1、3515789 0025518 7T8 DAE%FEu Technical Note 77-13 Supplement 1 DEPAR“T OF THE ARMY Office of the Chief of Engineers Washington, DC 20314 1 Septenber 1977 FACILITIES ENGINEERING Maintenance and Repair 1. PurDose. To distribute additional information on subject matter. 2. Amiicability. This supplement
2、applies to the same facilities engineering elements as did the basic technical note. 3. Discussion. Ihre specific and updated information regarding retrofilling of askarel-filled transformers has become available since the basic technical note was piblished. a. The cost of retrofilling has increased
3、, due mostly to higher costs for handling and disposing of askarel and askarel-contaminated materials. The total cost, including new liquid, flushing liquid, labor, and handling and disposal costs is approximately the cost of a new replacement transformer filled with the liquid for which it was desi
4、gned. When the remaining life of the existing transformer and the reduced performance because of the new liquid are considered, there is rarely any economic justification for retrofilling. percent of askarel, it must still be handled and disposed of as an askarel- filled transformer. of, regardless
5、of whether it was retrofilled or not, the cost will be the same. Msposal costs for a replaced transformer are therefore not a consideration in the economics of retrofilling. Because a retrofilled transformer still contains several This means that at the time the transformer is disposed b. There is a
6、 big question at this time regarding future availability of askarel for “topping-offft existing transformers. solution is available, this is of no concern. of an electrical grade of PCB known as aroclor, and thinners consisting of tri-or tetra-chlorobenzene. and 4% thinner. operation. effects. the t
7、ransformer manufacturer should be contacted to determine the maximum amunt of thinner that may be added. Because an alternative All askarels are composed Normally, the mixture is about 60$ aroclor Small amounts of thinner can thus be added without any adverse If large amounts of tri- anvor tetra-chl
8、orobenzene are required, A minimum of 30$ aroclor is required for proper transformer Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-3515789 O025539 b34 DAEN-FEU Technical Note 77-13 Supplement 1 c. Benzene is now under investigation as a possible ca
9、ncer-causing agent, and thinners containing benzene may not continue to be available. Should they not be available in the fiture, contact HWA, DAEN-FEU-E, Washington, DC 20314, autovm 223-6459, for information concerning available substitutes. 4. mi ration. to one year fkom the date of this suppleme
10、nt. The expiration date of this technical note is extended DAVIDM. CRABTI1EE Chief, Ut,il Engr and under normal circumstances, the combination of the two materials, in any percentage, should not create a liquid volume problem. As the percentage of RTEmp fluid in the Askarel increases, the viscosity
11、will change, approaching that of RTEmp fluid at higher concentrations. low percentages of RTEmp fluid, there should be a negligible affect on the heat transfer charac- teristics of the transformer. The net effect of this phenomenon will be that, as the RTEmp fluid percentage is increased, the transf
12、ormer will run somewhat hotter for a given ambient and load con- dition. Under most normal service loading condi- tions, the hot spot temperature rating of the insulation system will not be exceeded because most transformers do not operate at 100% load and full rated ambient most of the time. To the
13、 extent that they do, the transformer will run in an With -1- 3687 . . -. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-8 3535789 0025522 129 apparently overloaded condition for a somewhat longer period of time than would the pure Askarel transform
14、er. This might tend to reduce the thermal life of the transformer somewhat with high percen- tages of RTEmp fluid; but with the relatively small percentages which would normally be encountered in a makeup fluid situation and the greater thermal life of RTEmp-paper insulation systems, the effect woul
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- COEETN77131977FACILITIESENGINEERINGMAINTENANCEANDREPAIRASKARELFILLEDTRANSFORMERS 设备 工程学 维护 填充 联苯 变压器

链接地址:http://www.mydoc123.com/p-620704.html