ANSI American Society of Sanitary Engineering 1015-2011 Performance Requirements for Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Preventio.pdf
《ANSI American Society of Sanitary Engineering 1015-2011 Performance Requirements for Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Preventio.pdf》由会员分享,可在线阅读,更多相关《ANSI American Society of Sanitary Engineering 1015-2011 Performance Requirements for Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Preventio.pdf(36页珍藏版)》请在麦多课文档分享上搜索。
1、ASSE Standard #1015-2011ASSE Board Approved: August 2011ANSI Approved: August 2011An American National StandardPerformance Requirements for Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Prevention AssembliesASSE InternationalDouble Check Backflow Prevention As
2、semblies and i Double Check Fire Protection Backflow Prevention AssembliesASSE 1015-2011General InformationNeither this standard, nor any portion thereof, may be reproduced without the written consent of ASSE International.Instructions for receiving authorization to display the ASSE Seal are availab
3、le from ASSEs International Office. Organizations wishing to adopt or list any ASSE Standard should print the ASSE Standard number on the cover page first and in equal or larger type to that of the adopting or listing organization.ASSE InternationalMokena, IllinoisCopyright 2011, 2009, 2005, 1999, 1
4、993, 1988, 1971All rights reserved.ii Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Prevention AssembliesASSE 1015-2011Double Check Backflow Prevention Assemblies and iii Double Check Fire Protection Backflow Prevention AssembliesASSE 1015-2011ForewordThis for
5、eword shall not be considered a part of the standard. However, it is offered to provide background information.ASSE Product Standards are developed in the interest of consumer safety.The recognition of probable sources or causes of contamination of a potable water supply system and the application o
6、f essential devices, or means, to prevent the entrance of contaminants to the potable water system, causing it to become unfit for human consumption, is vital to the maintenance of its continued potability.There are two basic and practiced methods for the protection of potable water supplies:a) Prot
7、ection by ContainmentThe isolation, by suitable devices or means, of the system within the premises supplied, wherein may lie the source or sources of contamination, from the vendors or public water supply system.b) Protection of Each Individual OutletThe protection of each individual outlet by suit
8、able devices or means, which within the premises served may be a source of contamination.Protection by containment protects the vendors or public water supply only. It does not provide protection within the premises supplied.In modern plumbing systems, there are many situations where backflow could
9、occur due to backpressure conditions. In some, the pollutants that would get into the water supply would be undesirable, yet not be a hazard to the health of persons consuming the water.This standard covers two (2) types of devices, which are identified as Double Check Backflow Prevention Assemblies
10、 (DC) and Double Check Fire Protection Backflow Prevention Assemblies (DCF). The DC and the DCF are identical in their backflow protection. The DCF, which was added to this standard in 1999, has specific performance requirements relating to their use on fire protection systems.The devices described
11、are suitable for either protection by containment or protection of individual outlets where pollutants, which could be caused to enter the potable water, are low hazard.These devices are suitable for either hot or cold water service under continuous or intermittent pressure conditions.iv Double Chec
12、k Backflow Prevention Assemblies and Double Check Fire Protection Backflow Prevention AssembliesASSE 1015-2011Although many of the material specifications are detailed within Section 4.1 of this standard, it is the responsibility of the manufacturer and the installer to comply with the relevant juri
13、sdictional requirements.The working group, which developed this standard revision, was set up within the framework of the Product Standards Committee of ASSE International.Recognition is made of the time volunteered by members of this working group and of the support of the manufacturers who partici
14、pated in meetings for this standard.This standard does not imply ASSEs endorsement of a product which conforms to these requirements.Compliance with this standard does not imply acceptance by any code body.It is recommended that these devices be installed consistent with local codes by qualified and
15、 trained professionals.This standard was promulgated in accordance with procedures developed by the American National Standards Institute (ANSI).This edition was approved by the ASSE Board of Directors on August 9, 2011 as an ASSE standard.Double Check Backflow Prevention Assemblies and v Double Che
16、ck Fire Protection Backflow Prevention AssembliesASSE 1015-2011Joseph FugeloProduct Standards Committee ChairmanLabov Co.Philadelphia, PennsylvaniaRand AckroydRand Technical Consulting, LLCNewburyport, MassachusettsWilliam Briggs Jr.MGJ AssociatesNew York, New YorkMaribel CamposICC Evaluation Servic
17、esWhittier, CaliforniaJudson CollinsJulyco ProfessionalsMannford, OklahomaRon GeorgePlumb-Tech Design and(b) Double Check Fire Protection Backflow Prevention Assembly (DCF). These assemblies consist of two (2) independently acting check valves, internally force loaded to a normally closed position,
18、two (2) properly located, tightly closing shut-off valves, per Section 1.3.2.6, and properly located test cocks, per Section 1.3.2.4. These assemblies are designed and constructed to operate under intermittent or continuous pressure conditions.This standard also applies to Manifold Double Check Back
19、flow Prevention Assemblies consisting of two (2) or more complete Double Check Backflow Prevention Assemblies in parallel. The assemblies do not need to be of the same pipe size. The manifold size shall be identified by the single inlet and outlet of the manifold assembly. Manifold Double Check Back
20、flow Prevention Assemblies shall include line-sized shut-off valves on each inlet and outlet of the assemblies making up the manifold.1.2.2 Size RangeConnection pipe sizes shall be in accordance with Table 1.2 Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Prev
21、ention AssembliesASSE 1015-2011Table 1Rated Water Flow and Maximum Allowable Pressure Loss for Various SizesSize of DeviceRated FlowDC MaximumAllowable PressureLoss at Rated FlowDCF MaximumAllowable PressureLoss at Rated FlowNPSDNGPML/spsikPapsikPainchmm 1 1 1 2 2 3 4 6 8 10 12 14 16 8 10 15 18 20 2
22、5 32 40 50 65 80 100 150 200 250 300 350 400 1.00 3.00 7.50 20.00 30.00 50.00 75.00 100.00 160.00 225.00 320.00 500.00 1000.00 1600.00 2300.00 3000.00 3700.00 4400.00 0.06 0.19 0.47 1.26 1.89 3.15 4.73 6.31 10.09 14.20 20.19 31.55 63.09 100.94 145.11 189.27 233.43 277.60 10.0 10.0 10.0 10.0 10.0 10.
23、0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 68.9 68.9 68.9 68.9 68.9 68.9 68.9 68.9 68.9 68.9 68.9 68.9 68.9 68.9 68.9 68.9 68.9 68.9 - - - - 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 - - - - 52.2 52.2 52.2 52.2 52.2 52.2 52.2 52.2 52.2 52.2 52.2 52.2 52.2 52.2 1.2.3
24、Rated Pressure1.2.3.1 A DC assembly shall be designed for a working pressure of at least 150.0 psi (1034.2 kPa).1.2.3.2 A DCF assembly shall be designed for a working pressure of at least 175.0 psi (1206.6 kPa).Double Check Backflow Prevention Assemblies and 3 Double Check Fire Protection Backflow P
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIAMERICANSOCIETYOFSANITARYENGINEERING10152011PERFORMANCEREQUIREMENTSFORDOUBLECHECKBACKFLOWPREVENTIONASSEMBLIESANDDOUBLECHECKFIREPROTECTIONBACKFLOWPREVENTIOPDF

链接地址:http://www.mydoc123.com/p-430846.html