1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAugust 2, 20111SUBJECT 9703OUTLINE OF INVESTIGATIONFORDISTRIBUTED GENERATION WIRING HARNESSESIssue Number: 1AUGUST 2, 2011Summary of TopicsThis is the first issue of the Outline of Investigation
2、for DistributedGeneration Wiring Harnesses, Subject 9703.The UL Foreword is no longer located within the UL Outline of Investigation. Forinformation concerning the use and application of the requirements contained inthis Outline of Investigation, the current version of the UL Foreword is located onU
3、LStandardsInfoNet at: http:/ 2011 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 2, 2011SUBJECT 97032No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHO
4、UT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .52 General 52.1 Components .52.2 Units of measurement .62.3 References 63 Glossary .6CONSTRUCTION4 Enclosure 75 Protection of Users - Accessibility of Uninsulated Live Parts 86 Electric Shock 87 Wiring Terminals 88 Wire and Cable .89 Field Wiring Com
5、partments 810 Electrical Connections 811 Live Parts .912 Spacings 913 Barriers .914 Connectors 915 Printed-Wiring Boards 916 Fuses and Fuse Holders 9PERFORMANCE17 General 1018 Temperature .1019 Dielectric Voltage-Withstand Test .1120 Leakage Current Test .1221 Mold Stress-Relief Distortion .1322 Str
6、ain Relief Test .1323 Crush Test .1424 Push Test 1425 Impact Test 1526 Terminal Torque Test .1527 Grounding Impedance Test 1628 Bonding Conductor Test .1629 Compression Test 1630 Current Overload Test .1631 Corrosive Atmosphere Test 1732 Metallic Coating Thickness Test 1733 Water Spray Test .1734 We
7、t Insulation-Resistance Test .1735 Temperature Cycling Test .1836 Humidity Cycling Test .19AUGUST 2, 2011 SUBJECT 9703 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULRATING37 Details .20MARKINGS38 Details .2039 Installation and Assembly Inst
8、ructions .21APPENDIX AStandards for ComponentsA1AUGUST 2, 2011SUBJECT 97034UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover wiring harnesses intended to interconnect distributed generation systemd
9、evices.1.2 These requirements cover distributed generation wiring harnesses intended for factory and fieldwiring and may include assemblies of cables intended for interconnection of PV modules, solar collectors,and other distributed generation sources, interconnection of inverters, converters, contr
10、ollers, andchargers as well as distributed generation system communication harnesses and system outputharnesses.1.3 The products covered by these requirements are intended to be installed in accordance with theNational Electrical Code, ANSI/NFPA 70.2 General2.1 Components2.1.1 Except as indicated in
11、 2.1.2, a component of a product covered by this Outline of Investigation shallcomply with the requirements for that component. See Appendix A for a list of standards coveringcomponents generally used in the products covered by this Outline of Investigation.2.1.2 A component need not comply with a s
12、pecific requirement that:a) Involves a feature or characteristic not needed in the application of the component in theproduct covered by this Outline of Investigation, orb) Is superseded by a requirement in this Outline of Investigation.2.1.3 A component shall be used in accordance with its recogniz
13、ed rating established for the intendedconditions of use.2.1.4 Specific components are recognized as being incomplete in construction features or restricted inperformance capabilities. Such components are intended for use only under limited conditions, such ascertain temperatures not exceeding specif
14、ied limits, and shall be used only under those specific conditionsfor which they have been recognized.AUGUST 2, 2011 SUBJECT 9703 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL2.2 Units of measurement2.2.1 Values stated without parentheses
15、are the requirement. Values in parentheses are explanatory orapproximate information.2.3 References2.3.1 Any undated reference to a code or standard appearing in the requirements of this Outline ofInvestigation shall be interpreted as referring to the latest edition of that code or standard.3 Glossa
16、ry3.1 In the text of this outline, the term unit refers to any product covered by this outline. For the purposeof this outline, the definitions in 3.2 3.17 apply.3.2 AC MODULE The smallest complete unit that includes solar cells, optics, inverters, and othercomponents, excluding tracking devices, in
17、tended to generate ac power from sunlight.3.3 BARRIER A part inside an enclosure that reduces access to a part that involves a risk of fire,electric shock, injury to persons, or electrical energy-high current levels.3.4 ENCLOSURE A surrounding case constructed to provide a degree of protection again
18、st:a) The accessibility of a part that potentially involves a risk of fire, electric shock or injury topersons, orb) The risk of propagation of flame, sparks, and molten metal initiated by an electricaldisturbance occurring within.3.5 FIELD-WIRING LEAD A lead to which a supply, load, or other wire i
19、s intended to be connectedby an installer.3.6 FIELD-WIRING TERMINAL A terminal to which a supply, load, or other wire is intended to beconnected by an installer.3.7 FIXED UNIT A unit that is intended to be permanently connected mechanically and electricallyand only able to be detached by the use of
20、a tool.3.8 GROUNDED CONDUCTOR A system or circuit conductor that is intentionally grounded.3.9 KNOCKOUT A portion of the wall of an enclosure so fashioned that it is capable of being readilyremoved by a hammer, screwdriver, and pliers at the time of installation in order to provide an openingor hole
21、 for the attachment of an auxiliary device, raceway, cable, or fitting.3.10 LIVE PART An electrically conductive part within a unit that during intended use has a potentialdifference with respect to earth ground.3.11 MAXIMUM SYSTEM VOLTAGE The open-circuit voltage (Voc) of the photovoltaic module or
22、panel multiplied by the temperature correction factor specified in Article 690.7 of the National ElectricalCode, ANSI/NFPA 70 for crystalline and multi-crystalline silicon photovoltaic modules and panels. Themaximum system voltage is equal to the Voc for amorphous silicate and thin film photovoltaic
23、 modulesand panels.AUGUST 2, 2011SUBJECT 97036UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL3.12 OPEN-CIRCUIT VOLTAGE (Voc) The maximum no load output voltage of a photovoltaicmodule or panel at standard test conditions (STC).3.13 PERMANENTL
24、Y CONNECTED UNIT A unit connected to the electrical supply by means otherthan a supply cord and an attachment plug.3.14 PRESSURE TERMINAL CONNECTOR A terminal that accomplishes the connection of one ormore conductors by means of pressure without the use of solder. Examples of pressure terminalconnec
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT97032011OUTLINEOFINVESTIGATIONFORDISTRIBUTEDGENERATIONWIRINGHARNESSESISSUENO1 分布式 发电 布线 调查 大纲

链接地址:http://www.mydoc123.com/p-1069519.html