AHRI 1241 SI-2014 Performance Rating of Active Chilled Beams.pdf
《AHRI 1241 SI-2014 Performance Rating of Active Chilled Beams.pdf》由会员分享,可在线阅读,更多相关《AHRI 1241 SI-2014 Performance Rating of Active Chilled Beams.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、 2014 Standard for Performance Rating of Active Chilled Beams AHRI Standard 1241 (SI) Price $10.00 (M) $20.00 (NM) Copyright 2014, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office IMPORTANT SAFETY RECOMMENDATIONS AHRI do
2、es not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and opera
3、ted in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does not certify or guarantee t
4、hat any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This is a new standard. For I-P ratings, see AHRI Standard 1240 (I-P)-2014. TABLE OF CONTENTS SECTION PAGE Section 1. Purpose .1 Section 2. Scope 1 Section 3. Definitions1 Section 4. Classifications
5、 2 Section 5. Standard Equipment .3 Section 6. Test Requirements .3 Section 7. Rating Requirements 3 Section 8. Minimum Data Requirements for Published Ratings 4 Section 9. Marking and Nameplate Data 6 Section 10. Conformance Conditions .6 TABLES Table 1. Sound Power Level Rating Tolerances 4 APPEND
6、ICES Appendix A. References Normative .7 Appendix B. References Informative .7 AHRI STANDARD 1241 (SI)-2014 1 PERFORMANCE RATING OF ACTIVE CHILLED BEAMS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to provide, for Active Chilled Beams: definitions; classifications; standard equipm
7、ent; testing requirements; rating requirements; minimum data requirements for published ratings; marking and nameplate data; and voluntary conformance conditions. Section 2. Scope 2.1 This standard applies to Active Chilled Beams as defined in Section 3, including Multi-service Active Chilled Beams
8、and Room Air Induction Units. 2.2 Exclusions. 2.2.1 This standard does not apply to Active Chilled Beams employing volatile-refrigerant coils, condensing coils, or steam coils. 2.2.2 This standard does not apply to Passive Chilled Beams. Section 3. Definitions All terms in this document will follow
9、the standard industry definitions in the ASHRAE Wikipedia website (http:/wiki.ashrae.org/index.php/ASHRAEwiki) unless otherwise defined in this section. 3.1 Active Chilled Beam. An air induction and diffusion device which introduces conditioned air for the purposes of temperature and/or humidity con
10、trol. Primary Air is delivered through a series of Nozzles, which induces and conditions Secondary Air through a unit mounted coil. 3.1.1 Multi-service Active Chilled Beam. A chilled beam that incorporates space services other than cooling such as lighting. This type of Active Chilled Beam is usuall
11、y customized to meet specific project requirements. 3.1.2 Room Air Induction Unit. A type of Active Chilled Beam that requires more than 375 Pa of inlet static pressure to operate. 3.2 Air-induction Process. The process by which a jet of Primary Air induces Secondary Air through the coil. 3.2.1 Prim
12、ary Air. Air delivered through the Nozzle(s) of an Active Chilled Beam. 3.2.2 Secondary Air. Air induced through the coil of an Active Chilled Beam. 3.2.3 Supply Air. Supply air is the mixture of Primary Air and Secondary Air that is discharged to the space by the Active Chilled Beam. 3.2.4 Nozzle.
13、An air flow opening in the Plenum which discharges a jet of Primary Air via the Air-induction Process. 3.2.5 Plenum. An air compartment under positive pressure, and consisting of inlet(s) and Nozzle(s) for Primary Air. Also referred to as a Plenum chamber 3.2.6 Induction Ratio. The ratio of the volu
14、metric flow rate of Secondary Air to Primary Air. 3.2.7 Air Outlets and Inlets. Openings for the delivery or induction of air. AHRI STANDARD 1241 (SI)-2014 2 3.2.7.1 Supply Air Outlet. An opening for the delivery of supply air from the Active Chilled Beam unit. 3.2.7.2 Induced Air Inlet. An opening
15、through which Secondary Air is induced into the Active Chilled Beam. 3.2.8 Standard Air. Air weighing 1.2 kg/m3which approximates dry air at 21.1C and at a barometric pressure of 101 kPa of mercury. 3.2.9 Reference Air Temperature. Average air temperature of the induced air on the inlet side of the
16、cooling coil(s), measured as prescribed in ANSI/ASHRAE Standard 200. 3.3 Octave Band. A band of sound covering a range of frequencies such that the highest is twice the lowest. The Octave Bands used in this standard are those defined in ANSI Standard S1.11. 3.4 Passive Chilled Beam. A cooled element
17、 or coil, fixed in, above or under a ceiling that sensibly cools through natural convection using buoyancy driven air flow. The cooling media in the coil is water. 3.5 Product Line. A family of units of common basic design, consisting of a set of Models, and a progression of Sizes. 3.5.1 Model. The
18、style or structure of the Active Chilled Beam relative to the configuration of coils, Nozzles, and Air Outlets and Inlets as typified by the discharge pattern common to all Sizes. A given Model may have different Nozzle arrangements, Air Outlets and Inlets, coil configurations and Sizes. 3.5.2 Size.
19、 A measurement relative to the nominal length and width of the coil. 3.6 Published Rating. A statement of the assigned values of those performance characteristics, under stated rating conditions, by which a unit may be chosen to fit its application. These values apply to all units of a particular Mo
20、del and Size produced by the same manufacturer. 3.6.1 Published Ratings shall include Standard Ratings, properly identified as such, and should, in addition, include application ratings. 3.6.2 Standard Ratings. A rating based on tests performed at Standard Rating Conditions. 3.6.3 Application Rating
21、. A rating at other than Standard Rating Conditions; such other rating conditions are referred to as Application Rating Conditions. 3.7 Sensible Cooling Capacity. Capacity associated with a reduction in dry-bulb temperature, Btu/h. 3.8 “Shall“ or “Should“. “Shall“ or “should“ shall be interpreted as
22、 follows: 3.8.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.8.2 Should. “Should“ is used to indicate provisions which are not mandatory but which are desirable as good practice. 3.9 Sound Power Level
23、. Ten times the logarithm to the base ten of the ratio of the sound power radiated by the source to a reference sound power, expressed in decibels (dB). The reference sound power used in this standard is 1 picowatt (pW). 3.10 Throw. Horizontal or vertical axis distance an airstream travels after lea
24、ving an air outlet before the stream velocity is reduced to a specific terminal value. Section 4. Classifications 4.1 Active Chilled Beams are classified according to the following Product Lines: AHRI STANDARD 1241 (SI)-2014 3 4.1.1 Single or Multiple Discharge Openings. 4.1.2 Method of Secondary Ai
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI1241SI2014PERFORMANCERATINGOFACTIVECHILLEDBEAMSPDF

链接地址:http://www.mydoc123.com/p-422488.html