FORD EL3X-1992 PROGRAMMABLE CONTROLLERS - APPLICATIONS《可编程控制器的应用》.pdf
《FORD EL3X-1992 PROGRAMMABLE CONTROLLERS - APPLICATIONS《可编程控制器的应用》.pdf》由会员分享,可在线阅读,更多相关《FORD EL3X-1992 PROGRAMMABLE CONTROLLERS - APPLICATIONS《可编程控制器的应用》.pdf(17页珍藏版)》请在麦多课文档分享上搜索。
1、FORD MANUFACTURING STANDARDS =S=-E-=- - - - -CM_ _=E EL3X PROGRAMMABLE CONTROLLERS - APPLICATIONS EL3X DECEMBER 1992 Page 1 =-E=-=-=-=-=-E=_ -z-= 1. 1.1 GENERAL: The provisions of this Standard shall apply to all electrical/electronic control equipment for machine tools and industrial process equipm
2、ent where programmable controllers (PLCs) are specified. 1.2 This Standard shall supplement requirements in Ford Manufacturing Standards ELX, (electronic systems), EXl, (electrical equipment), and NEMA ICS 3-304, programmable controllers. 1.3 Use of the word “shall“ herein is understood as a require
3、ment; the word “should“ as a recommendation. 1.4 This Standard is not intended to be all-inclusive and any areas where questions of interpretation arise shall be submitted to the specifying activity for resolution. 1.5 Deviations from this Standard shall have the approval of the specifying activity
4、in writing. Any waivers granted shall apply only to the order in question and shall not be considered as permanent. 1.6 Hybrid PLC systems which include special electronic controls not integral to the PLC, and not already listed on the Form 2630 (e.g. for data conversion, communications, etc.) shall
5、 not be supplied without prior written approval from the specifying activity. 1.7 The selection and installation of accessories utilized with PLCs shall comply with the Electrical Equipment Data Form 2630, and any other documents issued by the specifying activity. 1.8 For requirements for PLCs, see
6、Ford Manufacturing Standard EL3. 2. ENVIRONMENT AND ENCLOSURE: 2.1 WINDOWS IN DOORS: *-k* When specified, a sealed window, minimum 0.125 inches thick (Lexan No. 940, or equivalent polycarbonate resin), shall be provided in NEMA 12 enclosure door(s) for observing status indicating lights. Radio frequ
7、ency suppression material (screen or film type) shall be applied to the window to maintain the RF immunity of the panel. gi I y- -w: c NOTE: * Indicates the following item belongs on the attached EL3X p 2 Option Sheet. .a .- . . . . .d“ 2.1.1 POWER SUPPLY REQUIREMENTS: FORD MANUFACTURING STANDARDS =
8、-=-=-_=_II-= 1=D=z= E-s=- EL3X PROGRAMMABLE CONTROLLERS - APPLICATIONS EL3X DECEMBER 1992 Page 2 =- -;x=-= _-_-c-_- i 2.1.1.1 Enclosures containing PLC mainframes, configurable PLC perinpherals or intelligent I/O devices shall have a transformer isolated power source and a transient suppressor appro
9、ved for programmable controller protection. 2.1.1.2 2.1.1.3 2.1.1.4 2.1.1.5 LINE OR LOAD SIDE POWER: * Power supplied to the isolation transformer shall be sourced from the LOAD side of the enclosures main disconnect or, at the specifying activitys WRITTEN OPTION, sourced from an approved lighting t
10、ransformer/disconnect (LTD) connected to the LINE side of the enclosures main disconnect. The LTD (or its Nema 1 switch and fuse portion, for those units with separate transformers sized 2000 VA and larger) shall be mounted behind the same control enclosure door as the main disconnect, typically the
11、 rightmost door. See Appendix A and B for diagrams. CONSTANT-VOLTAGE POWER: * When specified, regulated (or constant- voltage) power shall be used for both PLC power supplies AND their input modules. All PLC power supplies and input modules, including those in remote racks, shall receive power from
12、this same constant-voltage transformer. It may also be used for peripheral equipment, such as gaging, if required. Output modules shall draw power from the same AC source as the I constant-voltage transformer, but NOT from the secondary of i that transformer. (Refer to PLC manufacturers installation
13、 instructions for details). POWER PROVIDED THROUGH CRM CONTACTS: When the line side LTD option is used, all electrical equipment powered from an external source, and controlled by the PLCs outputs shall receive power through CRM contacts, or an electro- mechanical contactor which is de-energized by
14、CRM. Examples include, but are not limited to: a pick main console is typical. FORD MANUFACTURING STANDARDS mBs_- -_-_=_-c=-_-I-_-I -x=m_ _-_ -= EL3X PROGRAMMABLE CONTROLLERS - APPLICATIONS EL3X DECEMBER 1992 Page 4 . =- -=_=-sz=- -a-=-=- -xc-cc=_ -z=m 2.3.1 MESSAGE DISPLAYS: Where programmable mess
15、age displays are mounted in locations which cannot be accessed while the machinery is operating, such as wireways or enclosures above the line, the same programming provisions as required for PLCs on balconies shall apply. Cable length limitations shall be observed. 2.4 2.5 2.6 2.7 2.8 2.9 Minimum e
16、nclosure depth shall allow for at least 6 inches of clearance from the door surface, or door mounted components to the front of the PLC. ACCESSIBILITY OF EQUIPMENT: PLC equipment shall not be mounted behind a door mullion unless there is adequate space for servicing and replacement of the component.
17、 PROGRAMMING SHELF: f* When specified, a fold-down shelf shall be provided on enclosure doors which cover a PLC or remote communications ports to the PLC. The shelf shall safely support a programming device and related equipment and shall pull upward for use, and be equipped with sliding “gravity lo
18、ck“ braces or other means to prevent accidental collapse. Magnets shall NOT be used anywhere on the shelf. Shelves shall be those furnished by approved enclosure manufacturers or designs approved by the specifying activity. i The PLC shall be installed in the same enclosure with other electrical con
19、trol devices necessary for the operation of the machine or equipment, The PLC may be mounted on a common subplate with the electro-mechanical devices, e.g., motor starters, relays, etc., if such layout is approved by the PLC manufacturer and the specifying activity. Mounting of equipment on hinged p
20、anels, doors, etc., is not acceptable. WIRING multiply the ladder logic file size (in kilobytes) by 1.25 and provide excess memory accordingly. MEMORY FOR CIM: * When specified, the PLC shall contain memory to accommodate CIM/Memory Map requirements, in addition to the spare memory required by secti
21、on 2.11.2. 3. SYSTEM REQUIREMENTS: 3.1 PLC NETWORKS: Peer communications interfaces shall be provided on the PLCs for programming devices to communicate with all PLCs on the peer link network, one PLC at a time, from each PLC location. This same network may be used for data interchange and other fun
22、ctions needed to support CIM. 3.2 3.3 3.3.1 3.3.2 POWER SUPPLY INTERLOCKING: When more than one PLC power supply is used for a system, interlocking shall be provided between them to ensure that a failure which turns off one power supply shall also turn off the others. (Al so see section 2.1.1.5 abov
23、e). MOTION INTERLOCKS a: Inputs (8. Sotck List outputs (9. Auxiliary Diagrams, as required Interlocks for DIP switch settings (or soft- Charts (Sequence ware configuration equivalents), and Cycle Time) etc. Spare numbered sheets shall be assigned in each section for power, inputs, and outputs to acc
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- FORDEL3X1992PROGRAMMABLECONTROLLERSAPPLICATIONS 可编程控制器 应用 PDF

链接地址:http://www.mydoc123.com/p-744812.html