ANSI ASTM E2257-2017 Standard Test Method for Room Fire Test of Wall and Ceiling Materials and Assemblies.pdf
《ANSI ASTM E2257-2017 Standard Test Method for Room Fire Test of Wall and Ceiling Materials and Assemblies.pdf》由会员分享,可在线阅读,更多相关《ANSI ASTM E2257-2017 Standard Test Method for Room Fire Test of Wall and Ceiling Materials and Assemblies.pdf(19页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2257 17 An American National StandardStandard Test Method forRoom Fire Test of Wall and Ceiling Materials andAssemblies1This standard is issued under the fixed designation E2257; the number immediately following the designation indicates the year oforiginal adoption or, in the case of
2、revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This is a fire-test-response standard.1.2 This test method is intended to evaluate, under speci
3、fiedfire-exposure conditions, the contribution to room fire growthprovided by wall or ceiling materials and assemblies, or both.The method is not intended to evaluate the fire endurance ofassemblies or fires originating in the wall assembly. Themethod provides a means to evaluate the effectiveness o
4、fthermal barriers in restricting the contribution of combustiblematerials in the wall assembly to fire growth in a room fire.1.3 This test method, simulating a fire in the corner of a2420 by 3630 mm (8 by 12 ft) room containing a single opendoorway, provides a means to evaluate the relative perfor-m
5、ance of specified wall and ceiling materials or assemblieswhen they are used together in the same relationship within anenclosure, and simulating the manner in which they will beused.1.4 This test method is intended to evaluate the contributionto fire growth provided by a surface product using a spe
6、cifiedignition source. It shall, however, be noted that the type,position and heat output of the ignition source will consider-ably influence fire growth. The thermal exposure conditionsfrom the ignition source specified in this method will result inflashover during the 20 min duration for many comm
7、on finishmaterials, in particular if specimens are mounted on the wallsand the ceiling (standard configuration).1.5 This test method provides a means for evaluating walland ceiling finish materials and assemblies, including panels,tiles, boards, sprayed or brushed coatings, etc. This test methodis n
8、ot intended to evaluate flooring materials or furnishings.1.6 This method shall be used in conjunction with GuideE603, which covers instrumentation and the general effect ofvarious parameters, and Guide E2067, which deals withfull-scale oxygen consumption calorimetry.1.7 The values stated in SI unit
9、s are to be regarded as thestandard. The units given in parentheses are for informationonly.1.8 The text of this standard references notes and footnoteswhich provide explanatory information. These notes and foot-notes (excluding those in figures) shall not be considered asrequirements of the standar
10、d.1.9 This standard is used to measure and describe theresponse of materials, products, or assemblies to heat and flameunder controlled conditions, but does not by itself incorporateall factors required for fire-hazard or fire-risk assessment of thematerials, products, or assemblies under actual fir
11、e conditions.1.10 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1
12、.11 Fire testing is inherently hazardous. Adequate safe-guards for personnel and property shall be employed inconducting these tests.1.12 This international standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles
13、for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2E84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE136 Test Method for Behavio
14、r of Materials in a VerticalTube Furnace at 750CE176 Terminology of Fire StandardsE603 Guide for Room Fire ExperimentsE2067 Practice for Full-Scale Oxygen Consumption Calo-rimetry Fire Tests1This test method is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsib
15、ility of Subcommittee E05.21 on Smoke andCombustion Products.Current edition approved April 15, 2017. Published April 2017. Originallyapproved in 2003. Last previous edition approved in 2016 as E2257-16. DOI:10.1520/E2257-17.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcon
16、tact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West
17、Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trad
18、e Organization Technical Barriers to Trade (TBT) Committee.12.2 ISO Standards:ISO 9705 Fire TestsReaction to FireRoom Fire Test3ISO 13943 Fire SafetyVocabulary32.3 NFPA Standards:NFPA 265 Standard Method of Tests for Evaluating RoomFire Growth Contribution of Textile Wall Coverings4NFPA 286 Standard
19、 Method of Tests for Evaluating Contri-bution of Wall and Ceiling Interior Finish to Room FireGrowth43. Terminology3.1 DefinitionsFor definitions of terms used in thisstandard, see Terminology E176 and ISO 13943. In case ofconflict, the definitions given in Terminology E176 shallprevail.3.1.1 assemb
20、ly, na unit or structure composed of a com-bination of materials or products, or both. E1763.1.2 flashover, nthe rapid transitionto a state of totalsurface involvement in a fire of combustible materials withinan enclosure. E1763.1.3 heat flux, nheat transfer to a surface per unit area,per unit time.
21、 E1763.1.4 heat release rate, nthe heat evolved from the speci-men per unit time. E1763.1.5 optical density of smoke, na measure of the attenu-ation of a light beam through smoke, expressed as the commonlogarithm of the ratio of the incident flux, I0, to the transmittedflux, I. E1763.1.6 oxygen cons
22、umption principle, nthe expression ofthe relationship between the mass of oxygen consumed duringcombustion and the heat released. E1763.1.7 smoke, nthe airborne solid and liquid particulatesand gases evolved when a material undergoes pyrolysis orcombustion. E1763.1.8 smoke obscuration, nreduction of
23、 light transmissionby smoke as measured by light attenuation. E1763.2 Definitions of Terms Specific to This Standard:3.2.1 specimen, nrepresentative piece of the product,which is to be tested together with any substrate or treatment.4. Summary of Test Method4.1 This method uses a gas burner to produ
24、ce a diffusionflame in contact with the walls and ceiling in the corner of a2420 by 3630 by 2420 mm (8 by 12 by 8 ft) high room. Theburner produces a prescribed net rate of heat output of 100 kW(5690 Btu/min) during the first 10 min, followed by 300 kW(17 060 Btu/min) during the next 10 min. The con
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIASTME22572017STANDARDTESTMETHODFORROOMFIRETESTOFWALLANDCEILINGMATERIALSANDASSEMBLIESPDF

链接地址:http://www.mydoc123.com/p-432606.html