1、Lessons Learned Entry: 2696Lesson Info:a71 Lesson Number: 2696a71 Submitting Organization: SSCa71 Submitted by: Eric Trailla71 POC Name: Mary Byrda71 POC Email: mary.r.byrdnasa.gova71 POC Phone: 228.688.2635Subject: Substation Arc Flash Mishap Abstract: On Monday, September 24, 2007, at approximatel
2、y 12:50 pm Central Daylight Time (CDT), a worker suffered second degree burns to the hands as a result of exposure to an electrical arc flash. The arc flash was caused by an electrical short while servicing a kilowatt-hour meter; located at Stennis Space Centers Test Complex Area Building 4400. Sinc
3、e Worker 1 was hospitalized for inpatient care within 30 days of the incident, the incident was classified as a Type B Mishap in accordance with NPR 8621.1B, reference NASA IRIS incident number 2007-267-00006. The proximate (direct) causes leading to the mishap are listed below: 1. Meter Panel Assem
4、bly (MPA) being serviced by the worker was in an electrically energized state 2. Worker 1 opened MPA knife switches in preparation to review the kilowatt meter 3. Energized knife switch blades extended beyond plane of MPA cover opening 4. Worker 1 was not wearing leather protected, voltage rated glo
5、ves (PPE) 5. Worker 1 was not being monitored by another worker (i.e. buddy system) 6. Worker 1 placed metal MPA cover back onto the MPA enclosure 7. Metal MPA cover contacted the electrically energized knife switch blades causing electrical arc flash at MPA Description of Driving Event: At the time
6、 of the mishap, the injured worker and a co-worker were removing 277/480 volt electrical kilowatt-hour meters for calibration. The meters are associated with the building power distribution system serving Building 4400. Unfortunately, while performing the meter removal task, the affected Provided by
7、 IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-employee installed the metal cover of a meter panel enclosure onto electrically energized knife switches located within the enclosure. This action caused an electrical short resulting in the arc flash that injured
8、 the worker and also caused damage to the meter panel assembly. The worker was not wearing the PPE gloves required to perform the task, (i.e., the worker installed the cover with bare hands.)Lesson(s) Learned: 1. Failure to implement a Safety First type of philosophy amongst employees may lead to sa
9、fety incidents. 2. Without proper contract surveillance, incompliance with critical contractual and safety regulations (Occupational Safety and Health Act, OSHA) may not be identified and lead to safety incidents. 3. Failure to thoroughly assess the hazards of a job/task prior to performing the task
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- REGNASALLIS26962010LESSONSLEARNEDSUBSTATIONARCFLASHMISHAPPDF

链接地址:http://www.mydoc123.com/p-1019382.html