SAE AS 8020-1980 MINIMUM PERFORMANCE STANDARDS FOR ENGINE DRIVEN D C GENERATORS STARTER-GENERATORS AND ASSOCIATED VOLTAGE REGULATORS《发动机驱动的直流发电机 起动发电机及相关调压器的最低性能标准》.pdf
《SAE AS 8020-1980 MINIMUM PERFORMANCE STANDARDS FOR ENGINE DRIVEN D C GENERATORS STARTER-GENERATORS AND ASSOCIATED VOLTAGE REGULATORS《发动机驱动的直流发电机 起动发电机及相关调压器的最低性能标准》.pdf》由会员分享,可在线阅读,更多相关《SAE AS 8020-1980 MINIMUM PERFORMANCE STANDARDS FOR ENGINE DRIVEN D C GENERATORS STARTER-GENERATORS AND ASSOCIATED VOLTAGE REGULATORS《发动机驱动的直流发电机 起动发电机及相关调压器的最低性能标准》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、_ SAE Technical Standards Board Rules provide that: “This report is published by SAE to advance the state of technical and engineering sciences. The use of this report is entirely voluntary, and its applicability and suitability for any particular use, including any patent infringement arising there
2、from, is the sole responsibility of the user.” SAE reviews each technical report at least every five years at which time it may be revised, reaffirmed, stabilized, or cancelled. SAE invites your written comments and suggestions. Copyright 2017 SAE International All rights reserved. No part of this p
3、ublication may be reproduced, stored in a retrieval system or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without the prior written permission of SAE. TO PLACE A DOCUMENT ORDER: Tel: 877-606-7323 (inside USA and Canada)Tel: +1 724-776-4970
4、 (outside USA)Fax: 724-776-0790 Email: CustomerServicesae.org SAE WEB ADDRESS: http:/www.sae.org SAE values your input. To provide feedback on this Technical Report, please visit http:/standards.sae.org/AS8020 AEROSPACESTANDARDAS8020 Issued 1980-01 Reaffirmed 2017-10 Minimum Performance Standards fo
5、r Engine Driven D.C. Generators/Starter-Generators and Associated Voltage Regulators RATIONALEAS8020 has been reaffirmed to comply with the SAE Five-Year Review policy. 1. GENERAL STANDARDS1.1 Scope : This Aerospace Standard (AS) covers the general minimum performance standards for generators/starte
6、r-generators and associated voltage regulators for use in direct current (DC) electric systems for civil aircraft.1.2 Manufacturers Declaration : The manufacturer shall declare the following generator or regulator ratings and characteristics. These “declared“ values shall be the same as those values
7、 termed “rated“ under all sections of this AS.1.2.1Generator :(1) Rated Terminal Voltage(2) Rated Load Current(3) Minimum Blast Cooling Requirement (If Blast Cooling is to be Used)(4) Rated Speed Range(5) Continuous Operating Speed(6) Minimum Speed for Regulation(7) Maximum Speed for Regulation(8) M
8、aximum Overspeed(9) Minimum and Maximum External Field Resistance in Series With the Shunt Field(10) Maximum Operating Altitude(11) Allowable Brush and Commutator Wear (If Applicable)(12) Maximum Static Torque (If Applicable)(13) Equalizing Voltage (If Provided) at Rated Load Current(14) Overhung Mo
9、ment, With Respect to the Drive Pad(15) Terminal Block Cover (If Provided)(16) Type and Rating of Battery (If Required for Start-Up Excitation or Ripple Voltage Test)(17) Maximum Allowable Starter Current and Voltage(18) Rated Starter Locked Rotor Torque1.2.2 Regulator:(1) Rated Voltage(2) Rated Max
10、imum Controlled Field Current(3) Minimum Blast Cooling Requirement (If Blast Cooling is to be Used)(4) Minimum and Maximum Effective Regulator Resistance in Series With Generator Field(5) Maximun Operating Altitude(6) Range of Set Voltage Adjustment (If Adjustable)1.3 Effect of Tests : As a minimum
11、performance requirement, the equipment shall complete all tests under sections (2) and (3) without maintenance. There shall be no evidence of detrimental electrical or mechanical degradation.1.4 Test Samples : Tests under Sections (2) and (3) may performed in any sequence and using no more than two
12、(2) test generators or regulators. Section (4) tests may be performed in combination with Section (2) and (3) tests or performed separately on additional generators or regulators.1.5 System Description : Applicable performance tests described herein shall be met with a compatible generator and regul
13、ator. A battery shall not be included unless otherwise declared by the manufacturer.2. MINIMUM PERFORMANCE UNDER STANDARD CONDITIONSTests under this section shall be performed under the Standard Test Conditions described in Addendum (A).2.1 Generator Rating : The generator shall provide the continuo
14、us rated output current and voltage over the continuous operating speed range.2.2 Overload Capacity : Unless otherwise declared by the manufacturer, the generator shall deliver 150% rated current for two (2) minutes and 200% rated current for five (5) seconds at the minimum speed. IN NO CASE SHALL T
15、HE GENERATOR OVERLOAD CAPACITY BE LESS THAN 120% OF RATED CURRENT.2.3 Speed :2.3.1 Speed Range : The continuous operating speed range shall be that range over which the generator provides continuous rated output current and voltage.2.3.2 Minimum Speed for Regulation : When the generator is driven at
16、 minimum speed for regulation, it must deliver continuous rated current at rated voltage with not less than 0.5 ohm resistance connected in the external field circuit.2.3.3 Overspeed : The generator shall be capable of being driven at an overspeed equal to 115% of the maximum rated speed for five (5
17、) minutes without mechanical failure or impairment of electrical performance. This test shall be made with the generator control field circuit open and while the generator is hot from ANY prior test.2.3.4 Maximum Speed for Regulation : When the generator is driven at the maximum speed for regulation
18、, it must provide not more than rated voltage with 300 ohms or less resistance in the control field. Generators which do not have a control field shall be as specified by the manufacturer.2.4 Output Voltage :2.4.1 Steady State Voltage Regulation : When operating as a system, the Generator and Regula
19、tor shall have a voltage at the Point of Regulation that remains within 2.5% of the Regulator set voltage when operating at the minimum speed for regulation, maximum speed for regulation and at speed midway between these two speeds. At each test speed, the system shall be operated at no load, 25%, 5
20、0% and 100% rated current and the regulation values recorded. No Regulator adjustments are permitted during these tests. If the Regulator set voltage is adjustable, the adjustment range shall be declared by the manufacturer.2.4.2 Transient Voltage : During the application and removal of loads, the t
21、ransient voltage and recovery time shall not exceed the limits specified by Fig. 1.2.4.3 Ripple Voltage : The generator peak ripple voltage shall not exceed 7% of the nominal DC output voltage when operated at 120% minimum rated speed at 25% and 50% load. The field must be controlled by a manual rhe
22、ostat when making this test. See Fig. 2.2.5 Commutation (Brush Type Designs) : During operation of the generator over the load and speed range there must be no more than fine pin point sparking of the brushes. For Starter-Generators, commutation during starter operation should not damage the commuta
23、tor or degrade subsequent performance.2.6 Dielectric Strength : The generator and/or regulator must withstand, without evidence of breakdown, a test voltage of 500 volts r.m.s. at 50 or 60 Hertz for one (1) minute or 600 volts r.m.s. for one (1) second. The test voltage shall be applied between elec
24、trical circuits and frame and between mutually insulated circuits. Where the electrical circuits are intentionally grounded to frame for RFI control, the grounding circuit may be disconnected for this test.SAE INTERNATIONAL AS8020 Page 2 of 8_ 2.7 Equalizing Voltage : Where provided, the equalizing
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- SAEAS80201980MINIMUMPERFORMANCESTANDARDSFORENGINEDRIVENDCGENERATORSSTARTERGENERATORSANDASSOCIATEDVOLTAGEREGULATORS

链接地址:http://www.mydoc123.com/p-1025370.html