1、MIL-C-81752B g7 W 7797706 0256723 b W /- Y MIL-C-81952B(AS) 11 July 1977 Superseding 6 December 197$ MIL-C- 8 195 2A (AS) -_ MILITARY SPECIFICATION COOLER, LIQUID, ELECTRONIC EQUIPMENT HD-957( )/AWM-23(V) This specification has been approved by the Naval Air Systems Command, Department of the Navy 1
2、. SCOPE 1.1 Scope. This specification covers the performance, design, and test requirements for the Electronic Equipment Liquid Coolere(LC) HD-957 The LC shall consist of a cabinet assembly and a ( ) /AWM-23 (V) . 1.2 Classification. remote switching control. culation loop, a chilled water loop, loc
3、al controls and indicators, and elec- tronic subassemblies. The cabinet assembly shall contain a coolant cir- a. Cabinet assembly, major elements Re fer ence Nomenclature Pumping Unit - .Hydraulic Chiller Control Panel, External Gageboard, Internal b. R,emote switching control Nomenclature Control,
4、Remote Switching Paragraph 3.6.1 3.6.2 3.6.3 3.6.4 3.6.5 2. APPLICABLE DOCUMENTS Beneficial comments (recommendations, additions, deletions) and any perti- nent data which may be of use in improving this document should be addressed to: Engineering Specifications and Standards Department (Code 93) N
5、aval Air Engineering Center, Lakehurst, NJ zation Document Impravement Proposal (DD Form 1426) appearing at the end of this document or by letter. . 08733, by using self-addressed Standardi- -1- FSC-4935 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-
6、,-MIL-C-81952B (AS) I 2.1 General. The following documents of the issue specified in AS-4053, Applicable Document List for AWCS Test Set AN/AWM-23(V), form a part of this specification to the extent specified herein. MIL-T-81734 (AS) is the appli- cable general specification for the LC described her
7、ein (see 6.6). SPECIFICATIONS Mil i tarv MIL-M-7793 Meter, Time totalizing MTL-R-16743 RefrigeratingPlants and Systems, Mechanical and Refrigerating System Components - Dichlorodifluoromethane Type 12 - Naval Ship- board Test Set, Airborne Weapon Control System, MIL-T- 8 17 34 (AS) AN/AWM- 2 3 (V) H
8、ughes Air c ia f t Company HMS 20-1458 Material Specification, Fluid, Dielectric HP 10-27 Coolant, Silicate, Ester Base Hughes Process, Dielectric Coolant and Hydraulic Fluid and Operating Systems, Requirements for STANDARDS Military MI L-STD- 761 Electric Power, Alternating Current for Ship- board
9、Use, Characteristics and Utilization of PUBLICATIONS Hughes Aircraft Company. 3282244 Acceptance Test Procedure, Electronic Equipment Liquid Cooler 2.2 Availability of documents. Applicable (see 6.6) 2.3 Precedence of documents. When the requirements of the contract, this specification, or applicabl
10、e subsidiary documents are in conflict, the following precedence shall apply: a. b. c. Contract - The contract shall have precedence over any other document This Specification - This specification shall have precedence over all applicable subsidiary documents (see 6.6) Referenced documents - Any doc
11、ument referenced in this specifi- cation shall have precedence over all applicable documents referenced therein. -2- Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-C-l752B LI7 7777706 0256725 T 3. REQUIREMENTS 3.1 Materials, parts, and processes
12、. Not applicable. Unless otherwise specified herein, materials, parts and processes shall be in accordance with MIL-R- 16743. 3.2 Design and construction. Applicable. 3.2.1 Design features. Not applicable. Unless otherwise specified herein, design features shall be in accordance with MIL-R-16743. 3.
13、2.1.1 Method of operation. Applicable. 3.2.1.2 Commercial test equipment, Applicable. 3.2.1.2.1 Other commercial components. Applicable. 3.2.1.3 Circuit grounds. Applicable. 3.2.1.4 Interchangeability. Applicable. 3.2.1.5 Identification of product, Applicable. 3.2.1.6 Human factors. Applicable. 3.2.
14、1.7 Test set generated acoustic noise. Applicable. 3.2.1.8 Forced-liquid cooling. The LC shall supply cooling fluid to the test stations and weapon replaceable assemblies (WRAs) listed in Table I at the required operating temperature, pressure, and listed flow rate, 3.2.1.9 Space and weight limitati
15、ons. The cabinet assembly shall not exceed 36 inches by 30 inches by 72 inches. not exceed 8 inches by 4 inches by 8 inches. 1500 pounds. The remote control panel shall The weight shall not exceed o 3.2.1.10 Connectors. Applicable. 3.2.1.11 Secondary electrical power. Not applicable. 3.2.1.12 Interf
16、ace. The LC shall provide the interfaces specified below. 3.2.1.12.1 Test station interfaces. The LC shall interface with Test- Station, Radio Frequency 05-213( )/AWM-23(V), Test Station, Low Frequency 05-215( )/AWM-23(V) and 05-379( )/AWM-23(V) and Stand, Fill-Drain, Coolant System M-4730( )/AWM-23
17、(V) through two utility coolant lines (supply and return). 3.2.1.12.2 Potable water interface. The LC shall interface with the potable water through two utility water lines (supply and return). 3.2.1.12.3 Electrical power interface. The LC shall interface with the electrical power specified in 3.2,Z
18、.l through utility power lines. - 3- Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-C-L75ZB q7 a 777970b 0256726 L MIL-C-81952B (AS) TABLE I AN/AWG-9 FIRAS AND AN/Amf-23 ELEMENTS SERVICED BY THE LIQUID COOLER ITEM TEST STATION, RADIO FREQUENCY O
19、J- i13 ( ) /AWM- 2 3 (V) a. b. 6. d. e. f. I Oscillator, Radio Frequency 0-1633( )/AWG-9 : Transmitter, Radar T-1224( )/AWG-9 Power Supply PP-6770( )/AWG-9- Power Supply PP-6771( )/AWG-9 Receiver, Radar R-1785( )/AWG-9 Diuiimy Load, Electrical DA- 6 30 ( ) / AWM- 2 3 (V) TEST STATION, LOW FREQUENCY
20、OJ- 2 15 ( ) /AWM- 23 (V) and OJ-379( )/AWM-23(V) a. Antenna Antenna Servo Electronic Subassembly (when tested separately) b . Receiver, Infrared c. Processos, Data d. Dummy Load, Electr,:al e. Dummy Load, Electrical STAND, FILL-DRAIN COOLANT * Combined flow rates for te AS-2764( )/AWG-9 R-1786( )/A
21、WG-9 * CV-2947 ( ) /AWG-9 * DA-631( )/AWM-23(V) DA-632 ( ) /Am- 2 3 (V) MT-4730 ( ) /Awl- 23 (V) t s ition dummy loads and PiRAs under test will not exceed the maximum Elow rate listed for the teat station. * DA-631 and DA-632 are connected in series. * Tested on 05-2151 )/AWM-23(V) only. -4- MAXIMU
22、M * :LOW RATE GPM 6.8 0.2 4.8 0.8 0.8 0.3 5. O 2.5 2.5 1.0 1.0 0.5 o. 1 1.3 * 3.0 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-C-BL752B LI7 7777706 0256727 3 H MIL-C-81952B (AS) 3.2.2 Utilities. Applicable. 3.2.2.1 Electrical power. Applicable
23、. The LC shall operate from the utility electrical power forms listed in Table II. TABLE II LC ELECTRICAL POWER Item Input Power Forms +29 24 Vdc 440 Vac 60 Hertz CHx), 3-phase, 3-wire, ungrounded 220 Vac, 60 Hz, 3-phase, 3-wire, ungrounded, per MIL-STD-761 Type I. (Alternative power form for van ap
24、plication.) Maximum Load 10 amperes 11.0 kilovolt-amperes (kVA), 0.8 to 1.0 lagging power factor (pf) 11 kVA, 0.8 to 1.0 lagging pf 3.2.2.2 Clean air. Not applicable. 3.2.2.3 Potable water. Applicable. 3.2.2.4 Liquid coolant. Applicable. 3.2.2.5 Helium. Not applicable. 3.2.2.6 Nitrogen. Applicable.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILC81952B1977COOLERLIQUIDELECTRONICEQUIPMENTHD957AWM23VHD957AWM23V 液体 冷却 装置 电子设备 PDF

链接地址:http://www.mydoc123.com/p-978049.html