UL SUBJECT 2748A-2014 Outline of Investigation for Arcing Fault Interrupting Devices (Issue 2)《电弧故障断路器的调查大纲 (议题2)》.pdf
《UL SUBJECT 2748A-2014 Outline of Investigation for Arcing Fault Interrupting Devices (Issue 2)《电弧故障断路器的调查大纲 (议题2)》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 2748A-2014 Outline of Investigation for Arcing Fault Interrupting Devices (Issue 2)《电弧故障断路器的调查大纲 (议题2)》.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMAY 29, 20141UL 2748AOutline of Investigation for Arcing Fault Interrupting DevicesIssue Number: 2May 29, 2014Summary of TopicsThis Second issue of the Outline of Investigation is being published
2、 toinclude revisions to the requirements for the Internal Arcing Fault Testand for the Arcing Fault Interruption Test.ULs Outlines of Investigation are copyrighted by UL. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investiga
3、tion and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2014 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMAY 29, 20
4、14UL 2748A2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Components 43 Units of Measurement .54 Undated References 55 Glossary .5CONSTRUCTION6 General 67 Creepage and Clearance Distance 68
5、Wiring .79 Operation 7RATINGS10 General .8MARKING11 General .8INSTRUCTIONS12 General .9PERFORMANCE13 General .914 Continuous Current Test 1015 Power-Frequency Withstand Voltage Tests 1016 Internal Arcing Fault Test .1017 Arcing Fault Interruption Test .11MAY 29, 2014 UL 2748A 3UL COPYRIGHTED MATERIA
6、L NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover fast operating devices intended to interrupt currents associated with arcingfaults, having interrupting times faster than conventional overcurrent devices.1.2 These requ
7、irements cover open type devices that are intended to be installed within powerdistribution equipment.1.3 These requirements cover devices rated up to 38 kV ac maximum.1.4 This outline does not include the requirements for sensors intended to detect arcing faults, devicesintended to trigger the func
8、tioning of the arc interrupting device, or devices intended to quench arcingfaults by transferring the arc to a lower impedance path.1.5 This outline does not include requirements for integration and testing of arcing fault interruptingdevices within equipment it is intended to protect.2 Components2
9、.1 Except as indicated in 2.2, a component of a product covered by this outline shall comply with therequirements for that component.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in the application of the component in
10、theproduct covered by this outline; orb) Is superseded by a requirement in this outline.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific components are incomplete in construction features or restricted in performance capabilities.
11、Such components are intended for use only under limited conditions, such as certain temperatures notexceeding specified limits, and shall be used only under those specific conditions.MAY 29, 2014UL 2748A4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSIO
12、N FROM UL3 Units of Measurement3.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.4 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of this outline shall beinterpreted as referring
13、 to the latest edition of that code or standard.5 Glossary5.1 For the purpose of this outline, the following definitions apply.5.2 ARCING FAULT A non-intentional discharge of electrical energy in air or other gas, includingdischarges across the surface of an insulating material.5.3 INTERRUPTING DEVI
14、CE A device that is used to interrupt an arcing fault.5.4 LOW VOLTAGE A voltage of 1000 V ac or less.5.5 MEDIUM VOLTAGE A voltage of greater than 1000 V ac, up to 38 kV ac.5.6 OPEN TYPE DEVICE A device not provided with an overall enclosure. An open type device isintended to be field installed withi
15、n an end-product equipment enclosure.5.7 POLLUTION DEGREE 2 MICROENVIRONMENT An area where normally only nonconductivepollution occurs, but where occasional, temporary conductivity may be expected. Typical constructionsthat reduce the possibilities of conductive pollution and condensation or high hu
16、midity are:a) Non-ventilated enclosures that are provided with continuous application of heat through theuse of heaters or through continuous energization of the device, with interruptions such thatcooling to the point of condensation does not occur; orb) The use of ventilated enclosures where all o
17、penings are provided with filters.5.8 RESETTABLE Capable of being returned to a closed position by pushing a button, moving ahandle, or similar means. Devices that cannot possibly be returned to a closed position withoutreplacing parts using special tools are not considered resettable.5.9 STANDARD P
18、ROTECTIVE DEVICE A fuse, circuit breaker, or other device that providesprotection against overcurrents and that complies with standards that define the operatingcharacteristics for the overcurrent device.MAY 29, 2014 UL 2748A 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIB
19、UTION WITHOUT PERMISSION FROM ULCONSTRUCTION6 General6.1 Other than as noted in 6.2, interrupting devices that are intended to directly replace standardprotective devices shall comply with the dimensional requirements for the standard protective device thatwill be replaced.6.2 Interrupting devices t
20、hat are intended to directly replace standard protective devices may have overalldimensions that differ from standard device that will be replaced, providing the dimensional changes donot affect the electrical connections or mounting of the device when the replacement is made.6.3 Interrupting device
21、s that are not direct replacements for standard protective devices shall not havedimensions that would allow the device to be inserted in place of a standard protective device.7 Creepage and Clearance Distance7.1 A device intended to replace a standard protective device shall comply with the creepag
22、e andclearance distance requirements of the standard used to investigate the standard protective device.7.2 Creepage and clearance distances within low voltage control circuits of interrupting devices shallcomply with the creepage and clearance distance requirements of the Standard for Industrial Co
23、ntrolEquipment, UL 508. Creepage and clearance distances between low voltage control circuits and mediumvoltage control circuits shall be no less than the creepage and clearance distances required from the lowvoltage circuit to grounded metal, and shall also be sufficient to meet the dielectric requ
24、irements specifiedin this outline for the maximum voltage rating of the device, with the control circuits grounded duringtesting.7.3 For printed wiring boards, the creepage and clearance distances shall comply with requirements ofthe Standard for Insulation Coordination Including Clearances and Cree
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT2748A2014OUTLINEOFINVESTIGATIONFORARCINGFAULTINTERRUPTINGDEVICESISSUE2 电弧 故障 断路器 调查 大纲 议题 PDF

链接地址:http://www.mydoc123.com/p-1069341.html