VA 26 20 11-2010 ISOLATED POWER SYSTEMS.pdf
《VA 26 20 11-2010 ISOLATED POWER SYSTEMS.pdf》由会员分享,可在线阅读,更多相关《VA 26 20 11-2010 ISOLATED POWER SYSTEMS.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、09-10 26 20 11 - 1 SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. Note that the VA no longer installs new isolated power systems in human sur
2、gery rooms per VHA Directive 2008-011; this section only applies to renovation projects in which an existing isolated power system is altered, or to meet codes. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of isolated power systems. 1.2 RELATED
3、 WORK A. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements and items that are common to more than one section of Division 26. B. Section 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW): Cables and wiring. C. Section 26 05
4、26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path for possible ground fault currents. D. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduits for cables and wiring. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFI
5、CATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 SUBMITTALS A. Submit in accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. B. Shop Drawings: 1. Sufficient information shall be clearly presented to determine compliance with drawings and specifica
6、tions. 2. Include electrical ratings, dimensions, weights, mounting details, front view, side view, equipment and device arrangement, branch circuit overcurrent protection, wiring diagrams, materials, and connection diagrams. C. Manuals: Two weeks prior to the final inspection, submit four copies of
7、 the following to the /Resident Engineer/ /COTR/: Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 20 11 - 2 1. Complete maintenance, operating and testing manuals, including wiring diagrams, technical data sheets, and information for orderin
8、g replaceable parts: a. Include complete “As Installed“ diagrams that indicate all items of equipment and their interconnecting wiring. b. Include complete diagrams of the internal wiring for each of the items of equipment, including “As Installed“ revisions of the diagrams. c. The wiring diagrams s
9、hall identify the terminals to facilitate installation, maintenance, operation, and testing. D. Certifications: Two weeks prior to the final inspection, submit four copies of the following to the /Resident Engineer/ /COTR/: 1. Certification by the manufacturer that the equipment conforms to the requ
10、irements of the drawings and specifications. 2. Certification by the isolated electrical power system equipment manufacturer that the isolating transformers have been tested and conform to the leakage current and sound level requirements specified. 3. Certification by the contractor that the equipme
11、nt has been properly installed, adjusted, and tested. 1.5 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by basic designation
12、only. B. National Fire Protection Association (NFPA): 70-08 National Electrical Code (NEC) 99-05 Health Care Facilities C. Underwriters Laboratories, Inc. (UL): 6-07 . Electrical Rigid Metal Conduit-Steel 50-95 Enclosures for Electrical Equipment 797-07 . Electrical Metallic Tubing-Steel 1022-98 Lin
13、e Isolation Monitors 1047-03 Isolated Power Systems Equipment PART 2 - PRODUCTS 2.1 EQUIPMENT A. Isolated power systems shall be complete as shown on the drawings and include unitized isolated power units (IPUs), their associated remote outlets, power receptacles, grounding receptacles, equipotentia
14、l ground bus modules with power and grounding receptacles, line isolation monitors, and related circuitry. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 20 11 - 3 B. The isolated power systems shall be in accordance with NFPA 99 and UL 50,
15、 1022, and 1047. C. Incorporate the IPUs in factory-assembled units as shown on the detail drawings. House the isolation transformer, line isolation monitor, and circuit breaker panel board in each IPU unit. D. Line isolation monitors shall be in accordance with the following: 1. Article, “Line Isol
16、ation Monitor,“ in NFPA 99. 2. Dynamic-type, capable of detecting any combination of resistive and/or capacitive faults, including balanced, unbalanced, and hybrid faults. 3. Incorporate in each line isolation monitor, or on the front trim of the panel, a hazard meter or digital display, indicator l
17、ights, a buzzer with a local momentary-contact silencing switch or push-button, a test switch, and provisions for transmitting the alarm signals to a remote location. The hazard meter and indicator lights shall be conspicuously visible on the exterior face of the IPU. Transmission of the alarm signa
18、ls to remote locations up to several hundred feet from the monitor shall not unduly increase the leakage current for the system. E. Isolating transformers shall be in accordance with the following: 1. Single phase with primary and secondary voltages as indicated on the drawings. These ratings are fo
19、r continuous duty without the use of cooling fans. 2. Self-cooled by natural convection, dry, isolating windings, conventional (stacked design) type, with an electrostatic shield grounded between the primary and secondary windings, in accordance with NFPA 99. 3. Maximum temperature rises of material
20、s and components shall not exceed the values listed in Table 29.1 of UL 1047. 4. Cores shall be grain-oriented silicon steel. 5. Leakage current between each winding and ground shall be in compliance with UL 1047, Table 30.1, and Table 30.2. 6. Sound levels shall not exceed the following in accordan
21、ce with NEMA Standards: a. 5 kVA transformers or fewer: 28 dB. b. 7.5 kVA transformers: 32 dB. c. Larger transformers: 35 dB. 7. Temperature rise shall be limited 176 F 80 Cabove ambient temperature. 8. Each nameplate shall include the wiring diagram, leakage current, and sound level. Provided by IH
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2620112010ISOLATEDPOWERSYSTEMSPDF