1、 INCH-POUND MIL-DTL-24643/13E 1 October 2009 SUPERSEDING MIL-DTL-24643/13D 22 August 2002 DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, 300 VOLTS, TYPE LSTTRS This specification is approved for use by all Departments and Agencies of the Department of Defense. The requirements for acq
2、uiring the product described herein shall consist of this specification sheet and MIL-DTL-24643. Construction, Non-Watertight First - Copper conductor, coated or uncoated, 20 AWG, Class B stranding in accordance with ASTM B8. Second - Separator may be used at manufacturers option where required to p
3、rovide free-stripping insulation. Third - Thermoset insulation. Nominal wall thickness of 0.020 inch; wall thickness may vary from nominal as necessary, in order to meet the specified electrical requirements. Fourth - Two conductors, one black and one white (or natural), shall be cabled together to
4、form a pair. The length of lay shall be determined to permit a completed cable to meet the twisting and bending endurance tests. Fifth - An optional binder. Sixth - Braided shield of 34 or 36 AWG, coated or uncoated copper. Braid angle of 30 to 35 degrees; minimum coverage of 85 percent. Seventh - S
5、hield insulation of two polyester tapes with the outer tape sealed. An alternate shield insulation may consist of one polyester tape plus an extruded jacket of a suitable transparent material, minimum average thickness of the transparent material 0.003 inch. The standard identification code shall be
6、 applied by Method 2. Eighth - The specified number of pairs (see table I) shall be cabled together. The length of lay(s) shall be required for the completed cable to meet the twisting and bending endurance tests. Cabling sequence to be consecutive, starting with No. 1, from the center outward. A si
7、ngle pair shall not be used as center for the cable core. Outer layer shall be left hand. Inner layer (s) direction of lay shall be at the manufacturers option. Fillers may be used as necessary to form a firm, well rounded assembly. Ninth - An optional binder. Tenth - Cross-linked polyolefin jacket
8、(see table I for thickness). AMSC N/A FSC 6145 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-24643/13E TABLE I. Details. Overall diameter (inch) Military part no. M24643/13 Type and size Number of pairs Jacket wall thickness min. avg. (inch
9、) min. (inch) max. (inch) Roller diameter (inch) (max.) -01UN LSTTRS-2 2 0.050 0.629 0.680 2.0 -02UN LSTTRS-4 4 0.050 0.685 0.740 2.2 -03UN LSTTRS-6 6 0.050 0.814 0.880 3.0 -04UN LSTTRS-8 8 0.050 0.916 0.990 3.5 -05UN LSTTRS-10 10 0.050 0.999 1.080 4.0 -06UN LSTTRS-12 12 0.070 1.017 1.100 4.0 -07UN
10、LSTTRS-16 16 0.070 1.100 1.190 4.5 REQUIREMENTS: Qualification required. INSPECTION: Basic Electricals: Conductor resistance (ohms/1000 feet at 25 C, max.) 11.95 Voltage withstand (volts, root mean square, min.) Conductor to conductor 2000 Conductor to shield 1000 Component shield to component shiel
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILDTL2464313E2009CABLEELECTRICAL20DEGREECTO90DEGREEC300VOLTSTYPELSTTRSLSTTRS 3600 V20 90 电缆 PDF

链接地址:http://www.mydoc123.com/p-978637.html