NFPA 101 ERTA 2-2014 Life Safety Code.pdf
《NFPA 101 ERTA 2-2014 Life Safety Code.pdf》由会员分享,可在线阅读,更多相关《NFPA 101 ERTA 2-2014 Life Safety Code.pdf(1页珍藏版)》请在麦多课文档分享上搜索。
1、 Errata NFPA 101Life Safety Code2015 Edition Reference: 12.4.2.1 Errata No.: 101-15-2 The Committee on Assembly occupancies notes the following error in the 2015 edition of NFPA 101, Life Safety Code. 1. Add Subpart (2) of 12.4.2.1 which was inadvertently omitted from the First and Second Draft to r
2、ead as follows: 12.4.2.1 To be considered smoke protected, an assembly seating facility shall comply with both of the following: (1) All enclosed areas with walls and ceilings in buildings or structures containing smoke-protected assembly seating shall be protected with an approved, supervised autom
3、atic sprinkler system in accordance with Section 9.7, unless otherwise permitted by one of the following: (a) The requirement of 12.4.2.1(1) shall not apply to the floor area used for contest, performance, or entertainment, provided that the roof construction is more than 50 ft (15 m) above the floo