ISA 75 25 01-2000 Test Procedure for Control Valve Response Measurement from Step Inputs《控制阀分布输入反应测量的试验程序》.pdf
《ISA 75 25 01-2000 Test Procedure for Control Valve Response Measurement from Step Inputs《控制阀分布输入反应测量的试验程序》.pdf》由会员分享,可在线阅读,更多相关《ISA 75 25 01-2000 Test Procedure for Control Valve Response Measurement from Step Inputs《控制阀分布输入反应测量的试验程序》.pdf(34页珍藏版)》请在麦多课文档分享上搜索。
1、 AMERICAN NATIONAL STANDARD ANSI/ISA-75.25.01-2000 (R2010) Test Procedure for Control Valve Response Measurement from Step Inputs Approved 16 June 2010 ISA-75.25.01-2000 (R2010) Test Procedure for Control Valve Response Measurement from Step Inputs ISBN: 978-1-936007-49-3 Copyright 2010 by the Inter
2、national Society of Automation. All rights reserved. Not for resale. Printed in the United States of America. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), with
3、out the prior written permission of the Publisher. ISA 67 Alexander Drive P. O. Box 12277 Research Triangle Park, North Carolina 27709 USA - 3 - ISA-75.25.01-2000 (R2010) Preface This preface, as well as all footnotes and annexes, is included for information purposes and is not part of ISA-75.25.01-
4、2000 (R2010). The standards referenced within this document may contain provisions which, through reference in this text, constitute requirements of this document. At the time of publication, the editions indicated were valid. All standards are subject to revision, and parties to agreements based on
5、 this document are encouraged to investigate the possibility of applying the most recent editions of the standards indicated within this document. Members of IEC and ISO maintain registers of currently valid International Standards. ANSI maintain registers of currently valid U.S. National Standards.
6、 This document has been prepared as part of the service of the International Society of Automation (ISA), toward a goal of uniformity in the field of instrumentation. To be of real value, this document should not be static but should be subject to periodic review. Toward this end, the Society welcom
7、es all comments and criticisms and asks that they be addressed to the Secretary, Standards and Practices Board; ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709; Telephone (919) 549-8411; Fax (919) 549-8288; E-mail: standardsisa.org. The ISA Standards and Practices Departme
8、nt is aware of the growing need for attention to the metric system of units in general, and the International System of Units (SI) in particular, in the preparation of instrumentation standards. The Department is further aware of the benefits to USA users of ISA standards of incorporating suitable r
9、eferences to the SI (and the metric system) in their business and professional dealings with other countries. Toward this end, this Department will endeavor to introduce SI-acceptable metric units in all new and revised standards, recommended practices, and technical reports to the greatest extent p
10、ossible. Standard for Use of the International System of Units (SI): The Modern Metric System, published by the American Society for Testing Gibson, J. E. “Nonlinear Automatic Control,“ McGraw-Hill, 1963. Not the same as in ISA-51.1-1979 (R1993), linearity: the closeness to which a curve approximate
11、s a straight line. 3.13 overshoot: the amount by which a step response exceeds its final steady state value. Refer to Figure 24 of ISA-51.1-1979 (R1993). Usually expressed as a percentage of the full change in steady state value. 3.14 position Z: the position of the closure member relative to the se
12、ated position. In this standard and ISA-TR75.25.02-2000 (R2010), expressed as a percent of span. 3.15 resolution: smallest step increment of input signal in one direction for which movement of the output is observed. Resolution is expressed as percentage of input span. The term in this document mean
13、s: the tendency of a control valve to move in finite steps in responding to step changes in input signal applied in the same direction. This happens when the control valve sticks in place, having stopped moving after the previous step change. ISA-75.25.01-2000 (R2010) - 14 - 3.16 response: the time
14、history of a variable after a step change in the input. In this standard and ISA-TR75.25.02-2000 (R2010), the step response can be stem position, flow, or another process variable. 3.17 response flow coefficient vRC :* apparent flow coefficient as determined by testing in an operating type environme
15、nt. The data available in the operating environment may differ from the laboratory data required by valve sizing standards. 3.18 response gain ZG : the ratio of the steady state magnitude of the process change Z divided by the signal step s that caused the change. One special reference response gain
16、 is defined as that calculated from the 2 percent step size response time test. This is designated as Z02G . ZG = Z / s Z02G = 02Z / 02s 3.19 sampling interval st : the time increment between sampled data points. It is the inverse of the sampling rate, 0s0f/1tf = . As used in this standard and ISA-T
17、R75.25.02-2000 (R2010), since more than one variable is being sampled, it is the time between the sets of sampled data. Ideally, all variables in one set are sampled at the same time. If data is recorded using analog equipment, the time constant for the recording equipment shall be less than or equa
18、l to the maximum allowed t . 3.20 sampling rate 0f : the rate at which data samples are taken or the number of samples per unit time. See sampling interval. 3.21 shaft windup:* in rotary valve systems, the tendency of the drive shaft to twist under load while the closure member is stuck at a given p
19、osition. 3.22 sliding friction rF or rT : the force or torque required to maintain motion in either direction at a prescribed input signal ramp rate. 3.23 static: means without motion or change McGraw-Hill, “Dictionary of Scientific and Technical Terms,“ sixth edition, 2002; readings are recorded af
20、ter the device has come to rest. Static performance can be measured either without process loading (bench top tests), with simulated or active loading, or under process operating conditions. This kind of test is sometimes called a dynamic test McGraw-Hill above, which may cause confusion. The static
21、 behavior characteristics identified as important to the control valve performance are the dead band, the resolution, and the valve travel gain. 3.24 steady state: a condition of a dynamic system when it is at rest at a given value. In testing the responses of a dynamic system, step test methods are
22、 often used. The resulting system transitions from an initial steady state value to a new final steady state value. 3.25 step change: a nearly instantaneous step change made to an input signal of a dynamic system with the intention of stimulating a step response of the dynamic system. Such a test is
23、 used to characterize the step response of the dynamic system. - 15 - ISA-75.25.01-2000 (R2010) 3.26 step change time sct : the time between the start of a signal input step and when it reaches its maximum value. 3.27 step test: the application of a step change to an input signal in order to test th
24、e step response dynamics. 3.28 step response time (86T ): the interval of time between initiation of an input signal step change and the moment that the response of a dynamic reaches 86.5% of its full steady state value. The step response time includes the dead time before the dynamic response. 3.29
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ISA7525012000TESTPROCEDUREFORCONTROLVALVERESPONSEMEASUREMENTFROMSTEPINPUTS 控制 分布 输入 反应 测量 试验 程序 PDF

链接地址:http://www.mydoc123.com/p-789786.html