ASHRAE REFRIGERATION SI CH 13-2010 SECONDARY COOLANTS IN REFRIGERATION SYSTEMS《制冷系统中等冷却剂》.pdf
《ASHRAE REFRIGERATION SI CH 13-2010 SECONDARY COOLANTS IN REFRIGERATION SYSTEMS《制冷系统中等冷却剂》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE REFRIGERATION SI CH 13-2010 SECONDARY COOLANTS IN REFRIGERATION SYSTEMS《制冷系统中等冷却剂》.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、13.1CHAPTER 13SECONDARY COOLANTS IN REFRIGERATION SYSTEMSCoolant Selection 13.1Design Considerations 13.2Applications. 13.5ECONDARY coolants are liquids used as heat transfer fluidsS that change temperature as they gain or lose heat energy with-out changing into another phase. For lower refrigeratio
2、n tempera-tures, this requires a coolant with a freezing point below that ofwater. This chapter discusses design considerations for compo-nents, system performance requirements, and applications for sec-ondary coolants. Related information can be found in Chapters 3, 4,22, 30, and 31 of the 2009 ASH
3、RAE HandbookFundamentals.COOLANT SELECTIONA secondary coolant must be compatible with other materials inthe system at the pressures and temperatures encountered for max-imum component reliability and operating life. The coolant shouldalso be compatible with the environment and the applicable safetyr
4、egulations, and should be economical to use and replace.The coolant should have a minimum freezing point of 3 K belowand preferably 8 K below the lowest temperature to which it will beexposed. When subjected to the lowest temperature in the system,coolant viscosity should be low enough to allow sati
5、sfactory heattransfer and reasonable pressure drop.Coolant vapor pressure should not exceed that allowed at themaximum temperature encountered. To avoid a vacuum in a low-vapor-pressure secondary coolant system, the coolant can bepressurized with pressure-regulated dry nitrogen in the expansiontank.
6、 However, some special secondary coolants such as thoseused for computer circuit cooling have a high solubility for nitro-gen and must therefore be isolated from the nitrogen with a suit-able diaphragm.Load Versus Flow RateThe secondary coolant pump is usually in the return line up-stream of the chi
7、ller. Therefore, the pumping rate is based on thedensity at the return temperature. The mass flow rate for a givenheat load is based on the desired temperature range and requiredcoefficient of heat transfer at the average bulk temperature.To determine heat transfer and pressure drop, the density, sp
8、e-cific heat, viscosity, and thermal conductivity are based on the aver-age bulk temperature of coolant in the heat exchanger, noting thatfilm temperature corrections are based on the average film temper-ature. Trial solutions of the secondary coolant-side coefficient com-pared to the overall coeffi
9、cient and total log mean temperaturedifference (LMTD) determine the average film temperature. Wherethe secondary coolant is cooled, the more viscous film reduces theheat transfer rate and raises the pressure drop compared to what canbe expected at the bulk temperature. Where the secondary coolant is
10、heated, the less viscous film approaches the heat transfer rate andpressure drop expected at the bulk temperature.The more turbulence and mixing of the bulk and film, the betterthe heat transfer and higher the pressure drop. Where secondarycoolant velocity in the tubes of a heat transfer device resu
11、lts in lam-inar flow, heat transfer can be improved by inserting spiral tapes orspring turbulators that promote mixing the bulk and film. This usu-ally increases pressure drop. The inside surface can also be spirallygrooved or augmented by other devices. Because the state of the artof heat transfer
12、is constantly improving, use the most cost-effectiveheat exchanger to provide optimum heat transfer and pressure drop.Energy costs for pumping secondary coolant must be consideredwhen selecting the fluid to be used and the heat exchangers to beinstalled.Pumping CostPumping costs are a function of th
13、e secondary coolant selected,load and temperature range where energy is transferred, pump pres-sure required by the system pressure drop (including that of thechiller), mechanical efficiencies of the pump and driver, and elec-trical efficiency and power factor (where the driver is an electricmotor).
14、 Small centrifugal pumps, operating in the range of approx-imately 3 L/s at 240 kPa to 9 L/s at 210 kPa, for 60 Hz applications,typically have 45 to 65% efficiency, respectively. Larger pumps,operating in the range of 30 L/s at 240 kPa to 95 L/s at 210 kPa, for60 Hz applications, typically have 75 t
15、o 85% efficiency, respec-tively.A pump should operate near its peak operating efficiency for theflow rate and pressure that usually exist. Secondary coolant temper-ature increases slightly from energy expended at the pump shaft. Ifa semihermetic electric motor is used as the driver, motor ineffi-cie
16、ncy is added as heat to the secondary coolant, and the total kilo-watt input to the motor must be considered in establishing load andtemperatures.Performance ComparisonsAssuming that the total refrigeration load at the evaporatorincludes the pump motor input and brine line insulation heat gains,as w
17、ell as the delivered beneficial cooling, tabulating typical second-ary coolant performance values helps in coolant selection. A 27 mmID smooth steel tube evaluated for pressure drop and internal heattransfer coefficient at the average bulk temperature of 6.7C and atemperature range of 5.6 K for 2.1
18、m/s tube-side velocity providescomparative data (Table 1) for some typical coolants. Table 2 ranksthe same coolants comparatively, using data from Table 1.For a given evaporator configuration, load, and temperaturerange, select a secondary coolant that gives satisfactory velocities,heat transfer, an
19、d pressure drop. At the 6.7C level, hydrocarbonand halocarbon secondary coolants must be pumped at a rate of 2.3to 3.0 times the rate of water-based secondary coolants for the sametemperature range.Higher pumping rates require larger coolant lines to keep thepumps pressure and power requirement with
20、in reasonable limits.Table 3 lists approximate ratios of pump power for secondary cool-ants. Heat transferred by a given secondary coolant affects the costand perhaps the configuration and pressure drop of a chiller andother heat exchangers in the system; therefore, Tables 2 and 3 areonly guides of
21、the relative merits of each coolant.The preparation of this chapter is assigned to TC 10.1, Custom EngineeredRefrigeration Systems.13.2 2010 ASHRAE HandbookRefrigeration (SI)Other ConsiderationsCorrosion must be considered when selecting coolant, inhibitor,and system components. The effect of second
22、ary coolant and inhib-itor toxicity on the health and safety of plant personnel or consumersof food and beverages must be considered. The flash point andexplosive limits of secondary coolant vapors must also be evaluated.Examine the secondary coolant stability for anticipated mois-ture, air, and con
23、taminants at the temperature limits of materialsused in the system. Skin temperatures of the hottest elements deter-mine secondary coolant stability.If defoaming additives are necessary, their effect on thermal sta-bility and coolant toxicity must be considered for the application.DESIGN CONSIDERATI
24、ONSSecondary coolant vapor pressure at the lowest operating tem-perature determines whether a vacuum could exist in the secondarycoolant system. To keep air and moisture out of the system,pressure-controlled dry nitrogen can be applied to the top level ofsecondary coolant (e.g., in the expansion tan
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEREFRIGERATIONSICH132010SECONDARYCOOLANTSINREFRIGERATIONSYSTEMS 制冷系统 中等 冷却剂 PDF

链接地址:http://www.mydoc123.com/p-455935.html