《UL SUBJECT 2573-2017 OUTLINE OF INVESTIGATION FOR AUTOMATIC AIR RELEASE AND AIR VACUUM VALVES FOR FIRE PROTECTION SERVICE (Issue 2).pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 2573-2017 OUTLINE OF INVESTIGATION FOR AUTOMATIC AIR RELEASE AND AIR VACUUM VALVES FOR FIRE PROTECTION SERVICE (Issue 2).pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAugust 14, 20171UL 2573Outline of Investigation for Automatic Air Release, Air/Vacuum andCombination Air Valves for Fire Protection ServiceIssue Number: 2August 14, 2017Summary of TopicsThis seco
2、nd issue of the Outline of Investigation for Automatic AirRelease and Air/Vacuum Valves for Fire Protection Service, Subject 2573,includes requirements for combination air valves for dry standpipesystems such as those referenced in NFPA 502, Standard for RoadTunnels, Bridges, and other Limited Acces
3、s Highways.ULs Outlines of Investigation are copyrighted by UL LLC. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain t
4、he sole and exclusive property of ULLLC.COPYRIGHT 2017 UL LLCUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 14, 2017UL 25732No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERM
5、ISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Units of Measurement .43 Components 54 References .55 Glossary .5CONSTRUCTION6 General 67 Rated Pressure .68 Materials .6PERFORMANCE9 General 710 Leakage Test 711 Hydrostatic Strength Test .812 Cycling Test .813 Clogging Test .814 Elastomeric Parts (Exce
6、pt Gaskets) Test .915 Plastic Components Impacting Valve Operation 1015.1 Air oven aging .1015.2 Water aging .10MANUFACTURING AND PRODUCTION TESTS16 General 1117 Production Leakage Tests .11MARKINGS18 General 12INSTALLATION INSTRUCTIONS19 General 12AUGUST 14, 2017 UL 2573 3UL COPYRIGHTED MATERIAL NO
7、T AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover automatic air release (vents), air/vacuum valves and combination airvalves intended for fire protection service.1.2 Automatic air release valves for use in wet pipe automati
8、c sprinkler systems are intended forinstallation in a sprinkler branch line when it is desired to evacuate air from portions of the sprinkler pipingsystem.1.3 Automatic air release valves for use with fire pumps are intended for installation on the fire pump tovent entrapped air.1.4 Automatic air/va
9、cuum valves equipped with throttling devices are intended for use with vertical turbinepumps. These valves are intended to release large volumes of air in a controlled manner upon pumpstart-up to reduce air related surges and admit air after shutdown, to minimize the development of vacuumconditions
10、within the pump.1.5 Combination air valves equipped with throttling devices are intended for use in dry standpipe andsimilar applications where the (1) release of large volumes of air in a controlled manner is needed, (2)continuous release of air within the system is needed while the system is press
11、urized and (3) admissionof air into the system is needed to minimize the development of vacuum conditions when the system isshutdown.1.6 Requirements for installation of sprinkler systems are included in the Standard for the Installation ofSprinkler Systems, NFPA 13. Requirements for installation of
12、 devices on fire pumps are included in theStandard for the Installation of Stationary Pumps for Fire Protection, NFPA 20. Requirements for theinstallation of dry standpipe systems are included in standards such as the Standards for the Installationof Standpipe and Hose Systems, NFPA 14 and Road Tunn
13、els, Bridges, and other Limited AccessHighways, NFPA 502.2 Units of Measurement2.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.AUGUST 14, 2017UL 25734UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUT
14、ION WITHOUT PERMISSION FROM UL3 Components3.1 Except as indicated in 3.2, a component of a product covered by this Outline of Investigation shallcomply with the requirements for that component.3.2 A component is not required to comply with a specific requirement that:a) Involves a feature or charact
15、eristic not required in the application of the component in theproduct covered by this Outline of Investigation, orb) Is superseded by a requirement in this Outline of Investigation.3.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.3.4 Specific
16、 components are incomplete in construction features or restricted in performance capabilities.Such components are intended for use only under limited conditions, such as certain temperatures notexceeding specified limits, and shall be used only under those specific conditions.4 References4.1 Any und
17、ated reference to a code or standard appearing in the requirements of this Outline ofInvestigation, shall be interpreted as referring to the latest edition of that code or standard.5 Glossary5.1 For the purpose of this outline, the following definitions apply.5.2 AUTOMATIC AIR RELEASE VALVE (VENT) A
18、 device designed to automatically vent into theatmosphere entrapped air that may accumulate at localized high points within a pump or sprinkler pipingsystem while the system is under pressure.5.3 AUTOMATIC AIR/VACUUM VALVE A device designed to automatically release and admit largevolumes of air duri
19、ng vertical turbine pump start-up and shutdown.5.4 COMBINATION AIR VALVE A device (single or dual body) having the features of both anautomatic air release valve and an automatic air/vacuum valve.5.5 ORIFICE The opening through which the air is expelled.5.6 RATED PRESSURE The maximum working pressur
20、e intended to be applied to the inlet of thedevice during end use.5.7 THROTTLING DEVICE A device incorporating an adjustable closure element to control therelease of air from an air/vacuum valve.AUGUST 14, 2017 UL 2573 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION W
21、ITHOUT PERMISSION FROM ULCONSTRUCTION6 General6.1 An automatic air release valve shall have a minimum 1/2-inch (12.7-mm) nominal inlet and outletconnection. An automatic air/vacuum valve shall have a minimum 1-1/2-inch (38.1-mm) nominal inlet andoutlet connection. A combination air valve shall have
22、a minimum 1-1/2-inch (38.1-mm) nominal inlet andoutlet connection for the air/vacuum valve feature and a minimum 1/2-inch (12.7-mm) nominal inlet andoutlet connection for the air release feature of the valve.6.2 Threaded connections shall be in accordance with the Standard for Pipe Threads, General
23、Purpose(Inch), ANSI/ASME B1.20.1, or other national pipe thread standards.6.3 Flange dimensions shall comply with the requirements in the Standard for Gray Iron Pipe Flanges andFlanged Fittings (Classes 25, 125, and 250), ANSI/ASME B16.1, or other national pipe flange standards.6.4 An automatic air
24、release valve shall be provided with an orifice size not less than 1/16-inch (1.59-mm)diameter.6.5 An automatic air release valve intended for use on sprinkler branch lines shall be provided with astrainer having a maximum dimension of an opening in the strainer not exceeding 80 percent of theautoma
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT25732017OUTLINEOFINVESTIGATIONFORAUTOMATICAIRRELEASEANDAIRVACUUMVALVESFORFIREPROTECTIONSERVICEISSUE2PDF

链接地址:http://www.mydoc123.com/p-1069311.html