1、 1 ACI 364.12T-15TechNoteRepaiR of Leaking CRaCks in WaLLs of Liquid Containment stRuCtuResKeywords: chemical grout; concrete repair; crack injection; epoxy; leak; repair; rout and seal; wall; water tank.IntroductionNonprestressed reinforced concrete liquid contain-ment structuresin particular, nonc
2、ircular tanksoften exhibit vertical and diagonal cracks that are aestheti-cally objectionable. More importantly, cracks could result in loss of stored liquids, leakage of hazardous materials, concrete deterioration, and corrosion of rein-forcing bars. Such cracks, however, are seldom indica-tive of
3、structural failure. This TechNote reviews the methodology of repair in liquid containment structures.QuestionWhat are the typical causes of, and best practices to repair, vertical and diagonal cracks in liquid contain-ment structures?AnswerVertical and diagonal cracks in liquid containment structure
4、s are usually the result of restrained move-ment of concrete due to shrinkage, differential thermal expansion, and contraction from moisture and tempera-ture gradients over the wall height.In the absence of corrosion, dormant but leaking cracks are typically repaired by pressure injection of epoxy o
5、r chemical grout, vacuum injection, or routing and sealing on the interior or exterior wall surfaces, or both. Active cracks are repaired by pressure injection with chemical grouts; by routing and sealing with a flexible sealant on the interior or exterior wall surfaces, or both; or by application o
6、f a flexible barrier membrane on the liquid retention side of the wall. ACI Concrete Terminology (ACI CT-13) defines an active crack as one whose width changes with time, and a dormant crack as the oppositeone whose width does not change with time.Not all cracks require repair. Refer to ACI 224R, Ta
7、ble 4.1, for crack widths that require repair or remediation.DiscussionLiquid containment structures, such as large rectangular tanks, often exhibit vertical and diagonal cracks that are usually the result of restrained concrete shrinkage and thermal contraction, typically spaced 4 to 10 ft (1.2 to
8、3 m) apart (Fig. 1). These cracks generally have an insignificant effect on the structural integrity. Cracking, however, can affect the performance, serviceability, or both, of a structure, making repairs necessary to assure liquid-tightness and long-term durability (ACI 350). Liquid containment con
9、crete structures could have concrete roof slabs that should be kept liquid-tight to prevent contamination of the contents by exterior exposure. In these cases, differential shrinkage and thermal deformation of the concrete could result in significant wall and roof cracking if the appropriate expansi
10、on or contraction (movement joints) are not provided. Structures with movement joints in the walls and without matching joints in the base slab are prone to crack development, not only in the walls adjacent to the joint, but in the base slab below the movement joint. The cracks typically Fig. 1Verti
11、cal cracking at the walls of a liquid containment tank.American Concrete Institute Copyrighted Material www.concrete.org2 REPAIR OF LEAKING CRACKS IN WALLS OF LIQUID CONTAINMENT STRUCTURES (ACI 364.12T-15)extend diagonally, vertically, or both, and occur on both sides of the movement joints, resulti
12、ng from the restraint of the base slab. The width and spacing of cracks depends on concrete shrinkage and creep, the size and spacing of horizontal reinforcement, wall thickness, height and length of each placement (distance between vertical construction joints), and length between movement joints,
13、member restraints, and the concrete mixture.Crack widths can be controlled with appropriate reinforcement and detailing that result in tight cracks that do not leak. In liquid-retaining structures, the internal sides of walls should be consid-ered in repair selection and design.For more concrete rep
14、air guidance, refer to ACI 562, ACI 546R, ACI 224.1R, and ICRI Guideline No. 340.1. Refer to ACI 224.1R for an assessment of the intrinsic nature of cracks. Before selecting a repair methodology, the licensed design professional should deter-mine the cause of the cracksif they are active or dormant
15、and if corrosion is active in cracked areas. Because shrinkage of concrete continues over an extended period of time, resulting cracks should be considered active, especially if the structure is subjected to cycles of wet and dry periods. Dormant cracks usually result from an event of limited durati
16、on, such as temporary overload condi-tions during construction.For dormant cracks, injecting a rigid epoxy product restores the structural integrity of the member (ACI 503.7; RAP-1; ASTM C881/CM881).Conversely, except where it is needed for load-transfer purposes, rigid epoxy products should not be
17、used in active cracks (Fig. 2). If the conditions that cracked the wall initially are not, or cannot, be changed, the wall will crack again near the same location if the wall is structurally bonded back together. A repair technique incorpo-rating flexibility across the crack is the correct approach
18、for this type of condition (ACI 224.1R). Crack injection should not be used to repair cracks caused by corrosion of steel reinforcement unless supplemental means are used to mitigate the cause of the cracks and corrosion.If corrosion is present, it should be evaluated before making repairs. This Tec
19、hNote does not cover repair of cracks resulting from steel corrosion. There are various methods to mitigate, prevent, and control corrosion of reinforcing steel in concrete (ACI 222R).Active cracks can be repaired by: 1) pressure injecting of chemical grouts; 2) routing and sealing of cracks; and 3)
20、 installing a flexible barrier system (ACI 224.1R). These methods are considered serviceability repairs and not structural.1) Chemical grout injectionFlexible hydrophobic polyurethane foam grout material is often used for the crack repair in containment structures. Polyurethane foam retains most of
21、its volume after curing, even if the surrounding concrete should become dry, which is advantageous for repairing active cracks (Fig. 3 and 4). Hydrophilic grouts tend to shrink when allowed to dry out and lose volume, resulting in active leaking when the liquid is reintroduced at a later time. Note
22、that some of these grouts might not re-swell sufficiently upon rewet-ting to fully prevent future leakage. Both types of chemical grouts can be used to mitigate leaking cracks with injection performed from the exterior side of a liquid containment structure so the tanks need not be emptied. Interior
23、 injection can also be accomplished without draining the tank by experienced divers performing the work underwater. Some excavation could be required to access cracks below grade. For extensive cracking below grade, the application of a waterproofing system might be necessary.There are conditions, h
24、owever, where injection from the inside wall face is recommended to prevent liquid exfiltration, which could require the tank be emptied. Injection from the inside, however, provides access for crack repair below grade for buried or partially buried structures without excavation.The proper climatic
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ACI36412T2015REPAIROFLEAKINGCRACKSINWALLSOFLIQUIDCONTAINMENTSTRUCTURESPDF

链接地址:http://www.mydoc123.com/p-1242829.html