ASHRAE LV-11-004-2011 Performance Evaluation of Handheld Airflow Instruments Applied to Commercial Kitchen Exhaust Systems.pdf
《ASHRAE LV-11-004-2011 Performance Evaluation of Handheld Airflow Instruments Applied to Commercial Kitchen Exhaust Systems.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LV-11-004-2011 Performance Evaluation of Handheld Airflow Instruments Applied to Commercial Kitchen Exhaust Systems.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、690 ASHRAE TransactionsThis paper is based on findings resulting from ASHRAE Research Project RP-1376.ABSTRACTLaboratory measurements have been made to determinethe accuracy of several handheld instruments when used tomeasure the exhaust airflow rates during commercial kitchenairflow balancing. The
2、instruments included 4 in. (0.1 m) and2.75 in. (0.07 m) rotating vane anemometers, a hot filmanemometer, a velocity grid, and flow hoods with 2 2 ft(0.61 0.61 m) and 2 4 ft (0.61 1.22 m) hoods. Grease filterconfigurations included conventional baffle filters, cyclonefilters, and slot filters mounted
3、 in an 8 ft (2.4 m) canopy exhausthood. Exhaust airflow rate measurements were made atapproximately 2000, 3000, and 4000 scfm (0.94, 1.4, and1.9 m3/s) for each instrument and each filter type. Measure-ments were made with a gas fryer, half-size electric oven, anda gas underfired broiler idling (hot
4、tests) and turned off (coldtests) to determine the influence of hot appliances. Flow ratesdetermined using calibrated flow nozzles in the supply airsystem agreed to within a few percentage points of thosemeasured using the flow hoods. The other instruments gener-ally did not provide accurate results
5、 unless an appropriatecorrection factor, or K-factor, was used.INTRODUCTIONProper airflow balance is necessary in commercial kitch-ens to capture and contain the cooking effluent within theexhaust system, to allow for proper airflow rate and the result-ing minimal operating energy as the cooking loa
6、d changes,and to provide adequate indoor environmental air quality forthe cook staff and other building occupants. At present, the airbalancing industry and the commercial kitchen ventilationindustry each focus on different hardware, use different instru-mentation, and have developed their own test
7、protocols. TheInternational Mechanical Code (IMC) requires that properairflow rates be verified but offers no acceptable method toaccomplish this requirement. Other related documents includeANSI/ASHRAE Standard 111-2008, ANSI/ASHRAE Stan-dard 154-2003, ASTM F1704-05, and California EnergyCommission
8、Design Guides 1 and 2 (ASHRAE 2003, 2008;ASTM 2005; CEC 2004a, 2004b). The objective of this research is to provide a laboratory-developed/field-validated method of test (MOT) applicable tocommercial kitchens that would include recommended instru-mentation and test procedures to verify the supply an
9、d exhaustairflow rate balance and to measure the associated air pressuredifferences. This paper summarizes the laboratory testsconducted on three types of grease filters installed in a canopyexhaust hood. TEST FACILITYThe test facility is located at the Thermal EnvironmentalEngineering Laboratory in
10、 the Department of MechanicalEngineering at the University of Minnesota. It was initiallyconstructed for ASHRAE RP-745, and subsequently used forASHRAE RP-1375 to characterize the emissions from variouscommercial kitchen cooking appliances and representativefood products using an 8 ft (2.4 m) canopy
11、 exhaust hood,exhaust duct, and exhaust fan. Details of the initial configura-tion are contained in the ASHRAE RP-745 Phase II, FinalReport. Performance Evaluation of Handheld Airflow Instruments Applied to Commercial Kitchen Exhaust SystemsThomas H. Kuehn, PhD, PE Bernard A. Olson, PhDFellow ASHRAE
12、Kevin Campbell Andrew J. HawkinsonStudent Member ASHRAEThomas H. Kuehn is a professor, Bernard A. Olson is a senior research associate, and Kevin Campbell and Andrew J. Hawkinson areresearch assistants in the Department of Mechanical Engineering, University of Minnesota, Minneapolis, MN.LV-11-004 (R
13、P-1376)2011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without
14、ASHRAES prior written permission.2011 ASHRAE 691Significant modifications were required for the presentwork. Most were required for airflow handling and monitor-ing. Constraints on the length of the exhaust duct due to labo-ratory size prevented accurate direct measurements of theexhaust airflow rat
15、e. Thus, accurate flow rate measurementscould only be measured on the supply side. With an airtightfacility, the supply and exhaust flows rates would be equalwhen no heat sources were used and no additional flow wasadded. Several changes were made to the existing kitchen facil-ity, including efforts
16、 to make the entire kitchen airtight, relo-cating the exhaust duct collar on the hood to the right-rearcorner, and moving the hood so it was flush with the right-handwall. This wall acted as a symmetry plane so the hood wouldsimulate airflow entering a 16 ft (4.8 m) long hood; the 8 ft(2.4 m) hood w
17、as actually operational and tested while theother 8 ft (2.4 m) was the imaginary half. In addition, twoacrylic plastic windows were installed in the right and leftwalls near the front lower edge of the hood for optical evalu-ation of capture and containment of the cooking effluent. To provide measur
18、ed amounts of makeup air that repre-sented supply air from remote diffusers and transfer air fromother parts of the building, existing vinyl mesh screens thatformed the back wall of the facility were replaced by twogeneral air supply units. These were designed to be displace-ment air units with low
19、discharge velocity and formed the rearwall of the test kitchen. One or both could be removed to allowfor installation and removal of appliances, makeup air units,hoods, and any other large piece of equipment. Air wassupplied through an 8 in. (0.2 m) diameter flexible ductconnected at the top center
20、of each chamber. The air passedthrough an internal diffuser section 30 in. (0.76 m) long, andthen discharged through perforated panels that cover theremaining 79 in. (2 m) height of the chamber. The two sectionswere clamped together and to the outward face of the steelframe of the test kitchen with
21、a gasket interface. A sectionview of the test facility is shown in Figure 1.Air was supplied to the test facility through two sources,the general supply units described above and various dedi-cated makeup air units. A perimeter makeup air unit installedin front of the hood as shown in Figure 1 was u
22、sed in the testsreported here. A single fan served the entire supply air system using avariable frequency drive (VFD) connected to a 7.5 hp (5.6 kW)belt driven fan for airflow control. From a common 16 in.(0.41 m) diameter 72 in. (1.83 m) straight duct, two takeoffducts using 45 degree elbows provid
23、ed air to two parallel16 in. (0.41 m) diameter legs. One leg supplied air to thegeneral supply air units that formed the back wall of the testfacility, and the other supplied the various dedicated makeupair units. In both legs, a Model 2350 Metering Venturi Nozzle,manufactured by Lamba Square, was u
24、sed to monitor airflowrates. A full calibration of each Venturi nozzle was conductedby the Colorado Engineering Experiment Station, Inc. (CEESI),Figure 1 Schematic of commercial kitchen test facility used for flow measurement tests.692 ASHRAE Transactionsby sending the entire supply duct system to t
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELV110042011PERFORMANCEEVALUATIONOFHANDHELDAIRFLOWINSTRUMENTSAPPLIEDTOCOMMERCIALKITCHENEXHAUSTSYSTEMSPDF

链接地址:http://www.mydoc123.com/p-455378.html