《BS 5885-1-1988 Automatic gas burners - Specification for burners with input rating 60 kW and above《自动燃气燃烧器 额定输入功率60 kW及以上的燃烧器规格》.pdf》由会员分享,可在线阅读,更多相关《BS 5885-1-1988 Automatic gas burners - Specification for burners with input rating 60 kW and above《自动燃气燃烧器 额定输入功率60 kW及以上的燃烧器规格》.pdf(30页珍藏版)》请在麦多课文档分享上搜索。
1、BRITISH STANDARD BS 5885-1: 1988 Incorporating Amendments Nos. 1 and 2 Automatic gas burners Part 1: Specification for burners with input rating 60kW and above ICS 27.060.20BS5885-1:1988 This British Standard, having been prepared under the directionof the Gas StandardsCommittee, waspublished under
2、the authorityofthe Board of BSIandcomes intoeffect on 31 August 1988 BSI 09-1999 The following BSI references relate to the work on this standard: Committee reference GSE/27 Draft for comment 86/73991 DC ISBN 0 580 16691 0 Committees responsible for this British Standard The preparation of this Brit
3、ish Standard was entrusted by the Gas Standards Committee (GSE/-) to Technical Committee GSE/27, upon which the following bodies were represented: British Coal Corporation British Combustion Equipment Manufacturers Association British Gas plc Chief and Assistant Chief Fire Officers Association Depar
4、tment of the Environment (Property Services Agency) Electricity Supply Industry in England and Wales Fire Offices Committee Health and Safety Executive Society of British Gas Industries Water-tube Boilermakers Association Amendments issued since publication Amd. No. Date of issue Comments 6631 Decem
5、ber 1990 9260 July 1997 Indicated by a sideline in the marginBS5885-1:1988 BSI 09-1999 i Contents Page Committees responsible Inside front cover Foreword ii 1 Scope 1 2 Definitions 1 3 Verification 3 4 Gas flow pipework and controls 4 4.1 Filters and strainers 4 4.2 Pipework and flow components 4 4.
6、3 Gas flow in pipework 6 4.4 Vents on safety shut-off systems 6 4.5 Gas supply 6 4.6 Safety shut-off systems 8 5 Combustion air, pre-purge and post-purge 11 5.1 Combustion air 11 5.2 Pre-purge and post-purge 12 6 Electrical supply and ancillary equipment 12 6.1 Electricity supply 12 6.2 Electrical e
7、quipment 13 6.3 Instrument and control fluid supplies 14 7 Flame safeguard system 14 7.1 Flame detection 14 7.2 Start-gas flame establishment 15 7.3 Main flame establishment 15 8 Control system requirements 16 9 Fuel/air ratio control 16 10 Materials 17 10.1 General 17 10.2 Metallic materials 17 10.
8、3 Non-metallic materials 17 10.4 Glands and spindle packings 17 10.5 Jointing materials 17 10.6 Flexible pipes and pipe connections 17 11 Constructional requirements 18 11.1 Burner construction 18 11.2 Fixing 18 12 Manufacturers literature 19 13 Marking 19 14 Commissioning instructions 19 Appendix A
9、 Dual fuel burners 21 Appendix B Over-pressure protection 21 Table 1 Test gases 3 Table 2 Wall thickness of pipes complying with BS 3601 4 Table 3 Connections for valves and pipework 4 Table 4 Inlet pressure ranges 7 Table 5 Main gas safety shut-off valve system requirements 9 Table 6 Flame safeguar
10、d drop-out times 14 Table 7 Summary of materials 18 Publications referred to 23BS5885-1:1988 ii BSI 09-1999 Foreword This Part of BS 5885 has been prepared under the direction of the Gas Standards Committee and applies primarily to single gas-fired automatic burners. It is a revision of BS 5885:1980
11、, which is withdrawn. In general, each requirement in this Part is accompanied by an appropriate means of verification, such means being by inspection, by measurement or by specified test. In those cases where verification is to be achieved by measurement, no test method is given since the method of
12、 measurement is considered to be self-evident. Verification of compliance with requirements which invoke other British Standards is to be demonstrated by means of a declaration from the burner manufacturer and, where third party certification is required, may necessitate the production of documentar
13、y proof. Certain requirements are only capable of being verified when the burner is installed in its associated appliance. In these cases no verification procedure is specified as it is anticipated that the relevant appliance standard will incorporate the appropriate method of verification. For larg
14、e or special plant, commissioning procedures will also need to take this into account. Requirements which also relate to burners employing induced draught fans can only be tested in situ. It should also be appreciated that this Part of BS 5885 may not contain all the requirements for a particular ap
15、plication and therefore the burner may require additional features. Much of this Part of BS 5885 is applicable to dual fuel burners. However, it should not be assumed that compliance with this Part (or with standards dealing with burners using oil fuel, e.g. BS 799 and BS 5410) will necessarily sati
16、sfy all the safety requirements of dual fuel burners. For guidance, see Appendix A. It is recognized that for specialist heating processes it is permissible to use designs and test methods which differ from those specifically defined in this Part of BS 5885 but which nevertheless comply with the int
17、ent of this standard. Similarly, new systems or procedures resulting from advances in technology may be applied to give equal or improved safety. It is not intended that this Part of BS5885 should prohibit the development or use of such systems, but any departure from the specific requirements of th
18、is standard should be made only on the basis of sound engineering judgement and experience. It has been assumed in the drafting of this British Standard that the execution of its provisions is entrusted to appropriately qualified and experienced people. A British Standard does not purport to include
19、 all the necessary provisions of a contract. Users of British Standards are responsible for their correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. Summary of pages This document comprises a front cover, an inside front cover, pages i
20、and ii, pages1 to 24, an inside back cover and a back cover. This standard has been updated (see copyright date) and may have had amendments incorporated. This will be indicated in the amendment table on the inside front cover.BS5885-1:1988 BSI 09-1999 1 1 Scope This Part of BS5885 specifies minimum
21、 requirements for automatic gas burners employing forced or mechanically induced draught and having a heat input rating of 60kW and above. Such burners may be of packaged or non-packaged types, and may be designed for use with 1st, 2nd or 3rd family gases. BS5885 applies to burners intended for use
22、in industrial processes. It does not cover burners intended for use in heating appliances, e.g. boilers, which are covered by BS EN 676, Automatic forced draught burners for gaseous fuels. It covers single burners and dual fuel burners when operating only on gas. It does not cover multi-burners. Gui
23、dance on dual fuel burners is given in Appendix A. This Part of BS5885 specifies requirements primarily for the safety aspects of automatic control and operation. It does not constitute a complete specification for automatic burners and their ancillary equipment. NOTE 1The use of gases which are dir
24、ty, wet, of variable composition or high dewpoint may cause difficulties which are not covered in detail by this Part of BS5885. In such cases, suppliers and users of equipment will need to take additional measures to comply with the requirements of this standard. NOTE 2Burners complying with this P
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS588511988AUTOMATICGASBURNERSSPECIFICATIONFORBURNERSWITHINPUTRATING60KWANDABOVE 自动 燃气 燃烧 额定 输入 功率 60

链接地址:http://www.mydoc123.com/p-545464.html