NFPA 101 ERTA 5-2015 Life Safety Code.pdf
《NFPA 101 ERTA 5-2015 Life Safety Code.pdf》由会员分享,可在线阅读,更多相关《NFPA 101 ERTA 5-2015 Life Safety Code.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、 Errata NFPA 101 Life Safety Code 2015 Edition Reference: 14.3.4.4.1, 16.6.3.4.5, 18.5.2.3, 19.5.2.3, 24.3.4.2.1, 26.3.4.6.1, 28.3.4.6.1, and 30.3.4.6.1 Errata No: 101-15-5 The Committees on Safety to Life note the following errors in the 2015 edition of NFPA 101, Life Safety Code. 1. Replace the re
2、ference to “Section 9.8” with “Section 9.12” as follows: 14.3.4.4.1 Carbon monoxide alarms or carbon monoxide detectors in accordance with Section 9.8 9.12 shall be provided in new educational occupancies in the locations specified as follows: (1) On the ceilings of rooms containing permanently inst
3、alled fuel-burning appliances (2) Centrally located within occupiable spaces served by the first supply air register from a permanently installed, fuel-burning HVAC system (3) Centrally located within occupiable spaces adjacent to a communicating attached garage 2. Replace the reference to “Section
4、9.8” with “Section 9.12” as follows: 16.6.3.4.5 Single-station or multiple-station carbon monoxide alarms or detectors shall be provided in accordance with Section 9.8 9.12 in day-care homes where client sleeping occurs and one or both of the following conditions exist: (1) Fuel-fired equipment is p
5、resent. (2) An enclosed parking structure is attached to the day-care home. 3. Replace the reference to “Section 9.8” with “Section 9.12” in two locations, and change one reference from “18.5.2.2” to “18.5.2.2(2)” as follows: 18.5.2.3 The requirements of 18.5.2.2 shall not apply where otherwise perm
6、itted by the following: (1) Approved, suspended unit heaters shall be permitted in locations other than means of egress and patient sleeping areas, provided that both of the following criteria are met: (a) Such heaters are located high enough to be out of the reach of persons using the area. (b) Suc
7、h heaters are equipped with the safety features required by 18.5.2.2 18.5.2.2(2). (2) Direct-vent gas fireplaces, as defined in NFPA 54, National Fuel Gas Code, shall be permitted inside of smoke compartments containing patient sleeping areas, provided that all of the following criteria are met: (a)
8、 All such devices shall be installed, maintained, and used in accordance with 9.2.2. (b) No such device shall be located inside of a patient sleeping room. (c) The smoke compartment in which the direct-vent gas fireplace is located shall be protected throughout by an approved, supervised automatic s
9、prinkler system in accordance with 9.7.1.1(1) with listed quick-response or listed residential sprinklers. (d)* The direct-vent fireplace shall include a sealed glass front with a wire mesh panel or screen. (e)* The controls for the direct-vent gas fireplace shall be locked or located in a restricte
10、d location. (f) Electrically supervised carbon monoxide detection in accordance with Section 9.8 9.12 shall be provided in the room where the fireplace is located. (3) Solid fuelburning fireplaces shall be permitted and used only in areas other than patient sleeping areas, provided that all of the f
11、ollowing criteria are met: (a) Such areas are separated from patient sleeping spaces by construction having not less than a 1-hour fire resistance rating. (b) The fireplace complies with the provisions of 9.2.2. (c) The fireplace is equipped with both of the following: i. Hearth raised not less than
12、 4 in. (100 mm) ii. Fireplace enclosure guaranteed against breakage up to a temperature of 650F (343C) and constructed of heat-tempered glass or other approved material (d) Electrically supervised carbon monoxide detection in accordance with Section 9.8 9.12 is provided in the room where the firepla
13、ce is located (4) If, in the opinion of the authority having jurisdiction, special hazards are present, a lock on the enclosure specified in 18.5.2.3(3)(c)(ii) and other safety precautions shall be permitted to be required. 4. Replace the reference to “Section 9.8” with “Section 9.12” in two locatio
14、ns as follows: 19.5.2.3 The requirements of 19.5.2.2 shall not apply where otherwise permitted by the following: (1) Approved, suspended unit heaters shall be permitted in locations other than means of egress and patient sleeping areas, provided that both of the following criteria are met: (a) Such
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NFPA101ERTA52015LIFESAFETYCODEPDF