AHRI GUIDELINE W SI-2014 Selecting Sizing & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment.pdf
《AHRI GUIDELINE W SI-2014 Selecting Sizing & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment.pdf》由会员分享,可在线阅读,更多相关《AHRI GUIDELINE W SI-2014 Selecting Sizing & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment.pdf(24页珍藏版)》请在麦多课文档分享上搜索。
1、 AHRI Guideline W (SI) 2014 Guideline for Selecting, Sizing, or the tilt angle is reversed, effectively stopping heat transfer. 5.1.4.4 Cold Corner Damper or Traversing Defrost. For Plate Heat Exchangers, outdoor air is prevented from entering a portion of the Air-to-Air Heat Exchanger to enable the
2、 exhaust air energy to defrost that section of the component. 5.2 Condensation Removal. Means of removing condensate may be required. If so, observe applicable codes for piping and trapping of condensate drain(s). Section 6. System Balancing 6.1 Equal and Unequal Air Flows. The amount of outside air
3、 and exhaust air required may be the result of the building design. Many facilities have exhaust air removed from a variety of sources, other than the AAERVE. In order to maintain a proper air balance in the building, this may result in the need to exhaust less air than the outdoor air requirement.
4、In this case, Effectiveness will be increased by definition (because the percentage of energy extracted from the reduced exhaust airflow is increased), however, the conditions of the supply air will be less favorable and the performance of the building system will be affected (due to induced exfiltr
5、ation without benefit of energy recovery). If the exhaust air is greater than the outdoor air intake, then Effectiveness would again be increased by definition; supply air conditions would improve, but again, building system performance would be affected (in this case due to induced infiltration wit
6、hout benefit of energy recovery). 6.1.1 Energy Impacts. Equal (balanced) Supply and Exhaust Airflows provide the maximum energy recovery for a given AAERVE. The system should be balanced as closely as possible as long as other conditions, such as requirements for building pressurization, are met. 6.
7、1.2 Conditions Impact. Unequal airflows will influence the conditions of the supply air. Example: Reducing the Supply Airflow as compared to the exhaust will improve the supply air psychrometric conditions, but reduce the energy recovered from the exhaust air. On the other hand reducing the Exhaust
8、Airflow as compared to the supply will degrade the supply air psychrometric conditions. Again, energy recovered will be reduced. 6.1.3 Variable Air Flow. On systems that vary total system airflow and/or outdoor air (demand control ventilation, variable air volume, etc.) provisions should be made to
9、control both supply and exhaust airflows in concert. In no case should the airflows be lower than needed to provide the required outdoor air ventilation rate per ASHRAE standards or local codes. 6.1.4 Building or Zone Pressurization. Requirements for building or zone pressurization should be conside
10、red when designing and/or balancing the system. If building pressurization requirements would cause the AAERVE to be severely unbalanced, the designer should consider additional methods of building pressurization. 6.2 Balancing Methods. Provisions should be made for adjusting the airflows to require
11、d rates. The methods listed below can be used independently or in combination. 6.2.1 Dampers. Dampers may be used to balance airflows to the space to insure proper air distribution to individual zones or connected air-handling equipment. Dampers may also be used to balance AAERVE Supply and Exhaust
12、Airflows. However, controlling blower speed is a more energy efficient method of volume control than dampers. 6.2.2 Blower Settings. Methods such as multiple speed motors, adjustments in blower sheaves, etc., may be used to adjust airflows. 6.2.3 Variable Speed. Variable frequency drives, electronic
13、ally commutated motors, and similar variable speed technologies may be used to adjust airflows. AHRI GUIDELINE W (SI)-2014_ 6 6.2.4 Unitized. Operation of the main unitary blower can impact the AAERVE Supply and Exhaust Airflows. Methods should be provided to balance these flows and unitary airflow.
14、 6.2.5 Integrated. Operation of the main unitary blower can impact the AAERVE Supply and Exhaust Airflows. Methods should be included to balance these flows. 6.2.6 Measurement of Flows. Methods should be provided to measure Exhaust and Supply Airflows for the purpose of balancing. Methods can includ
15、e static pressure across the component, conventional velocity methods in the duct, or other airflow measuring devices. 6.2.7 Outdoor Air Correction Factor (OACF). Consider the impact of OACF to ensure that the correct amount of outside air is introduced to meet the ventilation requirements for the b
16、uilding. Example: If the outdoor air is being measured at the outside air inlet and the OACF = 1.1, the measured air volume should be 110% of the required (ventilation design) supply airflow. This will ensure that the specified level of outdoor air is being introduced into the building after the OAC
17、F impact from the Air-to-Air Heat Exchanger. Section 7. Economizer Operation 7.1 Economizer Operation. Some applications and standards/codes may require an air economizer be provided for the air-conditioning system. In these cases, provisions should be made to bypass or control the energy recovery s
18、ystem to permit air economizer operation. The bypass or separate economizer should be sized to handle the maximum outdoor air required during economizer operation. 7.1.1 Economizer Bypass. 7.1.1.1 Unitized and Integrated Systems. Outdoor air is brought into the conditioned space without crossing the
19、 component, thus not recovering energy. This can be accomplished by utilizing dampers, bypass duct and dampers, or by moving the Air-to-Air Heat Exchanger out of the outdoor airstream. 7.1.1.2 Coupled Systems. A system to introduce outdoor air into the conditioned space without crossing the Air-to-A
20、ir Heat Exchanger which utilizes the Economizer on the air-conditioning unit. 7.1.2 Wheel Economizer. System to introduce outdoor air into the conditioned space while crossing a Rotary Heat Exchanger without energy recovery. The component is stopped during the Economizer period when energy recovery
21、is not desired. All of the outdoor air crosses the component, thus limiting the outdoor air amount to the components airflow capacity at the application static pressure. Typically, full 100% outside air Economizer function can be provided with this method only for 100% outdoor air systems. 7.2 Modul
22、ation. All the above methods can be controlled to provide partial or modulated Economizer function. 7.3 Exhaust Air Relief. Barometric relief or power exhaust is often provided in conjunction with Economizers. The exhaust fan in the AAERVE may be able to provide or assist with this function. This sh
23、ould be considered in design. 7.4 AAERVE Shut Down. When a separate air economizer is provided, the control system should shut down the AAERVEs supply air stream at a minimum and typically also the AAERVEs exhaust air stream. Section 8. Design Considerations and Air-Conditioning Equipment Selection
24、8.1 Building Design. The type of building will determine the type of AAERVE required for the application. The design may require that the AAERVE be utilized in a mechanical room application, a rooftop application, a through-the-wall application, or a combination. 8.2 Codes and Standards. The authori
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRIGUIDELINEWSI2014SELECTINGSIZINGSPECIFYINGPACKAGEDAIRTOAIRENERGYRECOVERYVENTILATIONEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-422624.html