NAVY MIL-T-960 E-1963 TRAPS STEAM INTERMITTENT DISCHARGE AND CONTINUOUS FLOW NAVAL SHIPBOARD《海军舰间歇放电和连续流蒸汽陷阱》.pdf
《NAVY MIL-T-960 E-1963 TRAPS STEAM INTERMITTENT DISCHARGE AND CONTINUOUS FLOW NAVAL SHIPBOARD《海军舰间歇放电和连续流蒸汽陷阱》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-T-960 E-1963 TRAPS STEAM INTERMITTENT DISCHARGE AND CONTINUOUS FLOW NAVAL SHIPBOARD《海军舰间歇放电和连续流蒸汽陷阱》.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、MIL-T-Sb0E Li7 = SS9990b 0270323 O - MIL-T-960E (SHIPS) 21 June 1963 SUPERSEDING MIL-T-B6OD(SHIPS) 8 September 1958 MILITARY SPECIFICATION TRAPS, STEAM, INTERMITTENT DISCHARGE AND CONTINUOUS FLOW, NAVAL SHIPBOARD 1. SCOPE 1.1 Scope.- This specification covers steam traps for use in draining condensa
2、te from steam systems. 1.2 - Classification.- Sream traps shall be of the following types and series, as specified (see 6.1): Type I Type II Type III Series 100 Series 150 Series 300 Series 400 Series 600 Series 1500 - Fluid level actuated (open bucket, inverted bucket, or ball float). - Pulsating e
3、lement or bimetallic. - Continuous discharge, no moving parts. - Bronze body traps; up to and including 100 pounds per square inch .s.i.) working - Steel body traps; from 101 to 150 p.s.i., inclusive, working pressure, 500F. maximum - From 151 to 300 p.s.i., inclusive, working pressure; 775F. maximu
4、m temperature. - From 301 to 400 p.s.i., inclusive, working pressure; 775F. maximum temperature. - From 401 to 600 p.s.i., inclusive, working pressure at 975F. - From 601 to 1500 p.s.i., inclusive, working pressure at 975F. pressure, 425 degrees Fahrenheit (“F.) maximum temperature. temperature. 2.
5、APPLICABLE DOCUMENTS 2.1 The following documents of the issue in effect on date of invitation for bids or request for proposal, form a part of the specification to the extent specified herein. SPECIFICATIONS FEDERAL QQ-N-281 QQ-S-763 QQ-S-766 - Nickel-Copper Alloy (Monel and R-Monel), Bars, Plates,
6、Rods, Sheets, Strips, - Steel Bars, Shapes and Forgings - Corrosion Resisting. - Steel Plates, Sheets, and Strip Corrosion Resisting. Wire, Forgings and Structural and Special Shaped Sections. MILITARY MIL-B-857 MIL-D-963 MIL- F-1183 MIL-S-1222 MIL-S-2953 MIL-R- 17 13 1 MIL-F-20042 MIL-G-21032 - Bol
7、ts, Nuts and Studs. - Drawings, Electrical, Hull and Mech - Fittings, Tube Cast, Bronze, Silver - Studs, Continuous Thread (Bolt Stud. Round - High Temperature. - Strainers, Steam (for Small Branch Lines). - Rods, Welding, Surfacing. - Flanges, Pipe, Bronze (Silver Brazing). - Gaskets, Metallic - As
8、bestos, Spiral Wound (for ASA Commercial Flanged cal Equipment for Naval Shipboard Use. and Steel Bars, Joints in Piping Systems) (Identification Symbol 2410). STANDARDS MILITARY MIL-STD-105 - Sampling Procedures and Tables for Inspection by Attributes. DRAWINGS BUREAU OF SHIPS B-104 - Flanged Compo
9、sition, Pipe Fittings, 100 Pounds. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-T-SbOE 47 997770b 0270124 2 D MIL-T-QWE (SHIPS) PUBLICATIONS ! BUREAU OF SHIPS NAVSHIPS 250-692-13 - Radiographic Standards for Steel Castings. (Copies of specific
10、ations, standards, drawings, and publications required by suppliers in connection with specific procurement functions should be obtained from the procuring activity or as directed by the contract- ing officer .) 2.2 Other publications.- The following documents form a part of this specification to th
11、e extent specified herein. tIniess otherwise indicated, the issue in effect on they shall also operate satisfactorily when supported on a moving platform rolled up to 17-1/2 degrees in any direction from the normal horizontal. 3.6 Rated discharge capacity.- The rated discharge capacity shall be mark
12、ed on a permanently attached marking tag to indicate the capacity for the trap and the orifice furnished therewith (see 3.10). 3.6.1 Method of rating trap capacity.- Based upon the continuous discharge capacities of the trap at a temperature depression of lo“, 20“ and 30F. as determined by the labor
13、atory or by laboratory confirmed data submitted by the exhibitor, the trap shall be rated as follows: The rated discharge capacity shall be se- lected as the continuous discharge capacity at the highest pressure in the series, and, for 1/2 inch traps shall meet the minimum requirements specified in
14、table IV. Table IV - Minimum requirements for continuous discharge capacities of 1/2 inch traps at specified temperature depressions with constant back pressure of 30 p.s.i. Minimum capacity pounds per hour 10F. depression 1 20F. depression I 30F. depression 1 Trap 1 Inlet series pressure Type I LOO
15、 100 800 900 lo00 150 150 800 900 1000 300 300 800 900 1000 400 400 1400 1500 1600 soo0 600 600 2600 2800 L i 5 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-T-9bOE LI7-W 9999906 0230328 T .li MIL-T-SeOE(SFXIR3) Table IV - Minimum requirement8
16、for continuou8 discharge capcicities of l/Z inch traps at epecie temperoture depreseions with constant back pressure of 50 p.5. (Contd) Minimum capacity pounds per hour Trap Inlet series pressure 30F. depression 10F. depression 20F. depression Typen 100 100 1000 1100 1300 150 150 lo00 1100 1300 soo
17、300 lo00 1100 1300 400 400 1000 1100 1300 800 800 1000 1100 1300 1500 1400 2000 2500 3000 3.7 Steam loss.- Traps shall be designed to have a minimum loss or leakage of steam. When supplied with dry steam at the highest pressure for the trap seres, the trap shall not pass more than 20 pounds of steam
18、 per hour. 3.8 Detail requirements.- 3.8.1 Type I traps.- 3.8.1.1 Series.- Open bucket and inverted bucket traps may be furnished in all series. Ball float traps . shall be furnwm series 100 and 150 only. trap. 3.8.1.2 Air cock.- Ball float traps shall be fitted with an air cock for testing and to v
19、ent air from the 3.8.2 Types II and HI traps.- Types II and l traps may be furnished in all series. 3.9 Drawings.- Drawings shall be furnished in accordance with type I of MIL-D-963. 3.10 Markings.- Each trap shall be stamped or otherwise permanently marked with the following infor- mation in a mann
20、er which will not impair the serviceability of the trap: The data may be on a plate which shall be permanently secured to the trap body except for the direction of flow and body material, which shall be marked on the body directly. (a) The i.p.8. of the inlet and outlet connections. ) Direction of f
21、low (on the trap body). (c) The specification number, type and series - example: “Specification MIL-T-960, type II, series 600.“ (d) The name of the manufacturer. (e) Material of body (on the trap body). (f) Capacity at highest pressure in the series at a temperature depression of 30F (see 3.6). (g)
22、 Replacement seats or orifices shall be labeled to specify trap size and series. 3.11 Workmanship.- Workmanship shall be first class in all respects. 4. QUALITY ASSURANCE PROVISIONS 4.1 Responsibility for inspection.- Unless otherwise specified in the contract or purchase order, the supplier is resp
23、onsible for the performance of all inspection requirements as specified herein. Except as otherwise specified, the supplier may utilize his own facilities or any commercial laboratory acceptable to the Government. The Government reserves the right to perform any of the inspections set forth in the s
24、pecifica- tion where such inspections are deemed necessary to assure supplies and services conform to prescribed requirement s. 6 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-flIL-T-SbOE 47 9999906 0270329 L MIL-T-960E (SHIPS) 4.2 Qualification te
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILT960E1963TRAPSSTEAMINTERMITTENTDISCHARGEANDCONTINUOUSFLOWNAVALSHIPBOARD 海军 间歇 放电 连续流 蒸汽 陷阱 PDF

链接地址:http://www.mydoc123.com/p-982994.html