IEST RP-CC002 4-2016 Unidirectional-Flow Clean-Air Devices.pdf
《IEST RP-CC002 4-2016 Unidirectional-Flow Clean-Air Devices.pdf》由会员分享,可在线阅读,更多相关《IEST RP-CC002 4-2016 Unidirectional-Flow Clean-Air Devices.pdf(44页珍藏版)》请在麦多课文档分享上搜索。
1、Institute of Environmental Sciences and Technology IEST-RP-CC002.4 Contamination Control Division Recommended Practice 002.4 Unidirectional-Flow, Clean-Air Devices Arlington Place One 2340 S. Arlington Heights Road, Suite 620 Arlington Heights, IL 60005-4510 Phone: (847) 981-0100 Fax: (847) 981-4130
2、 E-mail: informationiest.org Web: www.iest.org IEST-RP-CC002.4 Institute of Environmental Sciences and Technology IEST 2016 All rights reserved 2 This Recommended Practice was prepared by and is under the jurisdiction of Working Group 2 of the IEST Contamination Control Division (WG-CC002). The foll
3、owing WG voting members contributed to the development of this edition of this Recommended Practice: R. Vijayakumar, WG-CC002 Chair, AERFIL Daniel Dennison, NNE Pharmaplan, Inc. Keith Flyzik, Micro-Clean, Inc. Donna Kasper, Hollingsworth CAS# 117-81-7. DOS or DEHS Dioctyl sebacate (DOS) or di(2-ethy
4、lhexyl) sebacate (DEHS); CAS# 122-62-3. HEPA (high-efficiency particulate air) filter An extended-medium, dry-type filter in a rigid frame having a minimum particle collection efficiency of 99.97% for 0.3-m mass median diameter particles of DOP when tested at rated airflow in accordance with MIL-STD
5、-282. NOTE: The foregoing is the traditional definition for the HEPA filter. Changes in filter manufacture, end-user re-quirements, and testing have introduced products that vary parametrically from filters that have been considered standard according to this definition. Additional information on th
6、is topic is given in IEST-RP-CC001. microspheres (or PSL) Monodisperse or polydisperse sized particles usually made of polystyrene latex (PSL). Monodisperse particle size is traceable to the National Institute of Standards and Technology (NIST) or other national standards bodies with re-spect to the
7、 diameter. NOTE: PSL refers to a common type of highly uniform spheres, or a suspension thereof, used to generate a solid aerosol. PSL is useful for leak testing filters where other aerosols may contaminate the filters in an unacceptable manner. The term latex refers to an emulsion in water of finel
8、y divided particles of synthetic rubber, plastic, or other elastomer, and is not to be confused with natural rubber latex. PAO (4 cSt poly-alpha-olefin) A grade of PAO with a viscosity of 4 centistokes at 100 C. With reference to filter testing, PAO also refers to a poly disperse aerosol of the desc
9、ribed material. PSL (see microspheres) ULPA (ultra-low-penetration air) filter A throwaway, extended-medium, dry-type filter in a rigid frame, having a minimum particle-collection efficiency of 99.999% (that is, a maximum particle penetration of 0.001%) when tested in accordance with the methods of
10、IEST-RP-CC007. ULPA filters are defined and described in IEST-RP-CC001. IEST-RP-CC002.4 Institute of Environmental Sciences and Technology IEST 2016 All rights reserved 10 unidirectional airflow (unidirectional flow) Air flowing in a single direction at the work zone of a clean-air device or clean a
11、rea. This can be verified by the absence of recirculating or stagnant air at the work zone either by visual methods or other techniques. Formerly referred to as laminar airflow. unidirectional clean air Unidirectional airflow that has been filtered with at least a Type C or more efficient filter. wo
12、rk zone The volume within the clean-air device or cleanroom that is designated for clean work and for which testing is re-quired. The work zone volume is defined by an entrance plane and an exit plane (normal to the airflow where there is unidirectional airflow). 4 BACKGROUND AND PURPOSE This RP pro
13、vides a set of recommended test procedures for determining clean-air-device performance. The principal purpose of clean-air-device performance testing is classification of air cleanliness in accordance with ISO 14644-1. Additional tests, such as those related to airflow characteristics, sources of p
14、articles, device pressurization and integ-rity, and environmental issues, provide a more complete characterization of performance of the device. When purchasing a clean-air device, appropriate sections of this RP should be referenced in the purchase order to define the expected performance of the un
15、it as received. 4.1 Applications Unidirectional-flow, clean-air devices are designed to provide a localized (stand-alone) clean environment for pro-tecting a product or manufacturing operation. Historically, these devices have been utilized in product manufactur-ing, sterility testing, or compoundin
16、g sterile preparations. These devices may be used within uncontrolled environments or surrounded by another controlled environment of lesser cleanliness. As with any device, all unidirectional-flow, clean-air devices should be used properly and be certified after installa-tion and at routine interva
17、ls to verify that the design requirements are being maintained. Whenever unidirectional airflow is considered, care should be exercised to avoid obstructions between the clean-air source and the critical work area that may cause turbulence or interfere with the desired environment within the clean z
18、one, as well as obstructions (including personnel) downstream from the product that can back stream contam-inants onto the product. In selecting the airflow pattern, horizontal or vertical, the user should consider the equipment and process to be used in the device with relationship to airflow. Many
19、 of these units can be modified to accommodate accessories such as sinks, utilities, and special process equip-ment. To define what is expected from the supplier, a drawing should be included with the request for quotation and with the purchase order. It should be noted that the placement of items w
20、ithin or on the work surface can alter the airflow patterns within the device and reduce its effectiveness unless the appropriate steps are taken during the orig-inal design and fabrication. 4.2 Operational concerns Exhausting clean-air devices should be equipped with a flow sensor to monitor supply
21、 and exhaust air. These devic-es are effective only if the air balance is correct. If the air balance drifts outside of the specifications, either the product may become contaminated or the operator may be exposed to potentially harmful materials. Air balance is of interest generally for biological
22、safety and containment cabinets. Procedures for air balance can be found in the instructions provided by the cabinet manufacturer or in NSF/ANSI Standard 49 and are not included in this RP. Fur-ther guidance on exhaust and proper ventilation systems may be found in ANSI/AIHA Z9.5 and ANSI/AIHA Z9.7.
23、 Whenever a fan-filter unit (see 5.9) or clean-air module (see 5.10) is used to provide a localized clean area, enclo-sure of the airflow is necessary to maintain the unidirectional flow from the filter to the critical work area. If the IEST-RP-CC002.4 Institute of Environmental Sciences and Technol
24、ogy IEST 2016 All rights reserved 11 airflow is not enclosed, the clean-air zone may be compromised by room air currents, cross-drafts, or induced air contaminants drawn into the HEPA-filtered airstream. Additional information concerning installation and maintenance is provided in Appendixes A, B, C
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IESTRPCC00242016UNIDIRECTIONALFLOWCLEANAIRDEVICESPDF

链接地址:http://www.mydoc123.com/p-784798.html