VA 03 30 00-2011 CAST-IN-PLACE CONCRETE.pdf
《VA 03 30 00-2011 CAST-IN-PLACE CONCRETE.pdf》由会员分享,可在线阅读,更多相关《VA 03 30 00-2011 CAST-IN-PLACE CONCRETE.pdf(32页珍藏版)》请在麦多课文档分享上搜索。
1、03-11 03 30 00 - 1 SECTION 03 30 00 CAST-IN-PLACE CONCRETE SPEC WRITER NOTE: Delete between / - / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION: This section specifies cast-in-place st
2、ructural concrete and materials and mixes for other concrete. 1.2 RELATED WORK: A. Materials testing and inspection during construction: Section 01 45 29, TESTING LABORATORY SERVICES. B. Concrete roads, walks, and similar exterior site work: Section 32 05 23, CEMENT AND CONCRETE FOR EXTERIOR IMPROVE
3、MENTS. 1.3 TESTING AGENCY FOR CONCRETE MIX DESIGN: A. Testing agency retained and reimbursed by the Contractor and approved by Resident Engineer. B. Testing agency maintaining active participation in Program of Cement and Concrete Reference Laboratory (CCRL) of National Institute of Standards and Te
4、chnology. / Accompany request for approval of testing agency with a copy of Report of Latest Inspection of Laboratory Facilities by CCRL./ C. Testing agency shall furnish equipment and qualified technicians to establish proportions of ingredients for concrete mixes. 1.4 TOLERANCES: A. Formwork: ACI
5、117, except the elevation tolerance of formed surfaces before removal of shores is +0 mm (+0 inch) and -20 mm (-3/4 inch). B. Reinforcement Fabricating and Placing: ACI 117, except that fabrication tolerance for bar sizes Nos. 10, 13, and 16 (Nos. 3, 4, and 5) (Tolerance Symbol 1 in Fig. 2.1(a), ACI
6、, 117) used as column ties or stirrups is +0 mm (+0 inch) and -13 mm (-1/2 inch) where gross bar length is less than 3600 mm (12 feet), or +0 mm (+0 inch) and -20 mm (-3/4 inch) where gross bar length is 3600 mm (12 feet) or more. C. Cross-Sectional Dimension: ACI 117, except tolerance for thickness
7、 of slabs 12 inches or less is +20 mm (+3/4 inch) and - 6 mm (-1/4 inch). Tolerance of thickness of beams more than 300 mm (12 inch) but less than 900 mm (3 feet) is +20 mm (+3/4 inch) and -10 mm (-3/8 inch). D. Slab Finishes: ACI 117, Section 4.5.6, F-number method in accordance with ASTM E1155, ex
8、cept as follows: Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-03-11 03 30 00 - 2 1. Test entire slab surface, including those areas within 600 mm (2 feet) of construction joints and vertical elements that project through slab surface. 2. Maximum e
9、levation change which may occur within 600 mm (2 feet) of any column or wall element is 6 mm (0.25 inches). 3. Allow sample measurement lines that are perpendicular to construction joints to extend past joint into previous placement no further than 1500 mm (5 feet). 1.5 REGULATORY REQUIREMENTS: A. A
10、CI SP-66 ACI Detailing Manual. B. ACI 318 - Building Code Requirements for Reinforced Concrete. C. ACI 301 Standard Specifications for Structural Concrete. 1.6 SUBMITTALS: A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. B. Shop Drawings: Reinforcing steel: Co
11、mplete shop drawings C. Mill Test Reports: 1. Reinforcing Steel. 2. Cement. D. Manufacturers Certificates: 1. Abrasive aggregate. 2. Lightweight aggregate for structural concrete. 3. Air-entraining admixture. 4. Chemical admixtures, including chloride ion content. 5. Waterproof paper for curing conc
12、rete. 6. Liquid membrane-forming compounds for curing concrete. 7. Non-shrinking grout. 8. Liquid hardener. 9. Waterstops. 10. Expansion joint filler. 11. Adhesive binder. E. Testing Agency for Concrete Mix Design: Approval request including qualifications of principals and technicians and evidence
13、of active participation in program of Cement and Concrete Reference Laboratory (CCRL) of National Institute of Standards and Technology / and copy of report of latest CCRL, Inspection of Laboratory. / F. Test Report for Concrete Mix Designs: Trial mixes including water-cement / fly ash / ratio curve
14、s, concrete mix ingredients, and admixtures. G. Shoring and Reshoring Sequence: Submit for approval a shoring and reshoring sequence for flat slab/flat plate portions, prepared by a registered Professional Engineer. As a minimum, include timing of form Provided by IHSNot for ResaleNo reproduction or
15、 networking permitted without license from IHS-,-,-03-11 03 30 00 - 3 stripping, reshoring, number of floors to be re-shored and timing of re-shore removal to serve as an initial outline of procedures subject to modification as construction progresses. Submit revisions to sequence, whether initiated
16、 by Resident Engineer (see FORMWORK) or Contractor. SPEC WRITER NOTE: Delete splitting tensile strength test of lightweight concrete if no lightweight concrete, or if only used on metal deck slabs. H. Test reports on splitting tensile strength (Fct) of lightweight concrete. 1.7 DELIVERY, STORAGE, AN
17、D HANDLING: A. Conform to ACI 304. Store aggregate separately for each kind or grade, to prevent segregation of sizes and avoid inclusion of dirt and other materials. B. Deliver cement in original sealed containers bearing name of brand and manufacturer, and marked with net weight of contents. Store
18、 in suitable watertight building in which floor is raised at least 300 mm (1 foot) above ground. Store bulk cement / and fly ash / in separate suitable bins. C. Deliver other packaged materials for use in concrete in original sealed containers, plainly marked with manufacturers name and brand, and p
19、rotect from damage until used. 1.8 PRE-CONCRETE CONFERENCE: A. General: At least 15 days prior to submittal of design mixes, conduct a meeting to review proposed methods of concrete construction to achieve the required results. B. Agenda: Includes but is not limited to: 1. Submittals. 2. Coordinatio
20、n of work. 3. Availability of material. 4. Concrete mix design including admixtures. 5. Methods of placing, finishing, and curing. 6. Finish criteria required to obtain required flatness and levelness. 7. Timing of floor finish measurements. 8. Material inspection and testing. C. Attendees: Include
21、but not limited to representatives of Contractor; subcontractors involved in supplying, conveying, placing, finishing, and curing concrete; lightweight aggregate manufacturer; admixture manufacturers; Resident Engineer; Consulting Engineer; Department of Veterans Affairs retained testing laboratorie
22、s for concrete testing and finish (F-number) verification. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-03-11 03 30 00 - 4 D. Minutes of the meeting: Contractor shall take minutes and type and distribute the minutes to attendees within five days o
23、f the meeting. SPEC WRITER NOTE: Mock-up is used only with architectural exposed concrete. Check with architect for requirements. Add ACI 303.1-97 “Standard Specification for Cast-In-Place Architectural Concrete” to the Applicable Publications section. 1.9 MOCK-UP: A. In addition to the other specif
24、ied samples and tests, construct a mock-up using the materials, reinforcing, forming system and construction methods proposed for use in exposed architectural concrete. B. Construct the mock-up with at least a 2.5 m by 2.5 m (8 feet by 8 feet) exposed surface and suitable foundations. Include the fo
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA0330002011CASTINPLACECONCRETEPDF