ASHRAE OR-05-9-3-2005 Dynamic Performance of a 30-kW Microturbine-Based CHP System《以一个30千瓦的微型燃气轮机为基础的CHP系统的动力性能》.pdf
《ASHRAE OR-05-9-3-2005 Dynamic Performance of a 30-kW Microturbine-Based CHP System《以一个30千瓦的微型燃气轮机为基础的CHP系统的动力性能》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-05-9-3-2005 Dynamic Performance of a 30-kW Microturbine-Based CHP System《以一个30千瓦的微型燃气轮机为基础的CHP系统的动力性能》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、OR-05-9-3 Dynamic Performance of a 30=kW Microturbine-Based CHP System Andrei Y. Petrov, PhD Member ASHRAE Abdolreza Zaltash, PhD Member ASHRAE D. Tom Rizy Solomon D. Labinov, PhD Randall L. Linkous ABSTRACT The goal of the Cooling, Heating, and Power (CHP) Program established in 2000 by the US Depa
2、rtment of Energy (DOE) is to provide research, development, and testing (both laboratory and field) and to accelerate implementation of distributed electric generation (DG) with thermally activated technologies (TAT). The objective is to provide DG with waste heat recovery, i.e., combination ofDGand
3、 waste heat recovery utilization to drive various TATunits (heat recovery, desiccant, absorption chiller units, etc.) and increase overall fuel efi- ciency of the technology. Dynamic tests of the CHP system, which were performed at the CHP Integration Laboratory of the Oak Ridge National Laboratory
4、(ORNL), are presented. The CHP system at the lab includes: a 30-kW microturbine generator, an air-to-water heat recovery unit, an indirect-red single-effect 1 O-ton (35-kW) absorption chiller, and indirect- and direct-red desiccant dehumidification units. The dynamic system response of the CHP syste
5、m was tested during both cold-start-up and power-dispatch (changing electric/ thermal demand) modes. The test results provide valuable information for both understanding CHPperformance as well as for use to develop better control tools for CHP equipment. INTRODUCTION DOES Cooling, Heating, and Power
6、 (CHP) Program was established in 2000. Its primary purpose is to provide research, development, and testing in order to accelerate implementa- tion of distributed electric generation (DG) with thermally activated technologies (TAT). The objective of the CHP Inte- gration Laboratory is to provide a
7、test bed for testing combined electric power generation and waste heat recovery utilization to drive various TAT units. The benefits of CHP include having both electric and thermal energy available from the same system and increasing overall fuel efficiency (NEP 2001). CHP system performance is an i
8、mportant aspect since some of these systems are intended to be used during backup/ emergency situations, and the time needed to reach a certain electrical/thermal demand from a cold start or during a load change becomes a crucial limiting factor. Also, the results of dynamic testing provide valuable
9、 data needed to create a dynamic model of the CHP system and provide input for developing better control hardware and software for the tech- nology. The dynamic performance of the 30-kW microturbine generator, which is a component ofthe CHP system presented in this paper, was previously outlined by
10、Langley et al. (2002), Rizy et al. (2002), and SCE (2004). Dynamic performance aspects of the CHP system with direct-fired desiccant dehu- midification unit are given by Petrov et al. (2004), so it is not considered in this paper. SYSTEM CONFIGURATION AND TEST EQUIPMENT The CHP system, which was tes
11、ted at the CHP Integration Laboratory, consists of a 30-kW microturbine generator (MTG), an air-to-water heat recovery unit (HRU), an indirect- fired (hot water-fired) IO-ton (35 kW) single-effect absorption chiller (AC) with air-handling unit (AHU), an indirect-fired desiccant dehumidification unit
12、 (IFDD), and a direct-fired desiccant dehumidification unit (DFDD) (Zaltash et al. 2003). The CHP system diagram is shown in Figure 1. The IFDD was used in these tests as a variable thermal load on the HRUs output (water side). There is an insulated air-duct ventilation system from the MTGs exhaust
13、to the HRU and to the DFDD. The flow from either of these TAT units is controlled via dampers. Also, there is a water loop from the HRU to the IFDD andor AC. - - A.Y. Petrov is a research associate, A. Zaltash is a research staff member, S.D. Labinov is a senior R for example, the heat recovery proc
14、ess does not begin simultaneously with the MTG start-up. The HRU operates in a “bypass” mode, which isolates the heat exchanger from the MTG exhaust gas by the HRUs diverter valve until the temperature of MTG exhaust gas at the inlet to HRU reaches a temperature setpoint value (195f5”F or 90.5f2.5”C
15、). The HRU uses the bypass mode to ASHRAE Transactions: Symposia 803 Table 1. Instrumentation and Measurement Precisions at the CHP Integration Laboratory Measurement Temperature Dew-point temperature Dew-point temperature Air flow Sensor Range Precision Resistive temperature detector -328 to 1,562F
16、 *0.2F (kO.lC) (-200 to 85OOC) Chilled mirror -40 to 140F zt0.2F (*O.lC) (-40 to 6OOC) Humidityhemperature transmitter -40 to 140F *0.4OF (*0.2OC) (-40 to 2 12OC) Fan evaluator* 500 to 5,000 scfm *2% (14.2 to 141.6 m3/min) I Water flow Gas flow - MTG Gas pressure - DFDD Gas pressure - MTG Power - MT
17、G Flow meter Pulse count test meter O to 415 cfh *0.2% 1 O pulseskf Pressure transducer (O to 11.8 m3h) O to I5 in wc (O to 3.73 kPa) O to 200 in wc (O to 49.73 kPa) Watt transducer O to 40 kW *OS% of full scale (O to 136,577 Btuh) *OS% of full scale Pressure transducer +OS% of full scale O to 100 g
18、pm (O to 0.38 m3/min) CHP System Startup with MTG Set for 20 kW *lYo CHP System Startup with MTG Set for 30 kW I Gas flow - DFDD 95.0 (35.0) 35.0 (1.7) Steady-State Percent Transient Value Deviation Time, min 20.0 O) could reach 20 minutes. Unfortunately, the operational condi- tions of the HRU comp
19、onent of the CHP system can?t always provide successful start of the AC operation with the first attempt. The first attempt doesn?t always produce sufficient thermal input to the AC unit (setpoint hot water temperature required to operate the AC could not be maintained). It was found that it usually
20、 requires two to three attempts before the AC starts to produce useful cooling capacity. The fluctuations caused by these attempts are not shown in Figure 8 in order to simpliQ it. In addition, the time constants do not include these attempts. The time between HRU and AC start-ups is usually 10 to 1
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR05932005DYNAMICPERFORMANCEOFA30KWMICROTURBINEBASEDCHPSYSTEM 一个 30 千瓦 微型 燃气轮机 基础 CHP 系统 动力 性能

链接地址:http://www.mydoc123.com/p-455662.html