NFPA 1 ERTA 1-2014 Fire Code.pdf
《NFPA 1 ERTA 1-2014 Fire Code.pdf》由会员分享,可在线阅读,更多相关《NFPA 1 ERTA 1-2014 Fire Code.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、 Errata NFPA 1Fire Code 2015 Edition Reference: 2.2, Table 6.1.14.4.1(a) and (b), 13.3.1.6, 13.7.2.13.2.1, 14.11.3.3, 18.5.2, 18.5.3, 20.1.2, 20.1.5.12, 25.1.1, 25.3, 25.4, A.3.3.164.2, and A.13.3.2.9.1 Errata No: 1-15-1 The Committee on Fire Code notes the following errors in the 2015 edition of NF
2、PA 1, Fire Code. 1. Revise Section 2.2 by replacing the NFPA 1192 edition year of 2014 with 2015, as follows: NFPA 1192, Standard on Recreational Vehicles, 20142015 edition. 2. Revise Table 6.1.14.4.1(a) and (b), single-dagger footnote, by replacing the reference to 13.3.1.7 with 13.3.1.8, as follow
3、s: Minimum Fire Resistance Rating. The fire resistance rating is permitted to be reduced by 1 hour, but in no case to less than 1 hour, where the building is protected throughout by an approved automatic sprinkler system in accordance with NFPA 13 and supervised in accordance with 13.3.1.78. 3. Revi
4、se 13.3.1.6 by deleting water mist as follows: 13.3.1.6* In areas protected by automatic sprinklers, automatic water mist heat-detection devices required by other sections of this Code shall not be required. 101: 9.7.1.4 4. Revise 13.7.2.13.2.1 by replacing the reference to 13.7.2.14 with 13.7.1.14,
5、 as follows: 13.7.2.13.2.1 Carbon monoxide alarms or carbon monoxide detectors in accordance with 13.7.21.14 and 13.7.2.13.2 shall be provided in new one- and two-family dwellings where either of the following conditions exists: (1) Dwelling units with communicating attached garages, unless otherwis
6、e exempted by 13.7.2.13.2.3 (2) Dwelling units containing fuel-burning appliances or fuel-burning fireplaces 101: 24.3.4.2.1 5. Revise 14.11.3.3 by replacing the NFPA 101 extract citation of 7.7.3.4 with 7.7.3.3, as follows: 14.11.3.3* Stairs and ramps that continue more than one-half story beyond t
7、he level of discharge shall be provided with an approved means to prevent or dissuade occupants from traveling past the level of discharge during emergency building evacuation. 101: 7.7.3.43 6. Revise 18.5.2 by deleting (122 m) and replacing it with (183 m) as follows: 18.5.2 Detached One- and Two-F
8、amily Dwellings. Fire hydrants shall be provided for detached one- and two-family dwellings in accordance with both of the following: (1) The maximum distance to a fire hydrant from the closest point on the building shall not exceed 600 ft (122183 m). (2) The maximum distance between fire hydrants s
9、hall not exceed 800 ft (244 m). 7. Revise 18.5.3 by deleting (76 m) and replacing it with (122 m) as follows: 18.5.3 Buildings Other than Detached One- and Two-Family Dwellings. Fire hydrants shall be provided for buildings other than detached one- and two-family dwellings in accordance with both of
10、 the following: (1) The maximum distance to a fire hydrant from the closest point on the building shall not exceed 400 ft (76122 m). (2) The maximum distance between fire hydrants shall not exceed 500 ft (152 m). 8. Revise 20.1.2 Flame-Retardant Requirements by changing the NFPA 101 extract citation
11、s from 12.4.5.11.X and 13.4.5.11.X to 12.4.6.11.X and 13.4.6.11.X, respectively, as follows: 20.1.2 Flame-Retardant Requirements. 20.1.2.1 Combustible scenery of cloth, film, vegetation (dry), and similar materials shall comply with one of the following: (1) They shall meet the flame propagation per
12、formance criteria contained in Test Method 1 or Test Method 2, as appropriate, of NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films. (2) They shall exhibit a heat release rate not exceeding 100 kW when tested in accordance with NFPA 289, Standard Method of Fire Tes
13、t for Individual Fuel Packages, using the 20 kW ignition source. 101: 12.4.56.11.1; 101: 13.4.56.11.1 20.1.2.2 Foamed plastics (see definition of cellular or foamed plastic in 3.3.41 of NFPA 101) shall be permitted to be used if they exhibit a heat release rate not exceeding 100 kW when tested in ac
14、cordance with NFPA 289, Standard Method of Fire Test for Individual Fuel Packages, using the 20 kW ignition source or by specific approval of the AHJ. 101: 12.4.56.11.2; 101: 13.4.56.11.2 20.1.2.3 Scenery and stage properties not separated from the audience by proscenium opening protection shall be
15、of noncombustible materials, limited-combustible materials, or fire-retardant- treated wood. 101: 12.4.6.11.3; 101: 13.4.56.11.3 20.1.2.4 In theaters, motion picture theaters, and television stage settings, with or without horizontal projections, and in simulated caves and caverns of foamed plastic,
16、 any single fuel package shall have a heat release rate not to exceed 100 kW where tested in accordance with one of the following: (1) UL 1975, Standard for Fire Tests for Foamed Plastics Used for Decorative Purposes (2) NFPA 289, Standard Method of Fire Test for Individual Fuel Packages, using the
17、20 kW ignition source 101: 12.4.56.11.4; 101: 13.4.56.11.4 9. Revise 20.1.5.12 Projection Rooms by changing the NFPA 101 extract citations from 12.4.6.X and 13.4.6.X to 12.4.7.X and 13.4.7.X, respectively, as follows: 20.1.5.12 Projection Rooms. 20.1.5.12.1 Film or video projectors or spotlights uti
18、lizing light sources that produce particulate matter or toxic gases, or light sources that produce hazardous radiation, without protective shielding shall be located within a projection room complying with 12.3.2.1.2 of NFPA 101. 101: 12.4.67.3; 101: 13.4.67.3 20.1.5.12.2 Every projection room shall
19、 be of permanent construction consistent with the building construction type in which the projection room is located and shall comply with the following: (1) Openings shall not be required to be protected. (2) The room shall have a floor area of not less than 80 ft2 (7.4 m2) for a single machine and
20、 not less than 40 ft2 (3.7 m2) for each additional machine. (3) Each motion picture projector, floodlight, spotlight, or similar piece of equipment shall have a clear working space of not less than 30 in. (760 mm) on each side and at its rear, but only one such space shall be required between adjace
21、nt projectors. 101: 12.4.67.4; 101: 13.4.67.4 10. Revise 25.1.1 by adding NFPA 102 as follows: 25.1.1 The construction, location, protection, and maintenance of grandstands and bleachers, folding and telescopic seating, tents, and membrane structures shall meet the requirements of this chapter. Seat
22、ing facilities located in the open air or within enclosed or semi-enclosed structures, such as tents, membrane structures, and stadium complexes, shall comply with this chapter, NFPA 101, and NFPA 102, Standard for Grandstands, Folding and Telescopic Seating, Tents, and Membrane Structures. 11. Revi
23、se Section 25.3 by changing all NFPA 101 extract citations from 12.4.8.X.X to 12.4.9.X.X, as follows: 25.3 Grandstands. 25.3.1 Seating. 25.3.1.1 Where grandstand seating without backs is used indoors, rows of seats shall be spaced not less than 22 in. (560 mm) back-to-back. 101: 12.4.89.2.1 25.3.1.2
24、 The depth of footboards and seat boards in grandstands shall be not less than 9 in. (230 mm); where the same level is not used for both seat foundations and footrests, footrests independent of seats shall be provided. 101: 12.4.89.2.2 25.3.1.3 Seats and footrests of grandstands shall be supported s
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NFPA1ERTA12014FIRECODEPDF