VA 26 24 16-2010 PANELBOARDS.pdf
《VA 26 24 16-2010 PANELBOARDS.pdf》由会员分享,可在线阅读,更多相关《VA 26 24 16-2010 PANELBOARDS.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、09-10 26 24 16 - 1 SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between / - / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation
2、, and connection of panelboards. 1.2 RELATED WORK A. Section 09 91 00, PAINTING: Identification and painting of panelboards. /B. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Requirements for seismic restraint of non-structural components./ C. Section 26 05 11, REQU
3、IREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements and items that are common to more than one Section of Division 26. D. Section 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW): Cables and wiring. E. Section 26 05 26, GROUNDING AND BONDING FOR E
4、LECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path for possible ground fault currents. F. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduits and outlet boxes. /G. Section 26 05 71, ELECTRICAL SYSTEM PROTECTIVE DEVICE STUDY: Requirements for ins
5、talling the over-current protective devices to ensure proper equipment and personnel protection./ H. Section 26 09 23, LIGHTING CONTROLS: Lighting controls integral to panelboards. I. Section 26 43 13, TRANSIENT-VOLTAGE SURGE SUPPRESSION: Surge suppressors installed in panelboards. 1.3 QUALITY ASSUR
6、ANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 SUBMITTALS A. Submit in accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from
7、IHS-,-,-09-10 26 24 16 - 2 B. Shop Drawings: 1. Sufficient information, shall be clearly presented to determine compliance with drawings and specifications. 2. Include electrical ratings, dimensions, mounting details, materials, wiring diagrams, accessories, and weights of equipment. Complete namepl
8、ate data, including manufacturers name and catalog number. C. Manuals: 1. When submitting the shop drawings, submit companion copies of complete maintenance and operating manuals, including technical data sheets and wiring diagrams. 2. If changes have been made to the maintenance and operating manua
9、ls that were originally submitted, then submit four copies of updated maintenance and operating manuals to the /Resident Engineer/ /COTR/ two weeks prior to final inspection. D. Certification: Two weeks prior to final inspection, submit four copies of the following to the /Resident Engineer/ /COTR/:
10、 1. Certification by the manufacturer that the materials conform to the requirements of the drawings and specifications. 2. Certification by the contractor that the materials have been properly installed, connected, and tested. 1.5 APPLICABLE PUBLICATIONS A. Publications listed below (including amen
11、dments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only. B. National Electrical Manufacturers Association (NEMA): PB-1-06 Panelboards 250-08 . Enclosures for Electrical Equipment (100
12、0V Maximum) C. National Fire Protection Association (NFPA): 70-2005 . National Electrical Code (NEC) 70E-2004 . Standard for Electrical Life Safety in the Workplace D. Underwriters Laboratories, Inc. (UL): 50-95 Enclosures for Electrical Equipment 67-09 Panelboards 489-09 . Molded Case Circuit Break
13、ers and Circuit Breaker Enclosures Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 24 16 - 3 PART 2 - PRODUCTS 2.1 PANELBOARDS A. Panelboards shall be in accordance with UL, NEMA, NEC, and as shown on the drawings. B. Panelboards shall be st
14、andard manufactured products. C. All panelboards shall be hinged “door in door” type with: 1. Interior hinged door with hand-operated latch or latches, as required to provide access only to circuit breaker operating handles, not to energized parts. 2. Outer hinged door shall be securely mounted to t
15、he panelboard box with factory bolts, screws, clips, or other fasteners, requiring a tool for entry. Hand-operated latches are not acceptable. 3. Push inner and outer doors shall open left to right. SPEC WRITER NOTE: Show on the drawings the information necessary to specify accessories and interconn
16、ection to other systems. D. All panelboards shall be completely factory-assembled with molded case circuit breakers and integral accessories, such as surge protective devices per Section 26 43 13, TRANSIENT-VOLTAGE SURGE SUPPRESSION, metering devices per Section 25 10 10, ADVANCED UTILITY METERING,
17、lighting controls per Section 26 09 23, LIGHTING CONTROLS, and as scheduled on the drawings or specified herein. Include one-piece removable, inner dead front cover, independent of the panelboard cover. SPEC WRITER NOTE: Show on the drawings the information required in the paragraph below. E. Panelb
18、oards shall have main breaker or main lugs, bus size, voltage, phase, top or bottom feed, and flush or surface mounting as scheduled on the drawings. F. Panelboards shall conform to NEMA PB-1, NEMA AB-1, and UL 67 and have the following features: 1. Non-reduced size copper bus bars with current rati
19、ngs as shown on the panel schedules, rigidly supported on molded insulators. 2. Bus bar connections to the branch circuit breakers shall be the “distributed phase” or “phase sequence” type. 3. Mechanical lugs furnished with panelboards shall be cast, stamped, or machined metal alloys of sizes suitab
20、le for the conductors to which they will be connected. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 24 16 - 4 4. Neutral bus shall be /100%/200%/rated, mounted on insulated supports. 5. Grounding bus bar shall be equipped with screws or l
21、ugs for the connection of grounding wires. 6. Buses shall be braced for the available short-circuit current. Bracing shall not be less than 10,000 A symmetrical for 120/208 V and 120/240 V panelboards, and 14,000 A symmetrical for 277/480 V panelboards. 7. Branch circuit panelboards shall have buses
22、 fabricated for bolt-on type circuit breakers. 8. Protective devices shall be designed so that they can easily be replaced. 9. Where designated on panel schedule “spaces,“ include all necessary bussing, device support, and connections. Provide blank cover for each space. 10. In two section panelboar
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2624162010PANELBOARDSPDF