CAN CSA-ISO IEC 18010A-2006 Amendment 1 Information technology – Pathways and spaces for customer premises cabling.pdf
《CAN CSA-ISO IEC 18010A-2006 Amendment 1 Information technology – Pathways and spaces for customer premises cabling.pdf》由会员分享,可在线阅读,更多相关《CAN CSA-ISO IEC 18010A-2006 Amendment 1 Information technology – Pathways and spaces for customer premises cabling.pdf(26页珍藏版)》请在麦多课文档分享上搜索。
1、 INTERNATIONAL STANDARD ISO/IEC180102002AMENDMENT 12005-12Amendment 1 Information technology Pathways and spaces for customer premises cabling PRICE CODE IEC 2005 Droits de reproduction rservs Copyright - all rights reserved International Electrotechnical Commission, 3, rue de Varemb, PO Box 131, CH
2、-1211 Geneva 20, SwitzerlandTelephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmailiec.ch Web: www.iec.ch L For price, see current catalogueCommission Electrotechnique InternationaleInternational Electrotechnical Commission NOT FOR RESALE.Amendment 1:2006 toNational Standard of CanadaCA
3、N/CSA-ISO/IEC 18010:04Amendment 1:2005 to International Standard ISO/IEC 18010:2002 has been adopted without modification(IDT) as Amendment 1:2006 to CAN/CSA-ISO/IEC 18010:04. This Amendment was reviewed by the CSATechnical Committee on Information Technology (TCIT) under the jurisdiction of the Str
4、ategic SteeringCommittee on Information Technology and deemed acceptable for use in Canada.December 2006 2 18010 Amend. 1 ISO/IEC:2005(E) FOREWORD Amendment 1 to International Standard ISO/IEC 18010 was prepared by subcommittee 25: Interconnection of information technology equipment, of ISO/IEC join
5、t technical committee 1: Information technology. 18010 Amend. 1 ISO/IEC:2005(E) 3 Page 2 Contents Add the following new items in the table of contents: Annex A (normative) Additional requirements for multi-tenant buildings A.1 INTRODUCTION A.2 Entrance facilities A.2.1 Entrance location consideratio
6、ns A.2.2 Telecommunications service entrance pathway A.2.3 Access A.2.4 Wireless A.3 Access provider spaces and service provider spaces A.3.1 General A.3.2 Location A.3.3 Pathways A.3.4 Design A.4 Common equipment room A.4.1 General A.4.2 Location A.4.3 Pathways A.4.4 Design A.5 Common telecommunica
7、tions room A.5.1 General A.5.2 Location A.5.3 Pathways A.5.4 Design A.6 Building and campus pathway requirements A.6.1 Building pathways A.6.2 Campus pathways Annex B (informative) Additional recommendations for multi-tenant buildings Existing Annexes A and B have to be renumbered as Annexes C and D
8、, as follows: Annex C (informative) Pathways and cable stresses Annex D (informative) Building entrance facility 4 18010 Amend. 1 ISO/IEC:2005(E) General Update the references to tables and figures whose numbers have been changed. Page 5 INTRODUCTION Add the following new paragraph: This standard ha
9、s 4 annexes: Annex A (normative) Additional requirements for multi-tenant buildings Annex B (informative) Additional recommendations for multi-tenant buildings Annex C (informative) Pathway and cable stresses Annex D (informative) Building entrance facility Page 6 1 Scope Replace the second paragrap
10、h by the following text: This International Standard also influences space allocation within the building. Both single- and multi-tenant buildings for residential and commercial use are considered by this standard. Page 7 3 Definitions and abbreviations 3.1 Definitions Add the following new definiti
11、ons after 3.1.9: 3.1.10 common equipment room (telecommunications) enclosed space used for equipment and backbone interconnections for more than one tenant in a building 3.1.11 common telecommunications room enclosed space used for backbone interconnections for more than one tenant in a building, wh
12、ich may also house equipment Renumber the existing definitions 3.1.10 to 3.1.26 as 3.1.12 to 3.1.28. 18010 Amend. 1 ISO/IEC:2005(E) 5 Page 9 3.2 Abbreviations Replace the existing text by the following: CER Common equipment room CTR Common telecommunications room EMI Electromagnetic interference HVA
13、C Heating, ventilation and air conditioning IT Information technology4 Conformance Add the following new items: c) For multi-tenant buildings, Annex A shall also be observed. d) Local regulations shall be followed. Page 10 5 Structure of a pathways and spaces infrastructure Replace existing figure 1
14、 by the following figure 1: 6 18010 Amend. 1 ISO/IEC:2005(E) Figure 1 Basic elements of a pathways and spaces infrastructure Page 11 6.3 Telecommunications room Add the following new paragraph before the last paragraph: Telecommunications room temperature and humidity shall provide for continuous op
15、eration of the installed active equipment. Humidifying and dehumidifying equipment may be required depending upon local environmental conditions. ER = Equipment room TR = Telecommunications room TR ER Entrance room Source entrance Building pathway TR TR TR Antenna entrance Alternate Campus pathway B
16、uilding pathwayTelecommunications outlet Work area18010 Amend. 1 ISO/IEC:2005(E) 7 6.4 Equipment room Add, on page 12, the following paragraph after the fifth paragraph: Equipment room temperature and humidity shall provide for continuous operation of the installed active equipment. Humidifying and
17、dehumidifying equipment may be required depending upon local environmental conditions. Page 12 6.5 Main terminal space Add an new subclause 6.6 after 6.5. 6.6 Home distributor (HD) The HD shall be able to contain telecommunications equipment, cable terminations and associated cross-connect cables. T
18、he HD should be located as close as practicable to the centre of the area served and preferably in the core area. The HD space shall be dedicated to the HD function and related support facilities. HD space should not be shared with electrical installations other than those for telecommunications. A
19、minimum of one dedicated electrical outlet shall be provided for equipment power. NOTE Local regulations should be followed for electrical power distribution. Renumber existing subclauses 6.6 to 6.9 as 6.7 to 6.10. Page 20 8.8 Handholes Add, after the end of subclause 8.8, the following two new anne
20、xes A and B and renumber existing annex A and annex B as annex C and annex D, respectively. 8 18010 Amend. 1 ISO/IEC:2005(E) Annex A (normative) Additional requirements for multi-tenant buildings A.1 INTRODUCTION Annexes A and B focus on the pathways and spaces that are common to multi-tenant buildi
21、ngs and campuses. Telecommunications pathways and spaces in multi-tenant buildings are challenged by the phased nature of their use. After the building is constructed and the first group of tenants moves in, the tenants telecommunications needs may immediately cause modifications to the building. Ov
22、er a span of years, as tenants cycle through the building, evolving tenant needs will oblige the owner/agent of the building to adapt its installations to these demands. Multi-tenant commercial office and residential buildings have life cycles that mirror that of single-tenant buildings. Many buildi
23、ngs are over 100 years old. Over time, these older buildings have become severely challenged to support escalating demands on their pathways and spaces as a result of tenants ever-increasing needs for telecommunications connectivity. Figure A.1 illustrates a representative model for the various func
24、tional elements that comprise multi-tenant pathways and spaces for a building. This is not intended to be an all-inclusive representation. It depicts the relationship between the elements and how they are configured to create a total system. Table A.1 provides a summary of the telecommunications spa
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- CANCSAISOIEC18010A2006AMENDMENT1INFORMATIONTECHNOLOGY PATHWAYSANDSPACESFORCUSTOMERPREMISESCABLINGPDF

链接地址:http://www.mydoc123.com/p-590756.html