ARI GUIDELINE K-2004 Guideline for Containers for Recovered Non-Flammable Fluorocarbon Refrigerants《不易燃碳氟化合物制冷剂容器指南》.pdf
《ARI GUIDELINE K-2004 Guideline for Containers for Recovered Non-Flammable Fluorocarbon Refrigerants《不易燃碳氟化合物制冷剂容器指南》.pdf》由会员分享,可在线阅读,更多相关《ARI GUIDELINE K-2004 Guideline for Containers for Recovered Non-Flammable Fluorocarbon Refrigerants《不易燃碳氟化合物制冷剂容器指南》.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、 4100 N. FAIRFAX DR., SUITE. 200 ARLINGTON, VIRGINIA 22203 2004 GUIDELINE for CONTAINERS FOR RECOVERED NON-FLAMMABLE FLUOROCARBON REFRIGERANTS Guideline K Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitte
2、d without license from IHS-,-,-Price $10.00 (M) $20.00 (NM) Copyright 2004, by Air-Conditioning and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office Note: This guideline supersedes ARI Guideline K-1997. IMPORTANT SAFETY DISCLAIMER ARI does not set safety
3、 standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance
4、 with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. ARI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. ARI does not certify or guarantee that any tests condu
5、cted under its standards/guidelines will be non-hazardous or free from risk. Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-TABLE OF CONTENTS SECTION PAGE Section 1. Purpo
6、se1 Section 2. Scope.1 Section 3. Definitions 1 Section 4. Containers .2 Section 5. Responsibility of Owner .2 Section 6. Labels and Markings.3 Section 7. Filling Procedures .4 Section 8. Transportation.5 APPENDICES Appendix A. References - Normative 6 Appendix B. References - Informative.6 Appendix
7、 C. DOT Service Pressures for Selected Non-Flammable Fluorocarbon Refrigerant Recovery Cylinders - Informative .7 TABLES FOR APPENDICES Table C1. DOT Service Pressures for Selected Non-Flammable Fluorocarbon Refrigerant Recovery Cylinders .7 Copyright Air-Conditioning and Refrigeration Institute Pro
8、vided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI GU
9、IDELINE K-2004 1CONTAINERS FOR RECOVERED NON-FLAMMABLE FLUOROCARBON REFRIGERANTS Section 1. Purpose 1.1 Purpose. Recovery, recycling and reclamation of certain non-flammable fluorocarbon refrigerants will prevent unnecessary release of these compounds. For practical and safety reasons, there is a ne
10、ed for containers designed and identified specifically for these uses. This document is intended as a recommended guide of good practice to be used on a voluntary basis by all who supply, use, store or transport these containers. In certain instances, this document sets forth federal requirements as
11、 of the date of publication hereof. This document is not intended to be an exhaustive listing of all such requirements. Applicable federal, state, and local requirements should be reviewed. 1.1.1 Intent. This guideline is intended for the guidance of the industry, including manufacturers, engineers,
12、 installers, contractors, and users. 1.1.2 Review and Amendment. This guideline is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This guideline applies to containers with service pressures no higher than 400 psig for the receipt, storage and transportation of re
13、covered non-flammable fluorocarbon refrigerants. Where this guideline mentions regulations that are mandated by the United States Federal Government, the reference to the federal regulation is provided. 2.2 Exclusions. This guideline does not apply to American Society of Mechanical Engineers (ASME)
14、pressure vessels for on-site recovery and storage that are not U.S. Department of Transportation (DOT) approved for transportation of non-flammable fluorocarbon refrigerants. Section 3. Definitions All terms in this document will follow the standard industry definitions established in the current ed
15、ition of ASHRAE Terminology of Heating, Ventilation, Air Conditioning and Refrigeration, unless otherwise defined in this section. 3.1 Reclamation. To reprocess refrigerant to new product specifications, by means which may include distillation. Chemical analysis of the refrigerant will be required t
16、o determine that appropriate product specifications are met. This term usually implies the use of processes or procedures available only at a reprocessing or manufacturing facility. 3.2 Recovered Non-Flammable Fluorocarbon Refrigerant. Refrigerant that has been removed from a system for the purpose
17、of storage, recycling, reclamation or transportation. 3.3 Service Pressure. The rated pressure marked on the cylinder or ton tank. Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from I
18、HS-,-,-ARI GUIDELINE K-2004_ 2 Section 4. Containers 4.1 Cylinders for Recovered Non-Flammable Fluorocarbon Refrigerants as referenced in Appendix C. 4.1.1 Federal Law requires that cylinders comply with United States Department of Transportation (DOT) packaging requirements, see Title 49 CFR. NOTE:
19、 Federal law forbids transportation of Specification 39 non-reusable/non-refillable cylinders, if refilled. Penalty for violating this requirement is up to $500,000 fine and five years imprisonment Title 49 U.S.C. (United States Code) Sec. 5124. Non-refillable cylinders meeting DOT Specification 39
20、should not be refilled or reused for any reason due to risk of serious personal injury. 4.1.2 Valve outlet connections should comply with Compressed Gas Association Publication V-1. 4.1.3 Pressure relief devices should comply with Compressed Gas Association Publication S-1.1. 4.1.4 Valves used for v
21、apor and/or liquid withdrawal should be clearly identified and marked. 4.2 Ton Tanks for Recovered Non-Flammable Fluorocarbon Refrigerants as referenced in Appendix C. 4.2.1 Federal Law requires that ton tanks comply with United States Department of Transportation (DOT) specification 106A500X or 110
22、A500W as detailed in Title 49 CFR, Section 179.300. 4.2.2 Valve outlet connections should comply with Compressed Gas Association Publication V-1. 4.2.3 Federal Law requires that pressure relief devices comply with Title 49 CFR. 4.3 Containers for Recovered Non-Flammable Fluorocarbon Refrigerants R-1
23、1, R-113 and R-123. 4.3.1 DOT Specifications require that steel drums comply with UN Specification 1A1, as per 49 CFR, Section 178.504. 4.3.2 Containers that originally contained new refrigerant R-11, R-113 or R-123 (excluding those originally used for cleaning agents) may be used, provided the foll
24、owing conditions are met: 4.3.2.1 The drums should be inspected internally and externally and found to be clean and free of dents, bulges, holes, cracks, rust, pits, creases or other structural weaknesses. 4.3.2.2 Closure devices, including gaskets, should be in such condition that they comply, in a
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARIGUIDELINEK2004GUIDELINEFORCONTAINERSFORRECOVEREDNONFLAMMABLEFLUOROCARBONREFRIGERANTS 易燃 氟化 制冷剂 容器

链接地址:http://www.mydoc123.com/p-429480.html