NAVY UFGS-31 21 13-2011 RADON MITIGATION《氡气缓解》.pdf
《NAVY UFGS-31 21 13-2011 RADON MITIGATION《氡气缓解》.pdf》由会员分享,可在线阅读,更多相关《NAVY UFGS-31 21 13-2011 RADON MITIGATION《氡气缓解》.pdf(36页珍藏版)》请在麦多课文档分享上搜索。
1、*USACE / NAVFAC / AFCESA / NASA UFGS-31 21 13 (August 2011)-Preparing Activity: NAVFAC SupersedingUFGS-31 21 13 (April 2006)UFGS-13287 (August 2004)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2011*SECTION TABLE OF CONTENTSDIVISION 31 - EARTHWORKSECTION 31
2、21 13RADON MITIGATION08/11PART 1 GENERAL1.1 SUMMARY1.2 REFERENCES1.3 DEFINITIONS1.3.1 Design1.3.2 Design Drawings1.3.3 Designer1.3.4 Contract Documents1.3.5 Long Term Radon Detectors1.3.6 Short Term Radon Detectors1.3.7 Suction Hole1.3.8 Suction Point1.3.9 Test Hole1.4 SYSTEM DESCRIPTION AND REQUIRE
3、MENTS1.4.1 Performance Requirements1.4.2 Criteria for Pricing Diagnostic Testing and Suction Points1.5 SUBMITTALS1.6 DESIGN REQUIREMENTS1.6.1 Design Drawing Requirements1.6.1.1 Radon Mitigation Systems (Format and Content)1.6.1.2 Radon Mitigation Systems Enclosures (Format and Content)1.6.2 Design N
4、arrative1.6.2.1 Format1.6.2.2 Content1.6.3 Design Review and Approval1.7 RADON DETECTOR LOCATION LOG1.8 WORKER HEALTH AND SAFETY1.9 QUALITY ASSURANCE1.9.1 Contractor Qualifications and Experience1.9.1.1 Contractor Qualifications1.9.1.2 Contractor Experience1.9.2 Testing Laboratory1.9.3 Diagnostic Te
5、sting Equipment1.9.4 On-Site SupervisionSECTION 31 21 13 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-1.10 DELIVERY, STORAGE AND HANDLING1.10.1 Delivery of Products1.10.2 Storage and Handling1.11 PROJECT CONDITIONS1.11.1 Project Drawings1.11
6、.2 Existing Conditions1.11.3 Building Descriptions1.12 POST MITIGATION TESTING - SCHEDULE OF PRICES DATAPART 2 PRODUCTS2.1 RADON MITIGATION SYSTEMS2.1.1 System Performance2.1.1.1 System Piping2.1.1.2 System Outlet Location2.1.1.3 System Failure Warning Monitor2.1.1.4 Air Cleaners2.1.1.5 Ventilation
7、Devices2.1.1.6 Back Drafting2.1.2 Radon Mitigation Systems Components2.2 RADON MITIGATION SYSTEMS ENCLOSURESPART 3 EXECUTION3.1 RADON TESTING3.1.1 Pre-Mitigation Testing3.2 DESIGN RADON MITIGATION SYSTEMS AND SYSTEMS ENCLOSURES3.3 RADON MITIGATION SYSTEMS INSTALLATION3.3.1 Installation3.3.2 Supervis
8、ion3.3.3 Electrical Work3.3.4 Mechanical Work3.3.5 System Identification3.4 RADON MITIGATION SYSTEM ENCLOSURES INSTALLATION3.5 FIELD QUALITY CONTROL3.5.1 Radon Mitigation System Inspection3.5.2 Post Mitigation Testing and Monitoring3.5.2.1 Short Term3.5.2.2 Long Term- End of Section Table of Content
9、s -SECTION 31 21 13 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-31 21 13 (August 2011)-Preparing Activity: NAVFAC SupersedingUFGS-31 21 13 (April 2006)UFGS-13287 (August 2004)UNIFIED FACILITIES GUIDE SPE
10、CIFICATIONSReferences are in agreement with UMRL dated July 2011*SECTION 31 21 13RADON MITIGATION08/11*NOTE: This guide specification covers the requirements for diagnostic testing for radon and designing and constructing radon mitigation systems in existing buildings and facilities, including const
11、ructing radon mitigation systems enclosures, when required.Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new project specification sections. Edit this guide specification for project specific requirements by a
12、dding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments, suggestions and recommended changes for this guide specification
13、are welcome and should be submitted as a Criteria Change Request (CCR).*RADON MITIGATION FOR NEW CONSTRUCTIONNOTE: EPA has published “EPA Map of Radon Zones“. Consult the map, EPA document EPA-402-R-93-071, “EPA Map of Radon Zones“ and EPA documents for each state for additional information concerni
14、ng radon zones.For new construction in Zone 1 areas as defined on “EPA Map of Radon Zones“, passive radon mitigation systems should be incorporated into the original building design. The design should include provisions to permit installation of exhaust fans, if necessary, after testing the building
15、 under occupied conditions. Criteria for radon mitigation SECTION 31 21 13 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-in new construction is specified in EPA 625-R-92-016, (1994, Third Printing with Addenda) “Radon Prevention in Design and
16、 Construction of Schools and Other Large Buildings“.Materials (aggregate for capiliary water barrier and poly(vinyl chloride) (PVC) pipe) currently in use for constructing new buildings, when properly arranged as indicated and specified in EPA 625-R-92-016, will provide a passive radon mitigation sy
17、stem. A separate specification section on radon mitigation for new construction seems unnecessary considering the materials are addressed in Division 02 and Division 15 sections and the installation will be shown on the drawings.*NOTE: In most cases the work for this project will be performed by sma
18、ll business Contractors with little or no sophisticated drawing resources. Therefore, the design requirements are very minimal with respect to the production of drawings.A simple, effective, efficient, and economical radon mitigation system is little more than a PVC vent pipe (one suction point) exh
19、austed to the atmosphere without a fan (passive system). For large areas requiring mitigation, the system could include several vent pipes connected to a single outlet with an appropriately sized in-line fan (active system). Depending on the distances between suction points, several individual vent
20、pipes with or without in-line fans may be more practical.This guide specification provides criteria and material requirements for diagnostic testing, designing and constructing radon mitigation systems, post mitigation testing and constructing gypsum wallboard enclosures to conceal the radon mitigat
21、ion systems in occupied spaces.*DRAWING INFORMATION REQUIREDNOTE: Prepare A4 (297 by 210 mm) 8 1/2 by 11 inch scaled drawings for each building and include at the end of this section. Depending on the building size, several drawings may be needed to show the entire building in legible scaled size.A
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYUFGS3121132011RADONMITIGATION 氡气 缓解 PDF