1、Designation: D56 05 (Reapproved 2010)Standard Test Method forFlash Point by Tag Closed Cup Tester1This standard is issued under the fixed designation D56; the number immediately following the designation indicates the year of originaladoption or, in the case of revision, the year of last revision. A
2、 number in parentheses indicates the year of last reapproval. A superscriptepsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.INTRODUCTIONTo ensure an acceptable precision, this dynamic flash
3、 point test method employs a prescribed rateof temperature rise for the material under test. The rate of heating may not in all cases give theprecision quoted in the test method because of the low thermal conductivity of certain materials. Toimprove the prediction of flammability, Test Method D3941,
4、 which utilizes a slower heating rate, wasdeveloped. Test Method D3941 provides conditions closer to equilibrium where the vapor above theliquid and the liquid are at about the same temperature. If a specification requires Test Method D56,do not change to Test Method D3941 or other test method witho
5、ut permission from the specifier.Flash point values are a function of the apparatus design, the condition of the apparatus used, andthe operational procedure carried out. Flash point can therefore only be defined in terms of a standardtest method, and no general valid correlation can be guaranteed b
6、etween results obtained by differenttest methods, or with test apparatus different from that specified.1. Scope1.1 This test method covers the determination of the flashpoint, by tag manual and automated closed testers, of liquidswith a viscosity below 5.5 mm2/s (cSt) at 40C (104F), orbelow 9.5 mm2/
7、s (cSt) at 25C (77F), and a flash point below93C (200F).1.1.1 For the closed-cup flash point of liquids with thefollowing properties: a viscosity of 5.5 mm2/s (cSt) or more at40C (104F); a viscosity of 9.5 mm2/s (cSt) or more at 25C(77F); a flash point of 93C (200F) or higher; a tendency toform a su
8、rface film under test conditions; or containingsuspended solids, Test Method D93 can be used.1.1.2 For cut-back asphalts refer to Test Methods D1310and D3143.NOTE 1The U.S. Department of Transportation (RSTA)2and U.S.Department of Labor (OSHA) have established that liquids with a flashpoint under 37
9、.8C (100F) are flammable as determined by this testmethod for those liquids that have a viscosity less than 5.5 mm2/s (cSt) at40C (104F) or 9.5 mm2/s (cSt) or less at 25C (77F), or do not containsuspended solids or do not have a tendency to form a surface film whileunder test. Other flash point clas
10、sifications have been established by thesedepartments for liquids using this test method.1.2 This test method can be used to measure and describethe properties of materials, products, or assemblies in responseto heat and flame under controlled laboratory conditions andcannot be used to describe or a
11、ppraise the fire hazard or firerisk of materials, products, or assemblies under actual fireconditions. However, results of this test method can be used aselements of fire risk assessment that takes into account all ofthe factors that are pertinent to an assessment of the fire hazardof a particular e
12、nd use.1.3 Related standards are Test Methods D93, D1310,D3828, D3278, and D3941.1.4 The values stated in SI units are to be regarded asstandard. The values given in parentheses are for informationonly.1.5 WARNINGMercury has been designated by manyregulatory agencies as a hazardous material that can
13、 causecentral nervous system, kidney and liver damage. Mercury, orits vapor, may be hazardous to health and corrosive tomaterials. Caution should be taken when handling mercury andmercury containing products. See the applicable product Ma-terial Safety Data Sheet (MSDS) for details and EPAswebsiteht
14、tp:/www.epa.gov/mercury/faq.htmfor addi-tional information. Users should be aware that selling mercury1This test method is under the jurisdiction of ASTM Committee D02 onPetroleum Products and Lubricants and is the direct responsibility of SubcommitteeD02.08 on Volatility.Current edition approved Oc
15、t. 1, 2010. Published November 2010. Originallyapproved in 1918. Last previous edition approved in 2005 as D5605. DOI:10.1520/D0056-05R10.2For information on United States Department of Transportation regulations, seeCodes of United States Regulation 49 CFR Chapter 1 and for information on UnitedSta
16、tes Department of Labor regulations, see Code of United States Regulation 29CFR Chapter XVII. Each of these items are revised annually and may be procuredfrom the Superintendent of Documents, Government Printing Office, Washington,DC 20402.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box
17、 C700, West Conshohocken, PA 19428-2959, United States.and/or mercury containing products into your state or countrymay be prohibited by law.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard
18、to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. For specificwarning statements see 8.2, 8.3, 9.5, 12.5, and refer to MaterialSafety Data Sheets.2. Referenced Documents2.1 ASTM Standards:3D93 Test Methods for Flash Point b
19、y Pensky-MartensClosed Cup TesterD1310 Test Method for Flash Point and Fire Point ofLiquids by Tag Open-Cup ApparatusD3143 Test Method for Flash Point of CutbackAsphalt withTag Open-Cup ApparatusD3278 Test Methods for Flash Point of Liquids by SmallScale Closed-Cup ApparatusD3828 Test Methods for Fl
20、ash Point by Small Scale ClosedCup TesterD3941 Test Method for Flash Point by the EquilibriumMethod With a Closed-Cup ApparatusD4057 Practice for Manual Sampling of Petroleum andPetroleum ProductsD6299 Practice for Applying Statistical Quality Assuranceand Control Charting Techniques to Evaluate Ana
21、lyticalMeasurement System PerformanceD6300 Practice for Determination of Precision and BiasData for Use in Test Methods for Petroleum Products andLubricantsE1 Specification for ASTM Liquid-in-Glass ThermometersE502 Test Method for Selection and Use of ASTM Stan-dards for the Determination of Flash P
22、oint of Chemicals byClosed Cup Methods2.2 Federal Test Method Standards:4Method 1101, Federal Test Method Standard No. 791bMethod 4291, Federal Test Method Standard No. 141A2.3 ISO Standards:5Guide 34 General Requirements for the Competence ofReference Material ProducersGuide 35 Certification of Ref
23、erence MaterialsGeneraland Statistical Principles3. Terminology3.1 Definitions:3.1.1 flash pointthe lowest temperature corrected to apressure of 101.3 kPa (760 mm Hg) at which application of anignition source causes the vapors of a specimen of the sampleto ignite under specified conditions of test.3
24、.1.1.1 DiscussionThe specimen is deemed to haveflashed when a flame appears and instantaneously propagatesitself over the entire surface of the fluid.3.1.1.2 DiscussionWhen the ignition source is a testflame, the application of the test flame may cause a blue haloor an enlarged flame prior to the ac
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD5620052010STANDARDTESTMETHODFORFLASHPOINTBYTAGCLOSEDCUPTESTER 密闭 闪点 试验 测定 标准 方法 PDF

链接地址:http://www.mydoc123.com/p-511873.html