ASHRAE OR-16-C036-2016 Data Center IT Energy Recovery Satisfying ASHRAE W2-W5 Liquid-Cooling Classes.pdf
《ASHRAE OR-16-C036-2016 Data Center IT Energy Recovery Satisfying ASHRAE W2-W5 Liquid-Cooling Classes.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-16-C036-2016 Data Center IT Energy Recovery Satisfying ASHRAE W2-W5 Liquid-Cooling Classes.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Tahir Cader is a power and cooling strategist with HP servers. Roy Dragseth is a section leader and is responsible for the HPC services at UiT The Arctic University of Norway in Tromso, Norway. John Peterson is a technical program manager for HP in Takoma Park, MD. Data Center IT Energy Recovery: Sa
2、tisfying ASHRAE W2-W5 Liquid-Cooling Classes Roy Dragseth, MSc Tahir Cader, PhD John Peterson, PE Member ASHRAEABSTRACT HEADING Recapture of the waste heat from data centers remains a difficulty undertaking. For liquid-cooled data centers, the temperature of the water has been too low to make it eco
3、nomically feasible to put full-blown heat recovery systems in place. The University of Tromso (UiT), in collaboration with an IT manufacturer, has undertaken a detailed study to investigate the technical and economic feasibility of capturing the waste heat from its current data center. A single rack
4、 of servers has been converted to liquid-cooling (CPUs only). The rack was tested using inlet water temperatures that satisfy ASHRAE W2 W5 liquid-cooling classes. Under all inlet water temperatures investigated, the key IT device temperatures remained well within specification, while producing rack
5、exhaust water temperatures as high as 147.2 degrees F (64 degrees C). Using the current UiT cost of energy, and assuming that 50% of the waste heat from a 1 MW data center is re-used, there is the potential to save over 375,000 Euros annually. As UiT is building out a new 2 MW data center, the poten
6、tial for greater heat recapture can greatly expand the re-use of the data center waste heat to the broader campus. INTRODUCTION ASHRAE is aiming for buildings to achieve net-zero energy use, including energy-intensive mission critical facilities, by the year 2030. Often data center heat is considere
7、d a bane, and energy recovery from the exhaust water source is not an option because the heat rejection and distribution is limited by exhaust water temperature, along with other physical and monetary constraints. However, opportunities are becoming more available for new and existing facilities as
8、data center densities and water cooling temperatures move steadily higher. In 2011 ASHRAEs Technical Committee (TC) 9.9 Mission Critical Facilities, Technology Spaces, and Electronic Equipment released a whitepaper entitled Thermal Guidelines for Liquid Cooled Data Processing Environments to propose
9、 five (5) classes of water-cooled IT (Information Technology) equipment, based on entering cooling water temperatures. The 2011 paper depicts re-use of data center heat, but for the higher temperatures the heat re-use was considered largely theoretical. This paper shows the actual results of liquid-
10、cooling IT equipment with supply water temperatures from the W2 to W5 ranges. Testing was performed in a 500 kW data center to understand the percentage of heat rejected to the liquid-cooling system at various IT performance loads. Using the results from the quantification of percentage heat rejecte
11、d to the water, a simple payback analysis was conducted in order to estimate the potential monetary savings from the re-use of the waste heat captured from the exhaust water stream from the IT equipment. Air Handler Campus Building Heating Plant Data Center RadiatorSpecialty Equipment Air Cooling Wa
12、ter cooled RacksHeat Rejection ASHRAE LIQUID-COOLING CLASSES ASHRAEs thermal guidelines for liquid-cooled data processing equipment consists of increasing temperature ranges as shown in Table 1 ASHRAE 2011. Note that the facility water is for the water supply to the IT equipment. At the higher tempe
13、ratures, the exhaust water temperatures begin to be more viable as a stand-alone heat source for building heating, pre-heating hot water, etc. For the results discussed in this paper, the supply water temperature begins at 68 degrees F (20.0 degrees C) and increases in increments of 18 degrees F (10
14、.0 degrees C) up to 122 degrees F (50.0 degrees C). These measurements span the liquid-cooled classes of W2 to W5. For the heating systems, the temperature of the water returning from the data center equipment is of more interest - for this work, the achieved range was 104 degrees F (40.0 degrees C)
15、 to 149 degrees F (65.0 degrees C). Since higher temperature liquid-cooling can be used to more efficiently allow for the re-use of data center heat, a minimum lower exhaust water temperature should be established for a design before it can be considered a viable heat source. UNIVERSITY OF TROMSO CA
16、MPUS HEATING SYSTEM Figure 1 shows a simplified arrangement of the campus-wide heating system at the University of Tromso. The figure shows the connections between the IT equipment, the cooling plant, heating plant, and the hot water heating system supporting a campus building. Also shown is a suppl
17、emental heating plant that will be used to boost the heat supplied by the data center; at present, the campus needs approach 10 MW, while the data center is slated for 2 MW at the outset. Indirect heat transfer via liquid-to-liquid heat exchangers (L2L HX) protects each system from the other, and al
18、so prevents equipment damage as a result of water quality issues, flows, temperature swings, etc. In addition, the L2L HXs allow for flow and pressure de-coupling of any two water loops, thereby allowing for variable performance of each loop. TEST SET-UP TO QUANTIFY WASTE HEAT RECOVERY The Universit
19、y of Tromso (UiT), located in Tromso (Norway), is aggressively pursuing liquid-cooled IT and the re-use of the waste heat from its data center. UiT currently has a small number of liquid-cooled racks that it is using to better understand how to optimize its design for an upcoming 2 MW data center. I
20、n May-June 2015, several tests, at different input Table 1: ASHRAE Liquid Cooled Guidelines Liquid Cooling Classes IT Equipment Supply WaterTemperature Range (F/C)W1 35.6-62.6 / 2-17 W2 35.6-80.6 / 2-27 W3 35.6-89.6 / 2-32 W4 35.6-113.0 / 2-45 W5 133.0 / 45 Figure 1: Basic schematic diagram of the d
21、ata center supporting heating system Figure 2: Liquid cooled server; liquid cooling is provided for the CPUs, (other components) Heat Exchanger RackWater distribution system Pump water temperatures and workloads, were conducted to measure the quantity of waste heat that can be captured from servers
22、with liquid-cooled CPUs. It is important to note that the server manufacturer has agreed to engage in this R HPL is a suite of benchmarks test used to stress IT systems in order to gauge their performance. Following are the main variables used during the testing: IT workloads: idle, 50%, 80% and 100
23、%;IT inlet air temperature: 68 degrees F (20 degrees C);Water inlet temperature:o 68 degrees F (20 degrees C)o 86 degrees F (30 degrees C)o 104 degrees F (40 degrees C)o 122 degrees F (50 degrees C);Water flow rate: fixed at 2.3 GPM (520 L/hr);Fan speed: 10% and 20% of max speed.The set-up was adequ
24、ately instrumented to capture all key power consumption values, air and water temperatures, water flow rate(s), etc. All IT data was captured using a utility supplied by the IT equipment manufacturer with data for the key devices reported in the results section. Figure 3: Liquid-cooled racks in the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR16C0362016DATACENTERITENERGYRECOVERYSATISFYINGASHRAEW2W5LIQUIDCOOLINGCLASSESPDF

链接地址:http://www.mydoc123.com/p-455760.html