ASHRAE 4722-2004 Integrated Damper and Pressure Reset for VAV Supply Air Fan Control《为变风量空调送风风机控制用的综合阻尼器和压力复位》.pdf
《ASHRAE 4722-2004 Integrated Damper and Pressure Reset for VAV Supply Air Fan Control《为变风量空调送风风机控制用的综合阻尼器和压力复位》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 4722-2004 Integrated Damper and Pressure Reset for VAV Supply Air Fan Control《为变风量空调送风风机控制用的综合阻尼器和压力复位》.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、4722 Integrated Damper and Pressure Reset for VAV Supply Air Fan Control Guanghua Wei, P.E. Associate Member ASHRAE Mingsheng Liu, Ph.D., P.E Member ASHRAE David E. Claridge, Ph.D., P.E. Member ASHRAE ABSTRACT This paper presents an integratgd damper and pressure reset (IDPR) method for variable air
2、 volume (VAV) system fan control. The IDPR method controls the static pressure at a minimum required level while maintaining at least one terrni- na1 box damper at full open position. When the entire system is flawless, the fan speed is controlled in a way similar to the terminal regulated air volum
3、e (TRAV) method to maintain at least one terminal box damper full open. When system faults exist, however, this controlstrategy uses less fan power than the TRAV method. The IDPR method can be implemented in both full DDC (direct digital control) systems and hybrid systems, where only the space temp
4、erature readings are communicated to the DDCcontroller at the air-handler level and the terminal boxes are controlled by pneumatic controllers. INTRODUCTION In a VAV system, the total supply airflow rate decreases as the building load decreases until the airflow reaches the minimum value. To ensure
5、adequate airflow under all load conditions, the supply air fan is often required to provide enough static pressure in a preselected duct location. When the duct static pressure is not satisfied, the control system can modulate the volume control device, such as a variable frequency drive (VFD), on t
6、he fan motor to maintain the static pressure at its setpoint. The duct static pressure sensor is typically located two- thirds of the way downstream in the main trunk of the supply air duct. Although this old rule of thumb is no longer recom- mended by ASHRAE (ASHRAE 1999), it is quite common in man
7、y existing systems. The fan usually maintains a constant static pressure setpoint. The setpoint is selected such that it provides enough static to terminal VAV boxes under design full-load conditions. However, under partial-load conditions, as we will discuss later, the static pressure required at t
8、he terminal VAV boxes may be far less than this setpoint. To improve partial-load operations, static pressure can be decreased to save fan power (Hartman 1989; Englander and Norford 1992; Warren 1993; Liu et al. 1997). A popular method is to reset the static pressure setpoint as a function of the ou
9、tside air temperature. This is reasonably accurate in envelope-dominated buildings (i.e., buildings with large ratios of exterior zones). Other methods reset the static pressure based on total supply airflow rate or supply air fan speed, since they are also indicators of the building load. The selec
10、tion of the reset schedule depends on a number of factors, such as internal load, envelope, and occupancy schedule. Expert judg- ment is required to set up the reset schedule. Due to the complex nature of building systems, even those control experts are sometimes very conservative in setting up the
11、reset schedules. The terminal regulated air volume (TRAV) control method integrates terminal box operation with supply air fan control (Hartman 1989). The TRAV method controls the supply fan based on real-time terminal box airflow require- ments (often calculated by the DDC controller) rather than m
12、eeting a duct static pressure setpoint. When the AHU and terminal boxes are flawless, the TRAV method minimizes fan power consumption. Similar control algorithms have been proposed by others. Englander and Norford (1992) used primary airflow error signals from one or more zones to modu- late the sta
13、tic pressure or fan speed. Warren (1993) presented a control strategy that resets the fan static pressure setpoint based on terminal box flow requirements. The reset signal Guanghua Wei is an assistant research engineer at the Energy Systems Laboratory and David E. Claridge is a professor in the Dep
14、artment of Mechanical Engineering, Texas A otherwise, the system operation could be unpredictable. For some hybrid systems, the DDC system only has indi- vidual zone space temperature input information. The actua- tors (dampers and/or reheat valves) at the terminal VAV boxes are controlled by pneuma
15、tic controllers. These boxes interface with the DDC system through EP (electric to pneumatic) transducers. Since the DDC system does not have information on airflows at the box level, the above-mentioned control strat- egies are not applicable. Therefore, an alternative or improve- ments for these c
16、ontrol strategies are needed. This paper discusses an improved control strategy that can be used with both full DDC systems and hybrid systems. In order to provide building comfort with low fan power consumption, the fan can be modulated based on the maxi- mum VAV box damper position (damper control
17、 output signal), combined with a predefined static pressure reset schedule. We call this control strategy the integrated damper and pressure reset (IDPR) method. It requires modulating the fan speed to maintain the maximum VAV box damper position at 95% open, as long as the static pressure is mainta
18、ined below the calculated setpoint based on a predefined reset schedule. THE IDPR CONTROL METHOD Theory We introduce the IDPR method by discussing the static pressure control method for a VAV system. To simplify the discussion, we assume the VAV system is equipped with a VFD. The static pressure sen
19、sor is typically located two-thirds of the way downstream in the main supply air duct for many existing systems. The static pressure control method main- tains the setpoint of the static pressure by modulating the fan speed. When the static pressure is lower than the setpoint, the fan speeds up to p
20、rovide more airflow (static) to meet the box needs, and vice-versa. A constant setpoint value specified by the design engineer is often used regardless of the building load conditions. Under partial-load conditions, however, the static pres- sure required at the terminal VAV boxes may be far less th
21、an this constant setpoint since the pressure drop across the box is proportional to the square of the airflow rate, as Equation 1 illustrates. AP=CvxQ* (1) where A = pressure drop across VAV box volume damper, Pa (in. Q = airflow, L/min (CFM) Cv = flow coefficient, Pa x min2 / L2 (in. H20 / CFM2) Fo
22、r example, at 70% design flow rate, the static pressure required at the VAV box is approximately 50% of the static pressure corresponding to the design flow rate (assuming the VAV box damper is wide open in both cases; that is, Cv is the same). Under this partial-load condition, the static pressure
23、loss between the locatiop of the static pressure sensor and the terminal box is also much less than that under full-load condi- tion. due to reduced airflow. This pressure loss reduction increases the static pressure in front of the terminal VAV box when a constant static pressure setpoint is used,
24、and the pres- sure drop (AP) across the VAV box volume damper increases. To maintain space condition, the VAV box damper has to move toward the closed position (to increase Cv) in order to reduce the airflow to 70% of design value. Consequently, a significant amount of fan power is wasted through th
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE47222004INTEGRATEDDAMPERANDPRESSURERESETFORVAVSUPPLYAIRFANCONTROL 风量 空调 送风 风机 控制 综合 阻尼 压力 复位 PDF

链接地址:http://www.mydoc123.com/p-454305.html