
6、icense from IHS-,-,-MIL-R-23098A (b) bL m 999990b 0088804 L MIL-R-2309 8A (SH) AMENDMENT-6 3.5.3.1, lines 1 and 2: Delete and substitute: “3.5.3.1 Cate or F, evaluation and procurement. Category F drawings shall contain the following m under column “3 phase delta“, opposite “Dielectric strength“ del
7、ete “X“ and substitute “-“; make the following changes under-column “3 phase wyel“: Table V, under column “1 phase“; opposite “Dielectric strength“ delete “-“ and substitute I P E !. . Opposite “Input voltage transient“ delete “-“ and siibstitute-“X“. Opposite “Output voltage transient“ delete “-* a
8、nd substitute wXm, Opposite “Output voltage build-up“ delete I-. and substitute “X“. Opposite “Output voltage modulation“ delete O-“ and substitute “Xu. Opposite “Output voltage modulation gain“ delete and substitute “X“. Opposite “No load input excitation current“ delete “-“ and substitute “X“. . O
9、pposite “Slope of no load input excitation current versus input voltage“ - delete “-“ and substitute “X“. Page 3 of 6 I- , Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-h) (i) Opposite “Efficiency“ delete and substitute “X“. -j) Opposite Waveform d
10、istortion“ delete *-“ ana substitute X“. Delete “Inclined operation“, and all references thereto. i;: Page 17 f: _. 4.5.2, line 2: 4.5.5.1, first sentence: Delete “MIL-E-2306“ and substitute “tIIL-E-2036“. Delete and substitute: “Heating tests shall be performed in I - accordance with the operationa
11、l configuration of 3.3.2(a), with line voltage regulators interconnected in a balanced three-phase delta system at 105 percent rated input voltage under conditions of rated full load output line current (balanced) at unity power factor.“ Page 18 P- 14 . Add as paragraph 4.5.6.1: 4.5.6.1 Grou A. When
12、 steady-state voltage regulation tests are performed at test condition Nos. *3 of table VII, in accordance with the group A procedure of 4.5.7.1, a broadband measurement of sound pressure level shall be conducted by means of a microphone positioned at a single point 3 feet in front of the regulator
13、equipment. Instrumentation. used in the performance of broadband measurement of sound pressure level shall Conform to MIL-STD-740. The single point observation of broadband noise shall demonstrate that the equipment does not produce any acoustic noise emission in excess of 65 decibels (db) referred
14、to 0.0002 microbar sound pressure level. noise test in accordance with 4.5.6 shall be conducted .to determine conformance with the requirements of 3.2.3.“ . . In the event that this noise level is exceeded, a Page 19 Table YII: Add the following: I Provided by IHSNot for ResaleNo reproduction or net
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILR23098A61976REGULATORSLINEVOLTAGESINGLEPHASE400HERTZACNAVALSHIPBOARD400 赫兹 交流 海军 舰载 单相 电压 调节剂

链接地址:http://www.mydoc123.com/p-981169.html