NAVY A-A-50624-1994 AIRFLOW MONITORING EQUIPMENT《气流监控设备》.pdf
《NAVY A-A-50624-1994 AIRFLOW MONITORING EQUIPMENT《气流监控设备》.pdf》由会员分享,可在线阅读,更多相关《NAVY A-A-50624-1994 AIRFLOW MONITORING EQUIPMENT《气流监控设备》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、A-A-50624 m 9999974 0364820 080 m A-A-50624 9 June 1994 COMMERCIAL ITEM DESCRIPTION AIRFLOW MONITORING EQUIPMENT The General Services Administration has authorized the use of this commercial item description in preference to MIL-S-16032M. Abstract. This Commercial Item Description covers requirement
2、s for airflow monitoring equipment that measures and provides a display of airflow velocity, and generates alarms whenever airflow velocity drops below a predetermined level. Integral components include an airflow sensor and an associated airflow display panel. The equipments are intended for use in
3、 virtually any air ventilation system including those which service hazardous material stowage compartments where impeded airflow could result in dangerous conditions. Salient characteristics. 1. Airflow monitoring svstem. The detailed requirements for airflow sen- sors and airflow display panels bu
4、ilt in accordance with this CID are described in sections (2) and (3) below respectively. The basic performance requirements of an airflow monitoring system comprised of an airflow sensor and airflow display panel built in accordance with this CID are as follows: a. Range. The airflow system shall a
5、ccommodate selectable subranges within an overall airflow range of from O to 50 meters per second (mps). b. Accuracv. Airflow velocity measurement accuracy shall be within f (3.0 percent of reading plus 2.0 percent of full-scale). Low-airflow alarm point detection accuracy shall be within: rt (6.0 p
6、ercent of the selected low-airflow point plus 1.0 percent full-scale). I 1 Beneficial comments, recommendations, additions, deletions, clarifications, etc. and any other data which may improve this document should be sent by letter to: Commander, Naval Sea Systems Command, ATTN: SEA 05442, 2531 Jeff
7、erson Davis Hwy., Arlington, VA 22242-5160. FSC 6680 AMSC N/A DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited. Licensed by Information Handling ServicesA-A-50624 c. Response time. When operated in a standard one-atmosphere ambient environment with an airflow velocity
8、 of 25 percent of full-scale, the airflow monitoring system shall achieve a full-accuracy output signal and full-accuracy display readout within 12 seconds for an airflow velocity step increase of from 30 to 75 percent full-scale. d. Repeatability. Airflow monitoring system repeatability shall be to
9、 within tr 1.5 percent of full-scale. 2. Airflow sensor. a. Required operating: principle. The sensor shall employ a thermal anemometer technique for sensing airflow. b. Physical characteristics. The sensor shall consist of a cylin- drical probe and an attached/integral electronics processing packag
10、e. The sensor probe shall be constructed of corrosion resistant material. shall be from 1.0 cm to 2.6 cm in outside diameter. appropriate for the cylindrical or rectangular duct size as specified. A mounting plate shall be provided to secure the sensor to the air duct. The sensor shall be readily re
11、movable from the mounting plate (to facilitate periodic cleaning). The sensor probe The probe length shall be c. Power input. The airflow sensor shall be powered by +15 to +18 Vdc and shall draw no more than 350 mA. d. Airflow Range. The airflow velocity range of the sensor shall be from zero mps to
12、 the full-scale mps value as specified. e. Output signal. The airflow sensor shall output a 4-20 mA signal linearly proportional to airflow velocity. A 4 mA output shall correspond to zero airflow velocity and a 20 mA output shall correspond to full-scale airflow velocity. The sensor shall drive a r
13、esistive load of 250 ohms t 5 percent. f. Accuracy. The airflow velocity output signal shall be accurate to within f (3.0 percent of reading plus 1 percent of full-scale). g. Repeatability. Repeatability shall be to within i 0.5 percent of full-scale. h. Response time. velocity change. When operatin
14、g in a standard one- atmosphere environment and an airflow velocity of 25 percent full-scale; the airflow sensor shall achieve a full-accuracy output signal within 10 seconds for an airflow velocity step increase to 75 percent full-scale, i. ResDonse time. temperature change. When operated in a stan
15、dard one-atmosphere environment and an airflow velocity of 50 percent full-scale; the airflow sensor shall achieve a full-accuracy output signal within four minutes for a 20 degrees Celsius (OC) temperature step increase. 2 Licensed by Information Handling ServicesA-A-50624 9999974 OLL14822 953 A-A-
16、 50624 j. Interface with airflow disDlav Danel. The airflow sensor shall connect to the airflow display panel via a three-conductor cable of a length as specified. One conductor shall carry the airflow signal, one conductor the dc power, and one shall be a common conductor. The cable shall be detach
17、able from the airflow sensor via an accessible screw-lug terminal located inside the airflow sensor assembly. The screw-lugs shall be marked as to function. k. Reliabilitv. The airflow sensor minimum mean time between failures (MTBF) shall be no less than 25,000 hours. 1. Safety (hazardous environme
18、ntl. The airflow sensor shall be in compliance with the NEC requirements for safe use in Class I, Division 2, Group D hazardous locations. 3. Airflow disDlay Danel a. Physical Characteristics. The airflow display panel shall not exceed the following outside dimensions: 33 cm in width, 28 cm in heigh
19、t, and 25.4 cm in depth (including any attached mounting pads). bulkhead mountable via the hole pattern as specified. matching the panel to the specified hole-pattern may be used.) The panel shall be corrosion resistant. The panel shall incorporate a swing-open panel door with an identification plat
20、e affixed on the outside of the panel door and labeled as indicated. The panel shall be (An adapter plate for b. Range. The airflow range of the panel shall be manually selectable. Selectable ranges shall include: O - 1 mps O - 2.5 mps O - 5 mps O - 10 mps O - 25 mps O - 50 mps c. Input signal. The
21、airflow panel shall accept a 4-20 mA signal linearly proportional to airflow velocity. airflow velocity and a 20 mA output shall correspond to full-scale airflow velocity. percent. A 4 mA output shall correspond to zero Input impedence for the signal shall be resistive at 250 ohms f 1 d. Airflow dis
22、play. The panel shall incorporate an illuminated digital readout. setting in meter-per-second (mps) on a selectable basis. Airflow velocity displayed shall be mean airflow velocity for the most recent one-second interval. The digital readout shall display airflow velocity or trip point e. Trip-DOint
23、 set. The panel shall enable the setting of a low- airflow alarm trip-point for any value in the selected airflow range. shall detect whenever airflow velocity drops below the trip-point setting for a period of 30 f 5 seconds and shall set a low-airflow alarm state accordingly. The panel shall retai
24、n memory of the trip-point setting at all times, including power loss times. The panel 3 Licensed by Information Handling ServicesA-A-50624 9999974 OLb4823 89T D A-A- 50624 f. Audible alarm. The panel shall incorporate an audible alarm which generates an audio output of from 75 to 95 dB at two feet.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYAA506241994AIRFLOWMONITORINGEQUIPMENT 气流 监控 设备 PDF

链接地址:http://www.mydoc123.com/p-976321.html