ISA RP31 1-1977 Specification Installation and Calibration of Turbine Flowmeters《涡轮流量计的安装和校准规范》.pdf
《ISA RP31 1-1977 Specification Installation and Calibration of Turbine Flowmeters《涡轮流量计的安装和校准规范》.pdf》由会员分享,可在线阅读,更多相关《ISA RP31 1-1977 Specification Installation and Calibration of Turbine Flowmeters《涡轮流量计的安装和校准规范》.pdf(38页珍藏版)》请在麦多课文档分享上搜索。
1、Specification, Installation,and Calibration of Turbine FlowmetersApproved 30 April 1977ISARP31.11977RECOMMENDED PRACTICEISA The Instrumentation,Systems, andAutomation Society TMCopyright 1977 by the Instrument Society of America. All rights reserved. Printed in the UnitedStates of America. No part o
2、f this publication may be reproduced, stored in a retrieval system, ortransmitted in any form or by any means (electronic, mechanical, photocopying, recording, orotherwise), without the prior written permission of the publisher.ISA67 Alexander DriveP.O. Box 12277Research Triangle Park, North Carolin
3、a 27709ISARP31.11977, Specification, Installation, and Calibration of Turbine FlowmetersISBN 0-87664-371-3ISA-RP31.1-1977 3PrefaceThis preface is included for informational purposes and is not part of Recommended Practice ISA-RP31.1-1977.This Recommended Practice has been prepared as part of the ser
4、vice of ISA toward a goal of uniformity in the field of instrumentation. To be of real value, this document should not be static, but should be subject to periodic review. Toward this end, the Society welcomes all comments and criticisms, and asks that they be addressed to the Standards and Practice
5、s Board Secretary, ISA, 67 Alexander Drive, P.O. Box 12277, Research Triangle Park, NC 27709, telephone 919-549-8411, e-mail: standardsisa.org.The ISA Standards and Practices Department is aware of the growing need for attention to the metric system of units in general, and the International System
6、of Units (SI) in particular, in the preparation of instrumentation standards. The Department is further aware of the benefits to USA users of ISA standards of incorporating suitable references to the SI (and the metric system) in their business and professional dealings with other countries. Toward
7、this end, this Department will endeavor to introduce SI and SI-acceptable metric units as optional alternatives to English units in all new and revised standards to the greatest extent possible. The Standard for Metric Practice, which has been published by the American Society for Testing and Materi
8、als as ANSI-Z210.1 (ASTM E 380-76; IEEE 268-1975) and future revisions will be the reference guide for definitions, symbols, abbreviations, and conversion factors.The ISA Standards Committee on Turbine Flowmeters, SP31, operates within the ISA Standards and Practices Department, L. N. Combs, Vice-Pr
9、esident. The men listed below serve as members of this committee.NAME COMPANYM. J. Ford, Chairman Pratt the terms defined in 4.3 Specific Terminology appear in italics.4.1 Design characteristics4.1.1 The following mechanical design characteristics shall be specified.1) *Measured FluidsThe liquids to
10、 be in contact with the wetted parts, e.g., JP-4 fuel, hydrochloric acid,etc.2) Configuration and Dimensionsa) For flared tubing (MS 33656) the nominal tube size, overall length, and equivalent fittings.b) For flanged types the nominal pipe size, and length between flanges.c) For male pipe-threaded
11、flowmeters the nominal pipe size and overall length.3) Mountings and Mounting DimensionsUnless the process connection serves as a mounting, the outline drawing shall in-dicate the method of mounting with hole sizes, centers and other pertinent dimen-sions, including thread specifications for threade
12、d holes, if used.4) The weight of the flowmeter.5) The following information shall be permanently marked on the flowmeter housing.a) Manufacturerb) Part or Model No.c) Serial No.d) Flow Directione) Nominal Tube or Pipe SizeISA-RP31.1-1977 114.1.2 Supplemental mechanical design characteristicsThe fol
13、lowing mechanical design characteristics shall be specified at the option of the purchaser.1) Minimum and maximum temperaturesThe minimum and maximum temperatures of the measured liquid, and of the sur-rounding environment.2) PressureThe maximum pressure of the measured liquid.3) SpeedThe maximum ou
14、tput frequency which the flowmeter can produce without physicaldamage.4.1.3 Required electrical design characteristicsThe following electrical characteristics shall be specified.1) *Excitation (modulating type only). Expressed as “_volts at_hertz.“2) *Electrical outputa) Output voltageExpressed as “
15、_volts“ minimum peak-to-peak at any flow within the operatingrange.b) Frequency at maximum rated flow expressed as “_Hz.“4.2 Performance characteristicsThe pertinent performance characteristics of turbine flowmeters should be specified in the order shown. Unless otherwise stated, they apply at *Room
16、 Conditions, as defined in ISA-S37.1 and are expressed in SI units. (Equivalent units may be substituted.)4.2.1 *RangeExpressed as “_to_meter3per second.“ 4.2.2 Linear rangeExpressed as “_to_meter3per second.“4.2.3 *SensitivityThe sensitivity (K factor) is expressed as “_cycles per meter3.“ Often us
17、ed as K , which is the average sensitivity across the flow range of interest to the user. Average is used here in the sense of (Kmax + Kmin)/2.4.2.4 *LinearityThe normal presentation of the calibration data is in cycles per meter3vs. frequency, which is the slope of a curve of flow vs. frequency. Li
18、nearity is then expressed as “_% of the average sensitivity (K factor).“ (See Linearity in 4.3 Specific Terminology.)12 ISA-RP31.1-19774.2.5 Pressure dropThe pressure drop across the flowmeter at maximum rated flow, expressed as “_differential pascals at _meter3per second“ when used with specific me
19、asured liquid.4.3 Specific terminologyActual flow: Refers to the actual volume of liquid passing through the flowmeter in a unit time as computed by applying all necessary corrections for the effects of temperature, pressure, air buoyancy, etc. to the corresponding readings indicated by the calibrat
20、or.Air buoyancy: The lifting effect or buoyancy of the ambient air which acts during a “weighing“ procedure with open gravimetric calibrations. This is caused by displacement of air from the measuring vessel during the calibration run. The standard air (50% R.H.) for correcting to “weights“ in vacuu
21、m has a density of 1.217 kg/m3at 288.7 K and 1.013 250E+05 Pa. When “weighings“ are made against “weights,“ the buoyancy force on these must also be considered. For brass “weights“ the net effect of air buoyancy in air at standard conditions is about 0.015%. Exact values can be determined by procedu
22、res outlined in paragraphs 3059 and 3060 of API Standard 1101, 1960 Editions, and NBS Handbook 77, Volume III, Pages 671-682.Apparent flow: The uncorrected volume flow as indicated by the calibrator.Back pressure: The absolute pressure level as measured four pipe-diameters downstream from the turbin
23、e flowmeter under operating conditions, expressed in pascals.*Calibration curve: A graph of the performance of a turbine flowmeter, showing sensitivity as the ordinate and volume flow, flowmeter frequency, or frequency divided by kinematic viscosity as the abscissa, for a liquid of specified density
24、, viscosity, and temperature.Calibration system: A complete system consisting of liquid storage, pumps, and filters; flow, pressure, and temperature controls; the quantity measuring apparatus; and the associated electronic instruments used to calibrate turbine flowmeters.Correlation check: A procedu
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ISARP3111977SPECIFICATIONINSTALLATIONANDCALIBRATIONOFTURBINEFLOWMETERS 涡轮流量计 安装 校准 规范 PDF

链接地址:http://www.mydoc123.com/p-789910.html