VA 26 23 00-2010 LOW-VOLTAGE SWITCHGEAR.pdf
《VA 26 23 00-2010 LOW-VOLTAGE SWITCHGEAR.pdf》由会员分享,可在线阅读,更多相关《VA 26 23 00-2010 LOW-VOLTAGE SWITCHGEAR.pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、09-10 26 23 00 - 1 SECTION 26 23 00 LOW-VOLTAGE SWITCHGEAR SPEC WRITER NOTE: This specification is not for general use. Use Section 26 24 11, DISTRIBUTION SWITCHBOARDS for most applications. Where justified, this specification may be used for main service entrance equipment (coordinate with Section
2、26 11 16, SECONDARY UNIT SUBSTATIONS). It should not be used for downstream levels of secondary distribution where switchboards would typically be used. Delete between / - / if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraph
3、s. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage indoor switchgear. 1.2 RELATED WORK /A. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Requirement for Seismic Restraint for Nonstructural Compo
4、nents./ B. Section 25 10 10, ADVANCED UTILITY METERING: Electricity meters installed in switchgear. C. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements and items that are common to more than one section of Division 26. D. Section 26 05 21, LOW-VOLTAGE ELEC
5、TRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW): Cables and Wiring. E. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path for possible fault currents. F. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYS
6、TEMS: Conduit and outlet boxes. G. Section 26 05 71, ELECTRICAL SYSTEM PROTECTIVE DEVICE STUDY: Coordination study of overcurrent protection devices. H. Section 26 11 16, SECONDARY UNIT SUBSTATIONS: Secondary unit substation. Provided by IHSNot for ResaleNo reproduction or networking permitted witho
7、ut license from IHS-,-,-09-10 26 23 00 - 2 /I. Section 26 13 13, GENERATOR PARALLELING CONTROLS: For generator paralleling controls./ J. Section 26 25 11, BUSWAYS: Feeder Busways and Fittings. K. Section 26 43 13, TRANSIENT-VOLTAGE SURGE SUPPRESSION: For TVSS units integral to the switchgear. 1.3 QU
8、ALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 FACTORY TESTS A. Low-voltage switchgear shall be thoroughly tested at the factory to assure that there are no electrical or mechanical defects. Tests shall be conducted as per UL a
9、nd ANSI Standards. Factory tests shall be certified. B. Thoroughly test the switchgear at the factory with the circuit breakers in the connected position in their cubicles. The factory tests shall be in accordance with C37.20 and ANSI C37.51 and shall include the following tests: 1. Design Tests 2.
10、Production Tests 3. Conformance Tests C. The following additional tests shall be performed: 1. Verify that circuit breaker sizes and types correspond to drawings and coordination study. 2. Verify tightness of bolted electrical connections by calibrated torque-wrench method in accordance with manufac
11、turers published data. 3. Confirm correct operation and sequencing of electrical and mechanical interlock systems by attempting closure on locked-open devices, and attempting to open locked-closed devices, and making key exchange with devices operated in off-normal positions. 4. Verify correct barri
12、er and shutter installation and operation. 5. Exercise all active components. 6. Inspect indicating devices for correct operation. 7. Perform a dielectric withstand voltage test on each bus section, each phase-to-ground with phases not under test grounded, in accordance with manufacturers published
13、data. 8. Perform insulation-resistance tests on control wiring with respect to ground. Applied potential shall be 500 volts dc for 300-volt Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 23 00 - 3 rated cable and 1000 volts dc for 600-volt
14、rated cable, or as required if solid-state components or control devices cannot tolerate the applied voltage. 9. If applicable, verify correct function of control transfer relays located in the switchgear with multiple control power sources. 10. Perform phasing checks on double-ended or dual-source
15、switchgear to insure correct bus phasing from each source. D. Furnish four (4) copies of certified manufacturers factory test reports to the Resident Engineer prior to shipment of the switchgear to ensure that the switchgear has been successfully tested as specified. SPEC WRITER NOTE: Determine if w
16、itness testing is a VA requirement. Edit or remove paragraph to conform to project requirements. /E. The Government shall have an option to witness the factory tests. All expenses of the Government Representatives trips to witness the testing will be paid by the Government. Notify the Resident Engin
17、eer not less than 30 days prior to making tests at the factory./ 1.5 SUBMITTALS A. Submit in accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: B. Shop Drawings: 1. Sufficient information, clearly presented, shall be included to determine compliance with drawings and specif
18、ications. 2. Include electrical ratings, dimensions, mounting details, materials, required clearances, terminations, weight, wiring and connection diagrams, plan, front, side, and rear elevations, sectional views, bus work, circuit breaker frame sizes, trip and short-circuit rating, long-time, short
19、-time, instantaneous and ground fault settings, coordinated breaker and fuse curves, accessories, and device nameplate data. 3. Show the size, ampere-rating, number of bars per phase and neutral in each bus run (horizontal and vertical), bus spacing, equipment ground bus, and bus material. C. Manual
20、s: 1. Submit, simultaneously with the shop drawings, companion copies of complete maintenance and operating manuals including technical data sheets, wiring diagrams, and information for ordering replacement parts. Provided by IHSNot for ResaleNo reproduction or networking permitted without license f
21、rom IHS-,-,-09-10 26 23 00 - 4 a. Wiring diagrams shall have their terminals identified to facilitate installation, maintenance, and operation. b. Wiring diagrams shall indicate internal wiring for each item of equipment and the interconnection between the items of equipment. c. Provide a clear and
22、concise description of operation, which gives, in detail, the information required to properly operate the equipment. d. Approvals will be based on complete submissions of manuals together with shop drawings. 2. Two weeks prior to final inspection, deliver four copies of the final updated maintenanc
23、e and operating manuals to the Resident Engineer. a. The manuals shall be updated to include any information necessitated by shop drawing approval. b. Complete “As Installed“ wiring and schematic diagrams shall be included which show all items of equipment and their interconnecting wiring. c. Show a
24、ll terminal identification. d. Include information for testing, repair, trouble shooting, assembly, disassembly, and factory recommended/required periodic maintenance procedures and frequency. e. Provide a replacement and spare parts list. Include a list of tools and instruments for testing and main
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2623002010LOWVOLTAGESWITCHGEARPDF