ANSI ATIS 0600015.12-2016 Energy Efficiency for Telecommunication Equipment Methodology for Measurement and Reporting Power Systems - Uninterruptible Power Supply Requirements.pdf
《ANSI ATIS 0600015.12-2016 Energy Efficiency for Telecommunication Equipment Methodology for Measurement and Reporting Power Systems - Uninterruptible Power Supply Requirements.pdf》由会员分享,可在线阅读,更多相关《ANSI ATIS 0600015.12-2016 Energy Efficiency for Telecommunication Equipment Methodology for Measurement and Reporting Power Systems - Uninterruptible Power Supply Requirements.pdf(29页珍藏版)》请在麦多课文档分享上搜索。
1、 AMERICAN NATIONAL STANDARD FOR TELECOMMUNICATIONS ATIS-0600015.12.2016 Energy Efficiency for Telecommunication Equipment: Methodology for Measurement and Reporting Power Systems Uninterruptible Power Supply Requirements As a leading technology and solutions development organization, the Alliance fo
2、r Telecommunications Industry Solutions (ATIS) brings together the top global ICT companies to advance the industrys most pressing business priorities. ATIS nearly 200 member companies are currently working to address the All-IP transition, 5G, network functions virtualization, big data analytics, c
3、loud services, device solutions, emergency services, M2M, cyber security, network evolution, quality of service, billing support, operations, and much more. These priorities follow a fast-track development lifecycle from design and innovation through standards, specifications, requirements, business
4、 use cases, software toolkits, open source solutions, and interoperability testing. ATIS is accredited by the American National Standards Institute (ANSI). The organization is the North American Organizational Partner for the 3rd Generation Partnership Project (3GPP), a founding Partner of the oneM2
5、M global initiative, a member of and major U.S. contributor to the International Telecommunication Union (ITU), as well as a member of the Inter-American Telecommunication Commission (CITEL). For more information, visit www.atis.org. AMERICAN NATIONAL STANDARD Approval of an American National Standa
6、rd requires review by ANSI that the requirements for due process, consensus, and other criteria for approval have been met by the standards developer. Consensus is established when, in the judgment of the ANSI Board of Standards Review, substantial agreement has been reached by directly and material
7、ly affected interests. Substantial agreement means much more than a simple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that a concerted effort be made towards their resolution. The use of American National Standards is completely volun
8、tary; their existence does not in any respect preclude anyone, whether he has approved the standards or not, from manufacturing, marketing, purchasing, or using products, processes, or procedures not conforming to the standards. The American National Standards Institute does not develop standards an
9、d will in no circumstances give an interpretation of any American National Standard. Moreover, no person shall have the right or authority to issue an interpretation of an American National Standard in the name of the American National Standards Institute. Requests for interpretations should be addr
10、essed to the secretariat or sponsor whose name appears on the title page of this standard. CAUTION NOTICE: This American National Standard may be revised or withdrawn at any time. The procedures of the American National Standards Institute require that action be taken periodically to reaffirm, revis
11、e, or withdraw this standard. Purchasers of American National Standards may receive current information on all standards by calling or writing the American National Standards Institute. Notice of Disclaimer however, it is also the least energy-efficient of the typical UPS operating modes. This mode
12、is sometimes called “Protected” or “Online”, and is referred to by standard IEC) definition as VFI. Dual-Corded End-use equipment with dual AC input power supplies, either of which can supply the entire equipment shelf. The purpose of the redundancy is for reliability, and this type of ICT equipment
13、 is commonly used in applications where maximum reliability (uptime) is desired/required. This is the equivalent of the telecommunications industrys A/B feeds for -48VDC-powered equipment. Line-Interactive A UPS operating mode where most of the power to the loads is provided by commercial AC; howeve
14、r any abnormalities in the sine wave are “fixed” by the addition of small amounts of power from the battery-fed inverter or via a self-adjusting transformer (which could be an autotransformer). This mode provides a compromise between the less-reliable Standby Mode, and the less energy efficient Doub
15、le-Conversion Mode. In other words, this mode has better energy efficiency than Double-Conversion Mode, but not as good as Standby Mode; and it provides more reliable power than Standby Mode, but not as reliable as that provided by Double-Conversion Mode. The IEC refers to this Line-Interactive oper
16、ating mode as VI. 1Available at: . 2Available at: . 3Available at: . 4Available at: . 5Available at: . 6Available at: . ATIS-0600015.xx.2009 3 Term Definition n+1 Internal redundancy (where loss of a single component doesnt jeopardize the common load) of inverters and/or rectifiers within a UPS. For
17、 example, a UPS system may be composed of 5 internal 25 kVA inverter modules, meaning that the total capacity of the system is 125 kVA, but the n+1 capacity of the system is 100 kVA. N+1 Multiple UPS power system sources are used to feed a maximum load of N, but loss of a single source leaves remain
18、ing sources capable of feeding the load. Standby Mode A UPS operating mode where the incoming AC power is routed directly to the equipment loads (with only a small portion being normally siphoned off to trickle charge the batteries through a rectifier). Backup is provided through a static transfer s
19、witch which quickly (typically within 1.2 to 4 ms) transfers the load(s) to the battery-fed inverter(s) when a commercial AC power problem is sensed. This mode of operating a UPS provides the least power protection (and thus the least reliability) to the load(s), but is the most energy-efficient mod
20、e of UPS operation. This mode is sometimes called Eco-mode because of its energy efficiency. It is also sometimes called “Off-line” mode. The standard IEC definition for this mode is called VFD. Tier rating system A rating system for critical power and HVAC systems defining the level of redundancy a
21、nd reliability on a scale from I to IV (1 to 4) with IV being the most redundant/reliable. Uninterruptible Power Supply An Uninterruptible Power Supply/System (UPS) provides power to AC loads, conditioned against commercial power faults by use of a rectifier, battery, and inverter systems, and possi
22、bly other power conditioning components. 3.2 Acronyms but the least reliable topology, as the protection for the loads from extreme over or under voltage or frequency events relies on a single-point-of-failure static transfer switch which typically takes 1.2-4 ms to transfer the loads to the battery
23、-fed inverter. This operating mode is represented by Figure 4.2 below. ATIS-0600015.xx.2009 6 Figure 4.2 VFD (Standby/Off-Line/Eco) Operating Mode An operating mode that provides some compromise between energy efficiency and output power reliability is known as Line-Interactive or Voltage Independen
24、t (VI). In this design or operating mode, most of the power is supplied from the commercial AC source, but often through either an isolating or auto-transformer, which can perform voltage adjustments, and/or the control electronics turn on the IGBTs of the inverter(s) periodically (when the need is
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIATIS0600015122016ENERGYEFFICIENCYFORTELECOMMUNICATIONEQUIPMENTMETHODOLOGYFORMEASUREMENTANDREPORTINGPOWERSYSTEMSUNINTERRUPTIBLEPOWERSUPPLYREQUIREMENTSPDF

链接地址:http://www.mydoc123.com/p-433462.html