AHRI 340 360-2007 Performance Rating of Commercial and Industrial Unitary Air-Conditioning and Heat Pump Equipment (Incorporating Addendum No 1 December 2010 Addendum No 2 June 201.pdf
《AHRI 340 360-2007 Performance Rating of Commercial and Industrial Unitary Air-Conditioning and Heat Pump Equipment (Incorporating Addendum No 1 December 2010 Addendum No 2 June 201.pdf》由会员分享,可在线阅读,更多相关《AHRI 340 360-2007 Performance Rating of Commercial and Industrial Unitary Air-Conditioning and Heat Pump Equipment (Incorporating Addendum No 1 December 2010 Addendum No 2 June 201.pdf(31页珍藏版)》请在麦多课文档分享上搜索。
1、 2007 Standard for Performance Rating of Commercial and Industrial Unitary Air-Conditioning and Heat Pump Equipment Approved by ANSI on 27 October 2011 ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2 (Formerly ARI Standard 340/360-2007) ANSI/AHRI STANDARD 340/360-2007 WITH ADDENDUM 2, Performan
2、ce Rating of Commercial and Industrial Unitary Air-Conditioning and Heat Pump Equipment June 2011 Addendum 2 (dated June 2011) of ANSI/AHRI Standard 340/360-2007, “Changes to ANSI/AHRI Standard 340/360-2007” is provided as follows. The particular additions are shown with shading and deletions shown
3、with strikethroughs. The following changes have been incorporated (additions are shown by shading and deletions are shown by strikethroughs) into the already published 2007 version of ANSI/AHRI Standard 340/360 to avoid confusion. 1. The language in Section 6.2.2 associated with units using discrete
4、 step fan control and variable air volume units has been revised. An external static equation has been added to the footnotes of Table 6. External Static The following equation has been added to the footnote of Table 6 of ANSI/AHRI Standard 340/360-2007: 2=MFullLoadCFMPartLoadCFicternalStatFullLoadE
5、xaticExternalSt ANSI/AHRI STANDARD 340/360-2007 WITH ADDENDUM 1, Performance Rating of Commercial and Industrial Unitary Air-Conditioning and Heat Pump Equipment December 2010 Addendum 1 (dated December 2010) of ANSI/AHRI Standard 340/360-2007, “Changes to ANSI/AHRI Standard 340/360-2007” is provide
6、d as follows. The particular additions are shown with shading and deletions shown with strikethroughs. The following changes have been incorporated (additions are shown by shading and deletions are shown by strikethroughs) into the already published 2007 version of ANSI/AHRI Standard 340/360 to avoi
7、d confusion. 1. The certification program scope, on the inside front cover, has been revised. 2. New provisions have been added to the footnotes of Tables 5 and 6 to specify the tolerances associated with external static pressure for all units, and the leaving air dry-bulb temperature on variable ai
8、r volume (VAV) units, respectively. Tolerances The following tolerance has been added to the footnote of Table 5 of ANSI/AHRI Standard 340/360-2007: The tolerance for external static pressure (averaged during the run time) for all equipment is -0 in H2O 0 Pa, +0.05 in H2O 12.5 Pa. The following tole
9、rance has been added to the footnote of Table 6 of ANSI/AHRI Standard 340/360-2007: The tolerance for the leaving air dry-bulb temperature on VAV units is 0.3 F 0.2 C. IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, compone
10、nts or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate f
11、or products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does not certify or guarantee that any test conducted under its standards/guidelines will be non-hazardous or free from risk. AP
12、PLICABILITY Integrated Energy Efficiency Ratio (IEER) is effective beginning January 1, 2010. Integrated Part-Load Value (IPLV) is was in effect until January 1, 2010 December 31, 2009. On January 1, 2010, IEER will supersede IPLV. IEER superseded IPLV on January 1, 2010. AHRI CERTIFICATION PROGRAM
13、PROVISIONS Scope of the Certification Program The Certification Program includes: all air-cooled, water-cooled and evaporatively-cooled unitary air-conditioning, air-source unitary heat pump equipment, and air-conditioning condensing units rated at or above 65,000 Btu/h 19,000 W at AHRI Standard Rat
14、ing Conditions (Cooling) but below 250,000 Btu/h 73,200 W at AHRI Standard Rating Conditions (Cooling). all air-cooled packaged unitary air-conditioners from 250,000 Btu/h to less than 760,000 Btu/h at AHRI Standard Rating Conditions (Cooling). Certified Ratings The following Certification Program r
15、atings are verified by test: Unitary Air-Conditioners and Air-Conditioning Condensing Units Air-cooled, water-cooled and evaporatively-cooled from 65,000 Btu/h 19,000 W to below 250,000 Btu/h 73,200 W. 1. AHRI Standard Rating Cooling Capacity, Btu/h 2. Energy Efficiency Ratio, EER, Btu/Wh 3. Integra
16、ted Energy Efficiency Ratio, (IEER) (effective January 1, 2010) or Integrated Part-Load Value, (IPLV) (effective through December 31, 2009) Air-Source Unitary Heat Pump Equipment Air-cooled from 65,000 Btu/h 19,000 W to below 250,000 Btu/h 73,200 W. 1. AHRI Standard Rating Cooling Capacity, Btu/h 2.
17、 Energy Efficiency Ratio, EER, Btu/Wh 3. High Temperature Heating Standard Rating Capacity, Btu/h 4. High Temperature Coefficient of Performance (COP 47F) 5. Low Temperature Heating Standard Rating Capacity, Btu/h 6. Low Temperature Coefficient of Performance (COP 17F) 7. Integrated Energy Efficienc
18、y Ratio, (IEER) (effective January 1, 2010) or Integrated Part-Load Value, (IPLV) (effective through December 31, 2009) Price $10.00 (M) $20.00 (NM) Copyright 2007, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office Unitar
19、y Air-Cooled Packaged Air-Conditioners from 250,000 Btu/h 73,200 W to below 760,000 Btu/h 220,000 W. 1. AHRI Standard Rating Cooling Capacity, Btu/h 2. Energy Efficiency Ratio, EER, Btu/Wh 3. Integrated Part-Load Value, IPLV (effective through 31 December, 2009) or Integrated Energy Efficiency Ratio
20、, (IEER) (effective 1 January, 2010) Conformance to the requirements of the Maximum Operating Condition Test, Cooling Low Temperature Operation Test, Insulation Efficiency Test (Cooling), and Condensate Disposal Test (Cooling) are also verified by test. Note: This standard supersedes ARI Standard 34
21、0/360-2004. TABLE OF CONTENTS SECTION PAGE Section 1. Purpose . 1 Section 2. Scope 1 Section 3. Definitions 1 Section 4. Classifications . 3 Section 5. Test Requirements 4 Section 6. Rating Requirements 4 Section 7. Minimum Data Requirements for Published Ratings . 13 Section 8. Operating Requiremen
22、ts .13 Section 9. Marking and Nameplate Data .15 Section 10. Conformance Conditions 15 TABLES Table 1. Classification of Commercial and Industrial Unitary Air-Conditioning Equipment . 3 Table 2. Classification of Commercial and Industrial Unitary Heat Pump Equipment . 4 Table 3. Conditions for Stand
23、ard Rating and Operating Tests . 5 Table 4. Expression of Standard Capacity Ratings 6 Table 5. Minimum External Pressure . 7 Table 6. IEER Part-Load Rating Conditions 9 APPENDICES Appendix A. References - Normative 16 Appendix B. References - Informative 16 Appendix C. Capacity Calculation for Unita
24、ry Equipment Using an Outdoor Air Cooling Coil Normative . 17 Appendix D. Method and Example of Calculating Integrated Part-Load Values (IPLV) Normative 19 TABLES FOR APPENDICES Table D1. Example IPLV Calculation (I-P Units) 22 FIGURES FOR APPENDICES Figure C1. Test Set-Up for Units Using an Outdoor
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI3403602007PERFORMANCERATINGOFCOMMERCIALANDINDUSTRIALUNITARYAIRCONDITIONINGANDHEATPUMPEQUIPMENTINCORPORATINGADDENDUMNO1DECEMBER2010ADDENDUMNO2JUNE201PDF

链接地址:http://www.mydoc123.com/p-422522.html