ANSI UL 218 CRD-2018 UL Standard for Safety Fire Pump Controllers - Section Paragraph Reference Section 14.3.4 Subject Line Reactors Used with Variable Frequency Drives (Edition 3.pdf
《ANSI UL 218 CRD-2018 UL Standard for Safety Fire Pump Controllers - Section Paragraph Reference Section 14.3.4 Subject Line Reactors Used with Variable Frequency Drives (Edition 3.pdf》由会员分享,可在线阅读,更多相关《ANSI UL 218 CRD-2018 UL Standard for Safety Fire Pump Controllers - Section Paragraph Reference Section 14.3.4 Subject Line Reactors Used with Variable Frequency Drives (Edition 3.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): QYZSStandard Number: UL 218Standard Title: Standard for Fire Pump ControllersEdition Date: September 16, 2015Edition Number: 3Section / Paragraph Reference: Section 14.3.4Subject: Line Reactors Used w
3、ith Variable Frequency DrivesDECISION:14.3.4 A line reactor rated for continuous duty shall be provided. It shall be installed ahead of the VFDand shall have a 5 percent impedance rating as a minimum. A reactor provided as an integral part of aVFD may satisfy all or part of the 5 percent impedance i
4、f the reactor is connected on the line side of theconverter (rectifier) section of the VFD.Note 1: This is to reduce the likelihood of capacitor and rectifier damage and to avoid capacitor overvoltage shutdown of the VFDand to reduce the input current harmonics to near sinusoidal to avoid overheatin
5、g the VFD input circuit components and wiring. Thisreactor is required whether or not the controller or its VFD also contain a DC link reactor, choke (inductor), or swinging choke. Bybeing ahead of the VFD, it protects both the input rectifiers or SCRs, as well as reducing capacitor current (ripple
6、current) andcapacitor over-voltage (and over-voltage trip) in the energy storage capacitors. The line reactor enhances line quality by suppressingline transients and disturbances.Note 2: A DC link reactor or choke does not protect the input rectifiers or SCRs from line voltage transients.RATIONALE F
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIUL218CRD2018ULSTANDARDFORSAFETYFIREPUMPCONTROLLERSSECTIONPARAGRAPHREFERENCESECTION1434SUBJECTLINEREACTORSUSEDWITHVARIABLEFREQUENCYDRIVESEDITION3PDF

链接地址:http://www.mydoc123.com/p-439058.html