ATIS 0600015-2018 Energy Efficiency for Telecommunication Equipment Methodology for Measurement and Reporting C General Requirements.pdf
《ATIS 0600015-2018 Energy Efficiency for Telecommunication Equipment Methodology for Measurement and Reporting C General Requirements.pdf》由会员分享,可在线阅读,更多相关《ATIS 0600015-2018 Energy Efficiency for Telecommunication Equipment Methodology for Measurement and Reporting C General Requirements.pdf(15页珍藏版)》请在麦多课文档分享上搜索。
1、ATIS-0600015.2018 (Revision of ATIS-0600015.2013) American National Standard for Telecommunications Energy Efficiency for Telecommunication Equipment: Methodology for Measurement and Reporting General Requirements Alliance for Telecommunications Industry Solutions Approved May 2018 American National
2、 Standards Institute, Inc. Abstract This document provides the methodology to be used by vendors and third-party test laboratories in the formation of a telecommunications energy efficiency ratio (TEER). This document is the base standard for determining telecommunications energy efficiency. ATIS-06
3、00015.2018 ii Foreword The information contained in this Foreword is not part of this American National Standard (ANS) and has not been processed in accordance with ANSIs requirements for an ANS. As such, this Foreword may contain material that has not been subjected to public review or a consensus
4、process. In addition, it does not contain requirements necessary for conformance to the Standard. The Alliance for Telecommunications Industry Solutions (ATIS) serves the public through improved understanding between providers, customers, and manufacturers. The Sustainability in Telecom: Energy and
5、Protection (STEP) Committee formerly the Network Interface, Power, and Protection Committee (NIPP) engages industry expertise to develop standards and technical reports for telecommunications equipment and environments in the areas of energy efficiency, environmental impacts, power and protection. T
6、he work products of STEP enable vendors, operators and their customers to deploy and operate reliable, environmentally sustainable, energy efficient communications technologies. STEP is committed to proactive engagement with national, regional and international standards development organizations an
7、d forums that share its scope of work. ANSI guidelines specify two categories of requirements: mandatory and recommendation. The mandatory requirements are designated by the word shall and recommendations by the word should. Where both a mandatory requirement and a recommendation are specified for t
8、he same criterion, the recommendation represents a goal currently identifiable as having distinct compatibility or performance advantages. Suggestions for improvement of this document are welcome. They should be sent to the Alliance for Telecommunications Industry Solutions, STEP, 1200 G Street NW,
9、Suite 500, Washington, DC 20005. At the time it approved this document, STEP, which is responsible for the development of this Standard, had the following leadership: E. Gallo, STEP Chair (Ericsson) J. Fuller, STEP Vice Chair (AT therefore, the Alternating Current (AC) noise on the input power port(
10、s) is not considered significant. All equipment used for taking physical measurements shall be in a current state of calibration traceable to NIST requirements or counterpart national metrology institute in other countries. All references to power in this document are defined as effective power aver
11、aged over measurement time. All references to energy is the effective power integrated over the measurement time. 5.2 Environmental Consideration 5.2.1 Temperature The equipment shall be evaluated at temperature of 25C 3C (77 5F). 5.2.2 Humidity The equipment shall be evaluated at a relative humidit
12、y of 30% to 75%. 5.2.3 Barometric Pressure The equipment shall be evaluated at a barometric pressure between 1060 and 812 mbar. 5.2.4 Voltage 5.2.4.1 DC Powered Equipment The equipment shall be evaluated at a DC voltage of 53V 2V. (This level is consistent with the voltage defined in ATIS-0600315 fo
13、r a -48 Vdc powering system.) Unless otherwise specified in a supplemental standard to this General Requirement Standard, equipment using nominal DC voltages other than -48Vdc shall be evaluated at 4% of the specified float voltage. Where applicable, the typical steady state voltage as defined in AT
14、IS-0600315 shall be used. 5.2.4.2 AC Powered Equipment The equipment shall be evaluated with a source providing the following conditions: Total Harmonic Distortion 3% up to and including the 13thharmonic As an example, number of voltages: o Single phase, 120 VAC 5%, 60 Hz 1%. o Single phase, 230 VAC
15、 5%, 50 or 60 Hz 1%. o Three phase, 208 VAC 5%, 50 or 60 Hz 1%. o Other voltages acceptable, depending on location of deployment. ATIS-0600015.2018 5 Unless otherwise specified in a supplemental standard to this General Requirement Standard, equipment using other nominal AC voltages shall be evaluat
16、ed at 5% of the specified voltage and 1% of the specified frequency. 5.3 Power Measurement Equipment The measurement equipment used to measure power, voltage and current for the purposes of determining energy or power for the Equipment Under Test (EUT) shall have the following minimum characteristic
17、s: A minimum digitizing sample rate of 40 kHz. Input circuitry with a minimum bandwidth of 80 kHz. Ability to log and store data for the total measurement period. Overall measurement accuracy shall be within +/- 1%. Measurements may be performed with a variety of instruments. These range from voltag
18、e and current meters with data acquisition capability to power analyzers capable of fully integrated measurement. NOTE - Measurement equipment with higher digitizing rates and higher accuracy may be desirable to ensure accurate measurement. 5.4 Power Source DC power sources used to provide power to
19、the EUT shall be capable of providing a minimum of 1.5 times the power rating of the EUT. 5.5 EUT Stabilization EUT shall be allowed to stabilize and then operate for a minimum of 15 minutes before measurements can be taken, except where otherwise noted in a supplemental standard. 5.6 Minimum Measur
20、ement Duration Measurements shall be performed over a minimum period of five minutes, except where otherwise noted in a supplemental standard. For EUT whose cycle time or energy saving mode requires a longer measurement period, the minimum measurement period shall be increased to provide an accurate
21、 indication of energy consumption. 5.7 Test Configuration EUT with multiple power connections (including redundant connections) shall have all feeds connected, and the power flow from all feeds shall be summed to obtain total system power. Within this document, the typical environment in a Central O
22、ffice is considered to be 27C (81F). The energy consumed by fans may be higher when operating at 27C than at lower temperatures. The data reported for the equipment shall represent fan power expected when the equipment is operating in a simulated environment of 27C at sea level. To capture this pote
23、ntial higher energy consumption, one of the following methods shall be used: Method 1: Test in a thermally controlled environment of no less than 27C. Method 2: If fans are configurable, they shall be configured with fixed speed settings representative of an operating environment of 27C at sea level
24、. With a modular system, the power from the fans may be evaluated once and incorporated in the data matrix. Method 3: If fans are not configurable, a power adjustment due to fan speed change must be added to the system power measured at the temperature defined in clause 5.2.1. With a modular system,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ATIS06000152018ENERGYEFFICIENCYFORTELECOMMUNICATIONEQUIPMENTMETHODOLOGYFORMEASUREMENTANDREPORTINGCGENERALREQUIREMENTSPDF

链接地址:http://www.mydoc123.com/p-541243.html