ASHRAE LV-11-007-2011 Hot-Water Distribution System Piping Heat Loss Factors-Phase III Test Results.pdf
《ASHRAE LV-11-007-2011 Hot-Water Distribution System Piping Heat Loss Factors-Phase III Test Results.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LV-11-007-2011 Hot-Water Distribution System Piping Heat Loss Factors-Phase III Test Results.pdf(15页珍藏版)》请在麦多课文档分享上搜索。
1、2011 ASHRAE 727ABSTRACTThis paper describes results of recent laboratory tests onadditional piping types and sizes in a variety of environmentsincluding in-air, in-attic, and in-floor, both insulated and unin-sulated, and compares them to previous test results by theauthor on other pipe configuratio
2、ns and environments. Newpipes tested included chlorinated polyvinyl chloride (CPVC)and high-density cross-linked polyethylene (PEX), in both in-air and in-attic environments, and rigid copper, in both in-atticand in-floor environments. These tests allowed calculation ofmeasured piping heat loss (UA)
3、 factors under a variety ofdifferent temperature and flow conditions, with various insu-lation levels. This piping UA information can be used to esti-mate piping heat loss and steady-state temperature drop underany desired temperature and flow conditions. The UA data canadditionally be used to deter
4、mine piping cool-down rates afterflow has ceased. Piping heat loss data are one critical part ofthe information necessary to accurately estimate total energylosses associated with piping systems. These energy loss effectsextend beyond just energy loss from the pipe itself, and include,for example, i
5、ncreases in tank heat loss caused by the need toset temperatures higher to overcome temperature drop of waterflowing through the pipe. A separate related paper discussestime, water, and energy waste while waiting for hot water toarrive at fixtures.INTRODUCTIONResults of in-field investigations of ho
6、t-water distribution(HWD) system behavior by the author and others (Hiller andMiller 2002; Hiller et al. 2002; Henderson 2003; Lutz andKlein 1998; Klein 2004) revealed that time, water, and energywaste characteristics of HWD systems were deteriorating innewer building designs compared to earlier pra
7、ctice. Furtherinvestigation revealed that there was a lack of information andrigorous data on how HWD systems really function, especiallywith regard to factors that affect time, water, and energy waste.For that reason, laboratory tests were initiated, aimed at quan-tifying factors that affect HWD sy
8、stem performance (Hiller2005a, 2007, 2010). These laboratory tests quantified numer-ous HWD system piping behaviors under a variety of temper-ature, flow rate, environment, and insulation conditions. Thispaper reports on only the piping heat loss behaviors observed,and includes examples of how that
9、information can be used toanalyze HWD system performance. A related paper discussesthe time, water, and energy waste that occurs while waiting forhot water to arrive at fixtures (Hiller 2011).METHODOLOGYA test laboratory was established in Davis, CA, wherecomplete full-size piping systems could be c
10、onstructed,instrumented, and tested. The tests discussed in this paperwere on horizontal 0.75 in. (19 mm) rigid copper pipe inseveral in-attic and in-floor configurations. The tests alsocovered 0.75 in. (19 mm) chlorinated polyvinyl chloride(CPVC) piping both in still air and in-attic, 0.75 in. (19
11、mm)high-density cross-linked polyethylene (PEX) piping both instill air and in-attic, 0.5 inch (13 mm) PEX in-air, and 0.375 in.(10 mm) PEX in-air, all both bare, and insulated with 0.75 in.(19 mm) thick foam pipe insulation. (All the piping tested istechnically tubing, but we call it piping here to
12、 be consistentwith common practice.) The results are compared to those ofother pipe sizes, types, and environments previously tested(Hiller 2005b, 2006a, 2006b, 2008a, 2008b).Hot-Water Distribution System Piping Heat Loss FactorsPhase III: Test ResultsCarl C. Hiller, PhD, PEFellow ASHRAECarl C. Hill
13、er is president of Applied Energy Technology Co., Davis, CA.LV-11-0072011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction, distribution, or transmis
14、sion in either print or digital form is not permitted without ASHRAES prior written permission.728 ASHRAE TransactionsTest fixtures in the laboratory consisted of the “in-air”test fixture, where horizontal piping could be tested far fromsurrounding structures, and a “buried” test fixture containing2
15、5.5 tons (25 metric tons) of damp sand where horizontalpiping could be tested in a simulated under-slab environ-ment. For the most recent tests, an additional new piping testfixture was constructed. This ceiling/attic/floor test fixturewas constructed overhead in the laboratory with 0.5 in. (13mm) t
16、hick gypsum wallboard on the bottom side, and 8 in.(200 mm) wooden joists spaced on 24 in. (610 mm) centers.In the ceiling/attic configuration, the top side of the test rigwas open to air. In the floor configuration the top side of thetest rig was covered with 0.75 in. (19 mm) thick plywood.Tests on
17、 new piping types were first performed separately“in-air,” both bare, and insulated with 0.75 in. (19 mm) thickfoam pipe insulation, and then were also tested in the ceiling/attic/floor test fixture. All piping setups were serpentinearrangements with four to six parallel passes and three to fiveU-be
18、nds. Fast response immersion thermocouples wereinserted directly through the pipe side wall using a specialcompression fitting fashioned by the principle investigator.Thermocouples were located at the entrance to each pipe testsection, at each U-bend, and at the outlet. Data were storedat one-second
19、 intervals for all tests.Figure 1 shows the bare 0.75 in. (19 mm) nominal diam-eter CPVC test section (four-pass, approximately 95 ft long)as tested in air. Figure 2 shows the bare 0.75 in. (19 mm) PEXtest section as tested in air (four-pass, approximately 92 ftlong). Figure 3 shows the bare 0.5 in.
20、 (13 mm) PEX test sectionas tested in air (six-pass approximately, 125 ft long). Figure 4shows the bare 0.375 in. (10 mm) PEX test section as tested inair (six-pass, approximately 160 ft long). Figures 5 and 6 showtwo of the many in-attic 0.75 in. (19 mm) rigid CU test config-urations (four-pass, ap
21、proximately 95 ft long). All the in-airconfigurations were tested both bare, and with 0.75 in.(19 mm) thick foam pipe insulation.Many hundreds of tests were performed, independentlyvarying water flow rate, initial pipe temperature, entering hot-water temperature, room air temperature, and insulation
22、 level.The foam pipe insulation thermal conductivity was approxi-Figure 1 0.75 in. (19 mm) CPVC piping4-pass, in-air.Figure 2 0.75 in. (19 mm) PEX piping4-pass, in-air.Figure 3 0.5 in. (13 mm) PEX piping6-pass, in-air.Figure 4 0.375 in. (10 mm) PEX piping6-pass, in-air.2011 ASHRAE 729mately 0.02 Btu
23、/hftF (0.036 W/mK). Since pipe insulationR-values are based on the pipe outer diameter, this yielded theR-values shown in Table 1 for the pipe insulation tested. Theseare the values that were printed on the outside of the insulation.The pipe heat loss (UA) factors were determined differ-ently for th
24、e flowing vs. zero-flow (cool-down) tests. To deter-mine UAflowing, the steady-state (or near steady-state) drop intemperature was measured from inlet to outlet in the pipe. Themeasured temperature drop and flow rate were then used tocalculate UAflowingfrom the following formula:Q = (mCp)w(Thot in T
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELV110072011HOTWATERDISTRIBUTIONSYSTEMPIPINGHEATLOSSFACTORSPHASEIIITESTRESULTSPDF

链接地址:http://www.mydoc123.com/p-455381.html