1、 2014 Standard for Performance Rating of Liquid Line Filters AHRI Standard 716 (SI) Price $15.00 (M) $30.00 (NM) Copyright 2014, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office IMPORTANT SAFETY DISCLAIMER AHRI does not
2、set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in
3、accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does not certify or guarantee that any
4、 tests conducted under the standards/guidelines will not be non-hazardous or free from risk. Note: For IP ratings, see AHRI Standard 715 (I-P)-2014. TABLE OF CONTENTS SECTION PAGE Section 1. Purpose 1 Section 2. Scope .1 Section 3. Definitions.1 Section 4. Tubing Connections 2 Section 5. Test Requir
5、ements 2 Section 6. Rating Requirements .3 Section 7. Minimum Data Requirements for Published Ratings .4 Section 8. Marking and Nameplate Data .4 Section 9. Conformance Conditions 4 TABLES Table 1. Standard Rating Conditions 2 FIGURES Figure 1. Pressure Drop vs. Contaminant Added .3 APPENDICES Appen
6、dix A. References - Normative .5 Appendix B. References - Informative5 _AHRI STANDARD 716 (SI)-2014 1 PERFORMANCE RATING OF LIQUID LINE FILTERS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Liquid Line Filters: definitions; tubing connections; test requirements; ra
7、ting requirements; minimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. Thi
8、s standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to hermetic Liquid Line Filters designed for use in the liquid line of all types of refrigeration and air-conditioning systems employing the following refrigerants: R-22, R-134a, R
9、-290, R-404A, R-407A, R-407C, R-410A, R-507A, R-600a, and R-744 as defined in ANSI/ASHRAE 34 with Addenda. This standard provides a means of determining the Overall Filter Efficiency and Contaminant Capacity of a Liquid Line Filter at specified conditions. 2.2 Exclusions. This standard does not appl
10、y to filters used in the suction line or low pressure side of refrigeration and air-conditioning systems. 2.3 Limitations. This standard only addresses the removal and retention of solid particles. Therefore, acid, dissolved contaminant, and moisture removal are not considered here. Although many co
11、mmercial Liquid Line Filter Driers have moisture removal and retention media, the subject of moisture removal is separate and distinct from the considerations of this standard. The rating standard for moisture removal performance of liquid line driers is ANSI/AHRI Standard 711 (SI). Section 3. Defin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI716SI2014PERFORMANCERATINGOFLIQUIDLINEFILTERSPDF

链接地址:http://www.mydoc123.com/p-422570.html