《UL 891 CRD-2016 UL Standard for Safety Switchboards - Section Paragraph Reference 6 2 1 6 2 16 8 6 14 8 8 4 Subject Inclusion of Inlet Outlet Requirements for Switchboards (Editio.pdf》由会员分享,可在线阅读,更多相关《UL 891 CRD-2016 UL Standard for Safety Switchboards - Section Paragraph Reference 6 2 1 6 2 16 8 6 14 8 8 4 Subject Inclusion of Inlet Outlet Requirements for Switchboards (Editio.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): WEVZStandard Number: UL 891Standard Title: Standard for SwitchboardsEdition Date: July 26, 2005Edition Number: 11Section / Paragraph Reference: 6.2.1, 6.2.16
3、, 8.6.14, 8.8.4Subject: Inclusion of Inlet/Outlet Requirements for SwitchboardsDECISION:6.2.1.12.2 Switchboards with inlets shall be marked with an additional short circuit current rating for theswitchboard when connected to the inlets.Note: When powered by an alternate source that is connected usin
4、g input connections in accordance with8.8.4.2, the source may provide less available current than that of the “normal” (utility fed) source. Portions ofthe switchboard circuit which will only be powered when connected to the alternate source, such as the inputconnections, may have short circuit curr
5、ent ratings less than the rating of the entire assembly.6.2.1.15.4 For switchboards with inlets and an additional short circuit current rating as specified in6.2.1.12.2, that portion of the switchboard circuit which will only be powered when connected to thealternate source may include components wi
6、th short circuit current ratings less than the rating marked onthe section or interior, but not less than the rating noted in 6.2.1.12.2.6.2.16 Switchboards with provisions for cord connections6.2.16.1 Switchboards provided with single pole separable connectors (input or output connections) thatare
7、not mechanically interlocked shall be marked:a) FOR USE BY QUALIFIED PERSONNEL ONLY, or equivalent, andb) With instructions as to the proper order of connection and disconnection, as noted in thebelow example:WARNING - Risk of Electric ShockPlug connection should be in the following order;1) Equipme
8、nt grounding conductor connectors;2) Grounded circuit conductor connectors; and3) Ungrounded conductor connectors.Disconnection should be in the reverse order.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL6.2.16.2 The marking required by 6.2
9、.16.1 shall be located adjacent to the point of connection.6.2.16.3 Switchboards with inlets shall be marked to indicate the type of derived system that theswitchboard is intended to interconnect in accordance with either (a) or (b):a) Switchboards that do not switch the neutral conductor shall be m
10、arked with the following:“WARNING - For Connection of a Nonseparately Derived (Floating Neutral) System Only.”b) Switchboards that switch the neutral conductor shall be marked with the following:“WARNING - For Connection of a Separately Derived (Bonded Neutral) System Only”6.2.16.4 Switchboards with
11、 inlets shall be marked to indicate the short circuit current rating when theswitchboard is powered by a source that is connected through the use of the inlets. See 6.2.1.12.2.8.6.14 Receptacles Relocated to Section 8.8.4.3.18.6.14.1 A receptacle shall be rated for the voltage involved and shall be
12、of the type having a terminalintended for use only with an equipment grounding conductor.8.6.14.2 Overcurrent protection for a receptacle branch circuit shall be provided within the section or inanother section of a group of sections intended to be used together.8.6.14.3 A single receptacle installe
13、d on an individual branch circuit shall have an ampere rating of notless than that of the branch circuit.8.6.14.4 A duplex receptacle or two or more receptacles on the same branch circuit shall have overcurrentprotection equal to the individual receptacle rating.8.6.14.5 A receptacle in a switchboar
14、d marked “Type 3R” shall comply with 8.2.1.5.1, 8.6.14.8, and8.6.14.9.8.6.14.6 After installation a receptacle face shall project a minimum of 0.38 mm (0.015 in) from thefaceplate or surrounding cover. A faceplate shall be installed so as to seat against a mounting surface.8.6.14.6.1 The receptacle
15、face may be flush with, or project from, a faceplate or surrounding cover ofinsulating material.8.6.14.7 A receptacle installed in a switchboard section shall be located so that neither an attachment plugmounted in the receptacle nor the flexible cord will be likely to interfere with the operation o
16、f any switchor circuit breaker handle. (Note: Relocated to 8.8.4.1.2)8.6.14.8 Class A ground-fault circuit interrupter protection shall be provided for all 130 V and less,single-phase, 15- or 20 A receptacles used in a switchboard marked as having a Type 3R enclosure orintended for outdoor use.8.6.1
17、4.9 All 15- and 20-ampere, 125- and 250-volt nonlocking receptacles used in a switchboard markedas having a Type 3R enclosure or intended for outdoor use shall be rated as “weather-resistant” type.8.8.2.1.1 A terminal (pressure wire connector or wire-binding screw) shall be provided for connection o
18、feach conductor intended to be field-installed in the switchboard section or interior. Connections may beprovided for cord-connected equipment, see Cord-Connectors, Clause 8.8.4.8.8.4 Cord-ConnectorsSTANDARD NUMBER: UL 891 -2-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBU
19、TION WITHOUT PERMISSION FROM UL8.8.4.1 General8.8.4.1.1 If provided with connections for cord-connected equipment, connectors shall comply with Clause8.8.4, Cord-Connectors.8.8.4.1.2 Connections for cord-connected equipment shall be located so that neither the connectormounted in an input or output
20、connector, nor the flexible cord attached to the connector, will be likely tointerfere with the operation of any switch or circuit breaker handle.8.8.4.1.3 An opening through which field installed wiring may pass shall be provided with a bushing orshall be formed so that there are no sharp edges wit
21、h which conductors may come in contact.8.8.4.1.4 All field wiring conductors of an alternating-current circuit that pass through a wall or partition ofmetal having magnetic properties, including the neutral, shall be run through the same opening. See8.8.1.8.6.8.8.4.1.5 An integral multiple pole conn
22、ector shall have sufficient number of poles to accommodate theground, neutral, and all ungrounded supply conductors in one connector. When single pole separableconnectors are provided, there shall be a sufficient number to accommodate the ground, neutral, and allungrounded supply conductors, and the
23、se connectors shall be grouped together.8.8.4.1.6 An integral multiple pole connector shall be of a design such that the ground connection is thefirst connection made when inserting a connector, and is the last connection to be opened when removingthe connector.8.8.4.1.7 Multipole inlets rated below
24、 200 A shall be suitable for connection and disconnection under load.8.8.4.2 Input connections8.8.4.2.1 An integral multiple pole inlet or single pole separable connector shall be of a construction withmale phase and neutral mating contacts, and shall have a rating no less than the rating of the ove
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL891CRD2016ULSTANDARDFORSAFETYSWITCHBOARDSSECTIONPARAGRAPHREFERENCE62162168614884SUBJECTINCLUSIONOFINLETOUTLETREQUIREMENTSFORSWITCHBOARDSEDITIOPDF

链接地址:http://www.mydoc123.com/p-1069036.html