NAVY A-A-50502-1990 AIR CONDITIONER (UNITARY HEAT PUMP) AIR TO AIR (3 000 TO 300 000 BTU)《空对空(酉热泵)空调器(3 000到300 000 BTU)》.pdf
《NAVY A-A-50502-1990 AIR CONDITIONER (UNITARY HEAT PUMP) AIR TO AIR (3 000 TO 300 000 BTU)《空对空(酉热泵)空调器(3 000到300 000 BTU)》.pdf》由会员分享,可在线阅读,更多相关《NAVY A-A-50502-1990 AIR CONDITIONER (UNITARY HEAT PUMP) AIR TO AIR (3 000 TO 300 000 BTU)《空对空(酉热泵)空调器(3 000到300 000 BTU)》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、I COMMERCIAL ITEM DESCRIPTION l AIR CONDITIONER, (UNITARY HEAT PUMP), AIR TO AIR (3,000 TO 300,000 BTU) Ji The General Services Administration has authorized the use of this Commercial Item Description (CID) in preference to Type I, Type II, Class A, Size 1 and 2 of Military Specification MIL-H-2254
2、7C(YD). 1, Abstract. This Commercial Item Description (CID) covers air-to-air heat pumps for use as residential, commercial, or industrial units and are designed to perform the functions of either heating or cooling, circulating, filtering, cleaning, and dehumidifying an air stream. supplemented by
3、electrical resistance heaters. air conditioning type heat pumps covered by the Association of Home Appliance Manufacturers. Types and classes are as follows: The heating function may be This CID does not apply to room Type I - Heat pump, factory assembled refrigerant circuit or circuits Type II - He
4、at pump (split-system) employing remote outdoor section (packaged unit), separate from indoor section. Class 1 - Department of Energy (DOE) covered products (units with Class 2 - Non-DOE covered products (units with cooling capacity up to cooling capacity up to 65,000 British thermal units (Btu/hr).
5、 300,000 Btu/hr). 2. Salient characteristics. 2.1 Tvpe I heat pump. Unless otherwise specified (see 6.1), the type I heat pump will consist of a factory assembled sheet metal enclosure complete with supply air blower, compressor motor assembly, compressor motor contactor or starter (when required),
6、compressor motor overload protection devices, and crankcase heat. protective device, control devices, changeover valve(s) and check valve(s) (when The unit will be equipped with refrigerant and fan overload IBeneficial comments (recommendations, additions, deletions) and any pertinent1 Idata which m
7、ay be of use in improving this document should be addressed to: I ICommanding Officer (Code 156), Naval Construction Battalion Center, Port I IHueneme. CA 93043-5000. I FSC 4120 DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited, Provided by IHSNot for ResaleNo reproduc
8、tion or networking permitted without license from IHS-,-,-A-A-50502 41 W 9999974 0059835 4 W A-A- 50502 required), refrigerant and oil charge, and a pressure relief means. Supplemental electrical heaters will be furnished with or in the unit. Temperature limiting devices will be furnished on heat pu
9、mps with supplemental electrical heaters. A room indoor thermostat will be provided. 2.2 Type II heat pump. Unless otherwise specified (see G,l), the type II heat pump will consist of a matched system consisting of separate outdoor and indoor sections connected with interconnecting refrigerant pipin
10、g, The outdoor section will consist of an outdoor coil(s), compressor(s) complete with protective devices and crankcase heat, changeover valve(s), check valve(s) when required, fan(s), cabinet, and all control devices and accessories as specified and required for proper operation of the outdoor port
11、ion of the system. section will consist of an indoor coil, supply air blower, cabinet, provision for mounting of filter(s), and all controls and accessories as specified and required for proper operation of the indoor portion of the system. will be provided with oil and a factory charge of refrigera
12、nt. Supplemental electrical heaters complete with temperature limiting devices and controls will be supplied as specified (see 6.1). An outdoor thermostat will be provided integral with or remote from the outdoor unit. A room thermostat will be provided. The indoor The system 2.3 Standards complianc
13、e. Where applicable, all heat pumps will conform to the following: a. b. c. Unit will conform to applicable Underwriters Laboratories (UL) standards. d. e. Insulation and adhesive will meet National Fire Protection Unit will be rated in accordance with Air Conditioning and Refrigeration Institute (A
14、I) Standards 240 or 340, and 270. Unit will be designed to conform to American National Standard Institute (ANSI) B 9.1. Roof curb will be designed to conform to National Roofing Contractors Association (NRAC) standards, Association (NFPA) 90A requirements for flame spread and smoke generation. 2.4
15、Design. between 115 degrees Fahrenheit (OF) and 55F in cooling mode and between 75OF and -20F in heating mode. of UL 559. otherwise specified (see G,l), air quantity and minimum external resistance will be as required in AR1 240 and AR1 340, as applicable. The heat pumps will be designed to operate
16、at ambient temperatures The heat pumps will conform to safety requirements The refrigerant will be ASHRAE refrigerant number R-22, Unless 2.5 Performance. 2 2.5.1 Heat Dump coolinp and heating capacity. cooling (sensible and latent) capacity will not be less than specified for the heating and coolin
17、g indoor and outdoor conditions (see 6.1). The minimum capacity for the supplemental heaters will be 80 percent of the heating load. The heat pump heating and Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-T A-A-50502 4L I 9999974 0059Lb b I A-A- 50
18、502 I 2.5.2 Sound ratinq. than an AR1 270 sound rating of 8.4 bels for units below 38,000 Btu/hr (11,100 watts (W), 8.6 bels for units between 38,000 Btu/hr and 65,000 Btu/hr (19,000 W), and 8.8 bels for units between 65,000 Btu/hr and 300,000 Btu/hr (87,930 W) in rated capacity. All outdoor unitary
19、 heat pumps will not be greater O 2.5.3 EnerpT performance requirement forall non-DOE rated heat pumps. The minimum Energy Efficiency Ratio (EER) for cooling will not be less than 8.0. The minimum Coefficient of Performance (COP) for high temperature heating at 47OF will not be less than 3.0. 2.5.4
20、Enerm performance requirement for DOE rated heat pumps (through 65.000 Btu./hr. single-phase-power units). The heat pumps will have the following minimum Seasonal Energy Efficiency Ratios (SEER), and minimum Heating Seasonal Performance Factor (HSPF) in accordance with AR1 240. 2.5.4.1 Current energ
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYAA505021990AIRCONDITIONERUNITARYHEATPUMPAIRTOAIR3000TO300000BTU 空对空 酉热泵 空调器 3000 300000 BTUPDF

链接地址:http://www.mydoc123.com/p-976279.html