1、Designation:B911/B911M05 Designation: B911/B911M 12Standard Specification forACSR Twisted Pair Conductor (ACSR/TP)1This standard is issued under the fixed designation B911/B911M; the number immediately following the designation indicates the yearof original adoption or, in the case of revision, the
2、year of last revision. A number in parentheses indicates the year of last reapproval.A superscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers ACSR Twisted Pair Conductor (ACSR/TP) for use as overhead electric conductors (see N
3、otes 1and 2).NOTE 1The conductor is fabricated from two component ACSR conductors of the same size twisted helically around each other. This conductor isidentified by the code name of the component ACSR conductor followed by /TP or the size and type of the component ACSR conductor followed by/TP.NOT
4、E 2There are registered trademark symbols that are also used to identify the twisted pair notation. Consult cable manufacturers for additionaldetails.1.2 The values stated in inch-pound either SI units or SIinch-pound units are to be regarded separately as standard. Each Thevalues stated in each sys
5、tem may not be exact equivalents; therefore, each system shall be used independently of the other.Combining values from the two systems may result in non-conformance with the specification. Forstandard.1.2.1 For conductor sizes designated by AWG or kcmil, the requirements in SI units have been numer
6、ically converted fromcorresponding values stated or derived in inch-pound units. For conductor sizes designated by SI units only, the requirements arestated or derived in SI units. 1.2.1ForFor density, resistivity, and temperature, the values stated in SI units are to be regarded asstandard.1.3 This
7、 standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatorylimitations prior to use.2. Referenced Documents2.
8、1 The following documents of the issue in effect on the date of material purchase form a part of this specification to the extentreferenced herein:2.2 ASTM Standards:2B232/B232M Specification for Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR)3. Terminology3.1 Definitions
9、 of Terms Specific to This Standard:3.1.1 component conductorsthe two conductors twisted to fabricate the finished ACSR/TP.4. Ordering Information4.1 Orders for material under this specification shall include the following information:4.1.1 Quantity of each size,4.1.1.1 Conductor Sizekcmil area of t
10、he fabricated ACSR/TP (2 3 kcmil area of one of the component conductors),4.1.2 Conductor type and the number of wires of the component conductors,4.1.3 The type of steel core wire and type of coating,4.1.4 Place of inspection,4.1.5 Package size and type,4.1.6 Special package markings, if required,
11、and1This specification is under the jurisdiction of ASTM Committee B01 on Electrical Conductors and is the direct responsibility of Subcommittee B01.07 on Conductorsof Light Metals.Current edition approved Oct.1, 2005. Published November 2005. Originally approved in 2000. Last previous edition appro
12、ved in 2000 as B911/B911M00. DOI:10.1520/B0911_B0911M-05.Current edition approved April 1, 2012. Published May 2012. Originally approved in 2000. Last previous edition approved in 2005 as B911/B911M 05. DOI:10.1520/B0911_B0911M-12.2For referenced ASTM standards, visit the ASTM website, www.astm.org,
13、 or contact ASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM website.1This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what change
14、s have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the officia
15、l document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.4.1.7 Heavy wood lagging, if required.5. Requirements for Component Conductors5.1 Before twisting, the component conductors shall conform to the requirements of Specification
16、B232/B232M.6. Twist6.1 The component conductors shall be twisted about themselves with a complete twist every 9 ft 6 1 ft. This twist length shallbe measured between the twisting machine and the take-up reel with normal take-up tension on the ACSR/TP.NOTE 3The twist length can be altered as the ACSR
17、/TP is wound up onto the take-up reel. It may not have the same twist length as when the TPis removed from the reel.6.2 The direction of the twist shall be left hand.7. Construction Requirements7.1 Construction requirements are given in Table 1 for ACSR/TP.TABLE 1 Construction Requirements for TP Ty
18、pe Conductor Using Aluminum Conductor, Steel Reinforced (ACSR)Code WordAEquivalentSize AWG orkcmilComponent Composition Outer Dimensions in.Nominal MassBlb/1000ft Rated Strg. lbCResistanceDOhms/1000ftdc at 20CAWG orkcmil Aluminum Steel minor majorSwan / TP 1 4 6 3 0.0834 1 3 0.0834 0.250 3 0.500 115
19、 3700 0.2016Swanate / TP 1 4 7 3 0.0772 1 3 0.1029 0.257 3 0.514 115 4720 0.1994Swallow / TP 1/0 3 6 3 0.0937 1 3 0.0937 0.281 3 0.562 145 4600 0.1601Sparrow / TP 2/0 2 6 3 0.1052 1 3 0.1052 0.316 3 0.632 182 5660 0.1267Sparate / TP 2/0 2 7 3 0.0974 1 3 0.1299 0.325 3 0.650 213 7260 0.1253Robin / TP
20、 3/0 1 6 3 0.1181 1 3 0.1181 0.354 3 0.708 230 7120 0.1005Raven / TP 4/0 1/0 6 3 0.1327 1 3 0.1327 0.398 3 0.796 290 8760 0.0796Quail / TP 266.2 2/0 6 3 0.1489 1 3 0.1489 0.447 3 0.894 336 10600 0.0633Pigeon / TP 335.6 3/0 6 3 0.1672 1 3 0.1672 0.502 3 1.004 461 13200 0.0502Penguin / TP 423.2 4/0 6
21、3 0.1878 1 3 0.1878 0.563 3 1.126 582 16700 0.0398Jaeger / TP 456.4 228.2 18 3 0.1126 1 3 0.1126 0.563 3 1.126 495 12100 0.0376Waxwing / TP 533.6 266.8 18 3 0.1217 1 3 0.1217 0.609 3 1.218 579 13700 0.0322Spoonbill / TP 533.6 266.8 22 3 0.1101 7 3 0.0612 0.624 3 1.248 642 17400 0.0321Scaup / TP 533.
22、6 266.8 24 3 0.1054 7 3 0.0703 0.633 3 1.266 687 20000 0.0320Partridge / TP 533.6 266.8 26 3 0.1013 7 3 0.0788 0.642 3 1.284 734 22600 0.0319Junco / TP 533.6 266.8 30 3 0.0943 7 3 0.0943 0.660 3 1.320 835 27800 0.0316Ostrich / TP 600.0 300.0 26 3 0.1074 7 3 0.0835 0.680 3 1.360 825 25400 0.0283Merli
23、n / TP 672.8 336.4 18 3 0.1367 1 3 0.1367 0.683 3 1.366 730 17400 0.0255Trogon / TP 672.8 336.4 20 3 0.1297 7 3 0.0576 0.692 3 1.384 757 19000 0.0256Woodcock / TP 672.8 336.4 22 3 0.1237 7 3 0.0687 0.701 3 1.402 809 21800 0.0255Widgeon / TP 672.8 336.4 24 3 0.1184 7 3 0.0789 0.710 3 1.420 866 25000
24、0.0254Linnet / TP 672.8 336.4 26 3 0.1137 7 3 0.0884 0.720 3 1.440 925 28200 0.0253Oriole / TP 672.8 336.4 30 3 0.1059 7 3 0.1059 0.741 3 1.482 1053 34600 0.0251Chickadee / TP 795.0 397.5 18 3 0.1486 1 3 0.1486 0.743 3 1.486 862 19900 0.0216Ptarmigan / TP 795.0 397.5 20 3 0.1410 7 3 0.0627 0.752 3 1
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMB911B911M2012STANDARDSPECIFICATIONFORACSRTWISTEDPAIRCONDUCTORACSRTP 钢芯铝绞线 ACSR 导线 ACSRTP 标准 规格 PDF

链接地址:http://www.mydoc123.com/p-462749.html