ASTM D1050-2005e1 Standard Specification for Rubber Insulating Line Hose《橡胶绝缘软管的标准规范》.pdf
《ASTM D1050-2005e1 Standard Specification for Rubber Insulating Line Hose《橡胶绝缘软管的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM D1050-2005e1 Standard Specification for Rubber Insulating Line Hose《橡胶绝缘软管的标准规范》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 1050 05e1Standard Specification forRubber Insulating Line Hose1This standard is issued under the fixed designation D 1050; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parent
2、heses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.e1NOTE18.1.2 was corrected editorially in March 2005.1. Scope1.1 This specificati
3、on covers acceptance testing of rubberinsulating line hose for use as a portable protective device forprotection of workers from accidental contact with live elec-trical conductors.1.2 Two types of line hose are provided and are designatedas Type I, non-resistant to ozone, and Type II and Type III,r
4、esistant to ozone.1.3 Five classes of line hose, differing in electrical charac-teristics, are provided and are designated as Class 0, Class 1,Class 2, Class 3, and Class 4.1.4 Four styles of line hose, differing in design characteris-tics, are provided and are designated as Style A, Style B, StyleC
5、, and Style D.1.5 The following precautionary caveat pertains only to thetest method portion, Sections 16, 17, 18, 19, of this specifica-tion: This standard does not purport to address all of the safetyconcerns, if any, associated with its use. It is the responsibilityof the user of this standard to
6、 establish appropriate safety andhealth practices and determine the applicability of regulatorylimitations prior to use. For specific precautionary statements,see 18.1.1.2. Referenced Documents2.1 ASTM Standards:2D 297 Test Methods for Rubber ProductsChemicalAnalysisD 412 Test Methods for Vulcanized
7、 Rubber and Thermo-plastic Rubbers and Thermoplastic ElastomersTensionD 570 Test Method for Water Absorption of PlasticsD 573 Test Method for RubberDeterioration in an AirOvenD 624 Test Method for Tear Strength of ConventionalVulcanized Rubber and Thermoplastic ElastomersD 2865 Practice for Calibrat
8、ion of Standards and Equip-ment for Electrical Insulating Materials TestingF 819 Terminology Relating to Electrical Protective Equip-ment for Workers2.2 Federal Specification:PPP-B-636 Box, Shipping, Filterboard32.3 ANSI Standards:4C 2 National Electrical Safety Code, Section 44C 39.5 Safety Require
9、ments for Electrical and ElectronicMeasuring and Controlling InstrumentationC 84.1 Electric Power Systems and Equipment-VoltageRatings3. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 breakdownthe electrical discharge or arc occurringbetween the electrodes and through the equipm
10、ent being tested.3.1.2 flashoverthe electrical discharge or arc occurringbetween electrodes and over or around, but not through, theequipment being tested.3.1.3 electrical testing facilitya location with qualifiedpersonnel, testing equipment, and procedures for the inspectionand electrical testing o
11、f electrical insulating protective equip-ment.3.1.4 electrode clearancethe shortest path from the ener-gized electrode to the ground electrode.3.1.5 insulatedseparated from other conducting surfacesby a dielectric substance (including air space) offering a highresistance to the passage of current.NO
12、TE 1When any object is said to be insulated, it is understood to beinsulated in a suitable manner for the conditions to which it is subjected.1This specification is under the jurisdiction of ASTM Committee F18 onElectrical Protective Equipment for Workers and is the direct responsibility ofSubcommit
13、tee F18.25 on Insulating Cover-up Equipment. This standard replacesANSI Standard J 6.1, which is no longer availableCurrent edition approved Jan. 1, 2005. Published February 2005. Originallyapproved in 1949 as D 1050 49 T. Last previous edition approved in 1999 asD 1050 90(1999).2For referenced ASTM
14、 standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from Standardization Documents, Order Desk, Bldg. 4, Section D,700 Rob
15、bins Ave., Philadelphia, PA 19111-5094, ATTN: NPODS.4Available from American National Standards Institute, 11 West 42nd Street,13th Floor, New York, NY 10036.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.Otherwise, it is, within th
16、e purpose of this definition, uninsulated.Insulating covering of conductors is one means of making the conductorinsulated.3.1.6 isolatedan object that is not readily accessible topersons unless special means of access are used.3.1.7 ozonea very active form of oxygen that may beproduced by corona, ar
17、cing, or ultra-violet rays.3.1.8 ozone cutting and checkingthe cutting action pro-duced by ozone on rubber under mechanical stress into a seriesof interlacing cracks.3.1.9 rubbera generic term that includes elastomers andelastomeric compounds, regardless of origin.3.1.10 voltage, maximum usethe ac v
18、oltage (rms) ratingof the protective equipment that designates the maximumnominal design voltage of the energized system that may besafely worked. The nominal design voltage is equal to thephase to phase voltage on multiphase circuits.3.1.11 If there is not multiphase exposure in a system areaand th
19、e voltage exposure is limited to phase (polarity on dcsystems) to ground potential, the phase (polarity on dc sys-tems) to ground potential shall be considered to be the nominaldesign voltage. If electrical equipment and devices are insu-lated, or isolated, or both, such that the multiphase exposure
20、 ona grounded wye circuit is removed, then the nominal designvoltage may be considered as the phase-to-ground voltage onthat circuit.NOTE 2The work practices and methods associated with removingmultiphase exposures at any given work site are not addressed in thisspecification. Users should refer to
21、ANSI C 2, National Safety Code,Section 44, for proper work practices.3.1.12 voltage, nominal designa nominal value consistentwith the latest revision on ANSI C 84.1, assigned to the circuitor system for the purpose of conveniently designating itsvoltage class.3.2 For definitions of other terms, refe
22、r to TerminologyF 819.4. Significance and Use4.1 This specification covers the minimum electrical,chemical, and physical properties guaranteed by the manufac-turer and the detailed procedures by which such properties areto be determined. The purchaser may at his option perform orhave performed any o
23、f these tests in order to verify theguarantee. Claims for failure to meet the specification aresubject to verification by the manufacturer.4.2 Line hose is used for personal protection; therefore,when authorizing its use, a margin of safety should be providedbetween the maximum voltage at which it i
24、s used and theproof-test voltage at which it is tested. The relationshipbetween proof-test voltage and the nominal maximum voltageat which line hose shall be used is shown in Table 1.4.3 It is common practice for the user of this type ofprotective equipment to prepare complete instructions andregula
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。