AHRI 921 SI-2015 Performance Rating of DXDedicated Outdoor Air System Units.pdf
《AHRI 921 SI-2015 Performance Rating of DXDedicated Outdoor Air System Units.pdf》由会员分享,可在线阅读,更多相关《AHRI 921 SI-2015 Performance Rating of DXDedicated Outdoor Air System Units.pdf(17页珍藏版)》请在麦多课文档分享上搜索。
1、 2015 Standard for Performance Rating of DX-Dedicated Outdoor Air System Units AHRI Standard 921 (SI) Price $10.00 (M) $20.00 (NM) Copyright 2015, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office IMPORTANT SAFETY DISCLAI
2、MER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installe
3、d and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does not certify or
4、guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This standard supersedes ANSI/AHRI Standard 920-2012. For I-P ratings, see AHRI Standard 920 (I-P)-2015. Foreword: DX-Dedicated Outdoor Air Systems (DX-DOAS) condition outdoor ventilation
5、 air independently from the building HVAC system. This approach to handling ventilation air results in superior humidity control by limiting the primary source of humidity in most buildings ambient humidity carried in by the ventilation air directly at its source. When the DX-DOAS removes enough moi
6、sture from the ventilation air to match the building interior load, energy savings can be obtained by running the separate, sensible cooling only, interior cooling system at a higher evaporating temperature, thus improving the energy efficiency. Further energy savings may be realized by providing on
7、ly the amount of ventilation air necessary and/or by using energy recovery from the building Exhaust Air to pre-treat the ventilation air. Alternate energy strategies may be employed to provide ventilation air at low or high dry-bulb temperatures to assist in building cooling and heating. TABLE OF C
8、ONTENTS SECTION PAGE Section 1. Purpose 1 Section 2. Scope . 1 Section 3. Definitions. 1 Section 4. Classifications . 4 Section 5. Test Requirements. 4 Section 6. Rating Requirements . 7 Section 7. Minimum Data Requirements for Published Ratings 10 Section 8. Operating Requirements . 11 Section 9. M
9、arking and Nameplate Data . 13 Section 10. Conformance Conditions 13 TABLES Table 1. Classification of DX-Dedicated Outdoor Air System Units . 4 Table 2. Operating Conditions for Standard Rating and Performance Tests for Classification A, B, and W DX-DOAS Units 5 Table 3. Operating Conditions for St
10、andard Rating and Performance Tests for Classification H DX-DOAS Units 6 Table 4. External Static Pressure 7 Table 5. Multiples for Rated Airflow . 7 Table 6. Basic Pumping Penalty (PPB) vs. Liquid Flow Rate (WF). 9 FIGURES Figure 1. DX-DOAS Units Airflow Schematic. 2 APPENDICES Appendix A. Referenc
11、es - Normative 14 Appendix B. References - Informative . 14 AHRI STANDARD 921 (SI)-2015 _ 1 PERFORMANCE RATING OF DX-DEDICATED OUTDOOR AIR SYSTEM UNITS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for DX-Dedicated Outdoor Air System Units: definitions; classifications
12、; test requirements; rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contrac
13、tors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to factory-assembled commercial or industrial DX-Dedicated Outdoor Air System Units as defined in Section 3. 2.1.1 Energy Source. Thi
14、s standard applies to electrically operated, vapor-compression refrigeration systems. 2.1.2 Installation. DX-Dedicated Outdoor Air System Units are intended for ducted or non-ducted installation with field or factory supplied grilles. 2.2 Exclusions. This standard shall not apply to products covered
15、 under ANSI/AHRI Standard 210/240, ANSI/AHRI Standard 340/360, and ANSI/AHRI/ASHRAE ISO Standard 13256-1. Direct conversion of values from testing performed under AHRI Standard 920 (I-P) shall not be used. Section 3. Definitions All terms in this document will follow the standard industry definition
16、s in the ASHRAE Terminology website (https:/www.ashrae.org/resources-publications/free-resources/ashrae-terminology) unless otherwise defined in this section. 3.1 Coefficient of Performance. A ratio of the heating capacity in watts to the power input values in watts at any given set of Rating Condit
17、ions expressed in W/W, including Supplementary Heat if required to provide room neutral supply air temperature as listed in Table 3. 3.1.1 Standard Coefficient of Performance (COP). A ratio of the capacity to power input obtained at Standard Rating Conditions, heating. 3.2 Conditioned Space. That pa
18、rt of a building that is humidified or dehumidified; heated or cooled, or both, for the comfort of occupants. 3.3 DX-Dedicated Outdoor Air System Units (DX-DOAS Units). A type of air-cooled, water-cooled, or water source factory assembled product which dehumidifies 100% Outdoor Air to a low dew poin
19、t, and includes reheat that is capable of controlling the supply dry-bulb temperature of the dehumidified air to the designed supply air temperature. This conditioned outdoor air is then delivered directly or indirectly to the Conditioned Space(s). It may pre-condition Outdoor Air by containing an e
20、nthalpy wheel, sensible wheel, desiccant wheel, plate heat exchanger, heat pipes, or other heat or mass transfer apparatus. Note: DX-DOAS Units can operate in combination with a separate sensible cooling system to satisfy the entire building humidity load. The system is sized to maintain a prescribe
21、d ventilation rate under any load condition. The ventilation rate can be constant or varied based on the building operation or occupancy schedule or in response to the actual occupancy. It may pre-condition Outdoor Air by incorporating an enthalpy wheel, sensible wheel, desiccant wheel, plate heat e
22、xchanger, heat pipes or other heat or mass transfer apparatus. It shall reheat the ventilation air by containing a reheat refrigerant circuit, _ AHRI STANDARD 921 (SI)-2015 2 sensible wheel, heat pipe, or other heat or mass transfer apparatus. Cooling components may include chilled water coils. Heat
23、ing components are optional and may include electrical resistance, steam, hot water, or gas heat. In addition, it may provide for air cleaning. 3.4 Exhaust Air. Air removed from the Conditioned Space and discharged to the outdoor area of the building by means of mechanical or natural ventilation sys
24、tems. 3.5 Exhaust Air Transfer Ratio (EATR). A ratio of the tracer gas concentration difference between the Supply Airflow and the Outdoor Airflow and the tracer gas concentration difference between the Return Airflow and the Outdoor Airflow at the 100% rated airflows, expressed as a percentage. 3.5
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI921SI2015PERFORMANCERATINGOFDXDEDICATEDOUTDOORAIRSYSTEMUNITSPDF

链接地址:http://www.mydoc123.com/p-422604.html