《UL SUBJECT 2573-2008 OUTLINE OF INVESTIGATION FOR AUTOMATIC AIR RELEASE AND AIR VACUUM VALVES FOR FIRE PROTECTION SERVICE (Issue 1)《消防用自动放气阀和空气 真空阀调查大纲 发布编号 1》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 2573-2008 OUTLINE OF INVESTIGATION FOR AUTOMATIC AIR RELEASE AND AIR VACUUM VALVES FOR FIRE PROTECTION SERVICE (Issue 1)《消防用自动放气阀和空气 真空阀调查大纲 发布编号 1》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULFebruary 15, 20081SUBJECT 2573OUTLINE OF INVESTIGATIONFORAUTOMATIC AIR RELEASE AND AIR/VACUUM VALVES FOR FIREPROTECTION SERVICEIssue Number: 1FEBRUARY 15, 2008Summary of TopicsThis first issue of
2、 the Outline of Investigation for Automatic Air Releaseand Air/Vacuum Valves for Fire Protection Service, Subject 2573, coversrequirements for automatic air release valves (vents) and air/vacuumvalves for use in fire pumps or wet pipe automatic sprinkler systems.The UL Foreword is no longer located
3、within the UL Standard. For informationconcerning the use and application of the requirements contained in thisStandard, the current version of the UL Foreword is located onULStandardsInfoNet at: http:/ 2008 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTIO
4、N ORDISTRIBUTION WITHOUT PERMISSION FROM ULFEBRUARY 15, 2008SUBJECT 25732No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Units of Measurement .43 Components 44 References .55 Glossary .5CONST
5、RUCTION6 General 57 Rated Pressure .68 Materials .6PERFORMANCE9 General 610 Leakage Test 611 Hydrostatic Strength Test .712 Cycling Test .713 Clogging Test .714 Elastomeric Parts (Except Gaskets) Test .8MANUFACTURING AND PRODUCTION TESTS15 General .916 Production Leakage Tests 9MARKINGS17 General .9
6、INSTALLATION INSTRUCTIONS18 General 10FEBRUARY 15, 2008 SUBJECT 2573 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover automatic air release (vents) and air/vacuum valves intended for fireprotecti
7、on service.1.2 Automatic air release valves for use in wet pipe automatic sprinkler systems are intended forinstallation in a sprinkler branch line when it is desired to evacuate air from portions of the sprinkler pipingsystem.1.3 Automatic air release valves for use with fire pumps are intended for
8、 installation on the fire pump tovent entrapped air.1.4 Automatic air/vacuum valves equipped with throttling devices are intended for use with vertical turbinepumps. These valves are intended to release large volumes of air in a controlled manner upon pumpstart-up to reduce air related surges and ad
9、mit air after shutdown, to minimize the development of vacuumconditions within the pump.1.5 Requirements for installation of sprinkler systems are included in the Standard for the Installation ofSprinkler Systems, NFPA 13. Requirements for installation of devices on fire pumps are included in theSta
10、ndard for the Installation of Stationary Pumps for Fire Protection, NFPA 20.2 Units of Measurement2.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.3 Components3.1 Except as indicated in 3.2, a component of a product covered by
11、 this Outline of Investigation shallcomply with the requirements for that component.3.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in the application of the component in theproduct covered by this Outline of Investigati
12、on, orb) Is superseded by a requirement in this Outline of Investigation.3.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.3.4 Specific components are incomplete in construction features or restricted in performance capabilities.Such components
13、 are intended for use only under limited conditions, such as certain temperatures notexceeding specified limits, and shall be used only under those specific conditions.FEBRUARY 15, 2008SUBJECT 25734UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM
14、 UL4 References4.1 Any undated reference to a code or standard appearing in the requirements of this Outline ofInvestigation, shall be interpreted as referring to the latest edition of that code or standard.5 Glossary5.1 For the purpose of this outline, the following definitions apply.5.2 AUTOMATIC
15、AIR RELEASE VALVE (VENT) A device designed to automatically vent into theatmosphere entrapped air that may accumulate at localized high points within a pump or sprinkler pipingsystem while the system is under pressure.5.3 AUTOMATIC AIR/VACUUM VALVE A device designed to automatically release and admi
16、t largevolumes of air during vertical turbine pump start-up and shutdown.5.4 ORIFICE The opening through which the air is expelled.5.5 RATED PRESSURE The maximum working pressure intended to be applied to the inlet of thedevice during end use.5.6 THROTTLING DEVICE A device incorporating an adjustabl
17、e closure element to control therelease of air from an air/vacuum valve.CONSTRUCTION6 General6.1 An automatic air release valve shall have a minimum 1/2-inch (12.7-mm) nominal inlet and outletconnection. An automatic air/vacuum valve shall have a minimum 1-1/2-inch (38.1-mm) nominal inlet andoutlet
18、connection.6.2 Threaded connections shall be in accordance with the Standard for Pipe Threads, General Purpose(Inch), ANSI/ASME B1.20.1, or other national pipe thread standards.6.3 Flange dimensions shall comply with the requirements in the Standard for Gray Iron Pipe Flanges andFlanged Fittings (Cl
19、asses 25, 125, and 250), ANSI/ASME B16.1, or other national pipe flange standards.6.4 An automatic air release valve shall be provided with an orifice size not less than 1/16-inch (1.59-mm)diameter.6.5 An automatic air release valve intended for use on sprinkler branch lines shall be provided with a
20、strainer having a maximum dimension of an opening in the strainer not exceeding 80 percent of theautomatic air release valves orifice diameter. The surface area of the screen openings shall not be lessthan a ratio of 4 to 1 of the cross-sectional area of a Schedule 40 pipe of the same nominal size a
21、s theinlet of the automatic air release valve.FEBRUARY 15, 2008 SUBJECT 2573 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL6.6 Automatic air/vacuum valves shall be equipped with a throttling device to control the release of air.7 Rated Pres
22、sure7.1 An automatic air release or air/vacuum valve shall have a rated pressure of 175 psig (1.21 MPa) orgreater.8 Materials8.1 The body of an automatic air release or air/vacuum valve including throttling device shall beconstructed of a metallic material having corrosion resistance at least equiva
23、lent to cast iron.8.2 Metallic seating surfaces used in an automatic air release or air/vacuum valve shall be constructed ofmaterials with corrosion resistance at least equivalent to brass, bronze, or Series 300 stainless steel.8.3 A strainer for an automatic air release or air/vacuum valve shall be
24、 constructed of materials havingcorrosion resistance at least equivalent to brass, bronze or Series 300 stainless steel.PERFORMANCE9 General9.1 Representative samples of each size automatic air release or air/vacuum valve are to be subjected tothe tests described in these requirements.10 Leakage Tes
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT25732008OUTLINEOFINVESTIGATIONFORAUTOMATICAIRRELEASEANDAIRVACUUMVALVESFORFIREPROTECTIONSERVICEISSUE1

链接地址:http://www.mydoc123.com/p-1069310.html